Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA057108R1 is a SACE Emax E6V 5000 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSI R5000 electronic release providing long-time, short-time and instantaneous protection.
£56,008.21
The ABB 1SDA057108R1 is a high-performance SACE Emax E6V air circuit breaker designed for protection and switching in demanding high-current low-voltage electrical distribution systems. Rated at 5000 A, this three-pole fixed breaker incorporates an ABB PR122/P-LSI R5000 electronic overcurrent release providing long-time overload, short-time delayed and instantaneous short-circuit protection.
As part of the proven ABB SACE Emax series, the E6V 5000 combines exceptional short-circuit performance with robust fixed switchboard construction. Its rear horizontal terminals provide a practical connection arrangement for permanent integration into industrial, infrastructure, utility and large commercial low-voltage distribution assemblies.
The E6V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC. Combined with a 100 kA short-time withstand current for 1 s, the breaker is well suited to major incoming and feeder circuits with high prospective fault currents.
Air circuit breakers such as the ABB SACE Emax E6V provide switching and overcurrent protection for major low-voltage distribution circuits. The electronic trip unit monitors current conditions and initiates circuit-breaker operation when configured overload or short-circuit thresholds are exceeded, helping protect busbars, cables, transformers and connected electrical equipment.
The PR122/P-LSI release combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection with the exceptional fault-interruption capability of the E6V frame. Its 150 kA Icu at 415 V AC makes this breaker particularly suitable for high-capacity distribution systems where very high prospective short-circuit currents can occur.
| Series | SACE Emax |
|---|---|
| Frame / type | E6V |
| ABB order code | 1SDA057108R1 |
| EAN | 8015644584481 |
| Product type | Air circuit breaker |
| Execution | Fixed |
| Terminal connection | Rear horizontal |
| Number of poles | 3 |
| Rated current (In) | 5000 A |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated operational current (Ie) | 5000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR122/P-LSI R5000 |
| Release type | Electronic |
| Protection functions | LSI – long-time, short-time and instantaneous |
| Overload release setting range | 2000–5000 A |
| Instantaneous short-circuit setting range | 7500–75000 A |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 150 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 100 kA |
| Short-time withstand current (Icw), 1 s | 100 kA |
| Short-time withstand current (Icw), 3 s | 85 kA |
| Earth-fault protection | No |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Motor drive | Optional |
| Power loss | 415 W |
| Electrical durability | 3000 cycles at Ue ≤ 440 V; 2000 cycles at 500–690 V |
| Mechanical durability | 12000 cycles |
| Product net dimensions (W × H × D) | 782 × 418 × 302 mm |
| Product net weight | 112 kg |
| Standard | IEC |
| Product group | 310513-New Emax |
The ABB 1SDA057108R1 is a SACE Emax E6V 5000 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSI R5000 electronic overcurrent release.
The PR122/P-LSI electronic release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E6V 5000 has an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC.
The ABB 1SDA057108R1 has a rated uninterrupted current of 5000 A, making it suitable for major high-current low-voltage distribution circuits.
The 1SDA057108R1 is a fixed circuit breaker equipped with rear horizontal terminals for permanent integration into a compatible low-voltage switchboard.
ABB SACE Emax air circuit breakers are engineered for reliable protection and switching in demanding low-voltage power distribution systems, combining high-current capability, advanced electronic protection and exceptional short-circuit performance.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.