Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA057120R1 SACE Emax E6V5000 three-pole withdrawable air circuit breaker moving part with a 5000 A rated current, PR121/P-LI R5000 electronic protection release and ultimate short-circuit breaking capacity of up to 150 kA.
£56,240.16
The ABB 1SDA057120R1 is a high-performance SACE Emax E6V air circuit breaker moving part designed for protection and switching of high-current low-voltage electrical distribution systems. Part of the ABB New Emax series, the E6V5000 combines a 5000 A current rating with the PR121/P-LI electronic overcurrent release for dependable protection in demanding industrial, commercial and infrastructure power distribution applications.
This three-pole withdrawable circuit breaker moving part is equipped with the PR121/P-LI R5000 electronic trip unit. Its LI protection functions provide long-time overload (L) and instantaneous short-circuit (I) protection, while the withdrawable construction enables the moving part to be isolated and removed from its corresponding fixed part for inspection, maintenance or replacement.
The E6V5000 provides an ultimate short-circuit breaking capacity of up to 150 kA at 220–440 V AC, with 130 kA at 500 V AC and 100 kA at 660–690 V AC. Combined with its 5000 A current capability and high short-time withstand performance, the 1SDA057120R1 is suited to critical distribution systems with substantial prospective fault currents.
Air circuit breakers such as the ABB SACE Emax E6V5000 provide switching and protection for high-current low-voltage distribution circuits. The electronic trip unit monitors electrical conditions and initiates circuit interruption when configured protection thresholds are exceeded, helping protect busbars, cables, transformers and connected equipment against damaging overload and short-circuit currents.
The PR121/P-LI release combines long-time overload and instantaneous short-circuit protection for straightforward and dependable circuit protection. Together with the E6V5000's 5000 A current capability, short-circuit breaking capacity of up to 150 kA and withdrawable moving-part construction, the 1SDA057120R1 is particularly suited to critical installations where high fault-clearing performance and maintainability are required.
| Series | SACE Emax / New Emax |
|---|---|
| Order code | 1SDA057120R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E6 |
| Short-circuit performance level | V |
| Rated current (In) | 5000 A |
| Rated operational current (Ie) | 5000 A |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Trip unit | PR121/P-LI R5000 |
| Trip unit type | Electronic |
| Protection functions | Long-time overload and instantaneous short-circuit protection (LI) |
| Ultimate short-circuit breaking capacity (Icu), 220–440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu), 500 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu), 660–690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics), 220–415 V AC | 150 kA |
| Service short-circuit breaking capacity (Ics), 440 V AC | 125 kA |
| Service short-circuit breaking capacity (Ics), 500–690 V AC | 100 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 85 kA |
| Version | Withdrawable |
| Installation component | Moving part (MP) |
| Terminal connection type | Withdrawable circuit breaker |
| Auxiliary contacts | 4 contacts with open / closed circuit-breaker position indication |
| Power loss | 700 W |
| Electrical durability at Ue ≤ 440 V | 3000 cycles |
| Electrical durability at Ue 500–690 V | 2000 cycles |
| Mechanical durability | 12,000 cycles |
| Maximum electrical operating frequency | 10 cycles per hour |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 810 × 461 × 396.5 mm |
| Net weight | 116 kg |
| EAN | 8015644584603 |
| Customs tariff number | 85362090 |
| Current type | AC |
| Reference standard | IEC |
The ABB 1SDA057120R1 is a 5000 A withdrawable air circuit breaker moving part designed for switching and protection of high-current low-voltage electrical distribution systems.
The E6V5000 has a rated operational and uninterrupted current of 5000 A, making it suitable for major high-capacity power distribution applications.
The circuit breaker is fitted with an electronic ABB PR121/P-LI R5000 overcurrent release providing long-time overload and instantaneous short-circuit protection.
The E6V5000 has an ultimate short-circuit breaking capacity of 150 kA at 220–440 V AC, 130 kA at 500 V AC and 100 kA at 660–690 V AC.
The 1SDA057120R1 is a three-pole withdrawable moving part designed for use with the corresponding fixed part of an ABB SACE Emax E6 withdrawable circuit-breaker installation.
ABB SACE Emax air circuit breakers are engineered for reliable protection and switching in demanding low-voltage power distribution systems, combining high current capacity, electronic protection, robust short-circuit performance and serviceable withdrawable configurations for industrial and infrastructure applications.