1SDA057008R1 ABB E6H 6300 PR121/P-LI 6300 A 3-Pole Fixed Air Circuit Breaker

1SDA057008R1 ABB E6H 6300 PR121/P-LI 6300 A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA057008R1 is a fixed three-pole 6300 A SACE Emax E6H air circuit breaker with PR121/P-LI electronic protection, rear horizontal terminals and a 100 kA ultimate short-circuit breaking capacity through 690 V AC.

SKU: 1SDA057008R1MPN: 1SDA057008R1
Price
List Price £77,293.30 ex VAT
Your Price (ex VAT) Save 25%
£57,969.98 25% OFF
You save £19,323.33 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £57,969.98
Trade pricing is personalised to your account

Manufacturer Lead Time

£57,969.98

Why Choose the ABB 1SDA057008R1 E6H 6300 Air Circuit Breaker?

The ABB 1SDA057008R1 is a high-capacity SACE Emax E6H 6300 air circuit breaker (ACB) designed for protection and switching in demanding high-current low-voltage electrical distribution systems. Part of the ABB New Emax / SACE Emax range, this three-pole fixed circuit breaker combines a 6300 A rated current with the PR121/P-LI electronic overcurrent release.

The PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. These protection functions help safeguard busbars, conductors, switchgear and connected equipment against sustained overcurrents and severe short-circuit faults in high-capacity electrical distribution installations.

With a rated uninterrupted current of 6300 A, three-pole fixed construction and rear flat horizontal terminals, the 1SDA057008R1 is engineered for permanent integration into high-current switchboards. The E6H performance level provides rated ultimate and service short-circuit breaking capacities of 100 kA from 220–690 V AC, together with a short-time withstand capability of 100 kA for 1 s.

Key Advantages

  • Very high 6300 A current rating for demanding low-voltage power-distribution systems.
  • Three-pole fixed configuration for permanent high-current switchboard installations.
  • PR121/P-LI R6300 electronic overcurrent release with long-time and instantaneous protection.
  • 100 kA ultimate short-circuit breaking capacity from 220–690 V AC.
  • 100 kA service short-circuit breaking capacity from 220–690 V AC.
  • 100 kA short-time withstand current for 1 s for demanding distribution applications.
  • Rear flat horizontal terminals support integration with suitable high-current busbar systems.
  • Four auxiliary contacts provide circuit-breaker open/closed status indication.

Key Features

  • ABB SACE Emax E6H 6300 series.
  • 6300 A rated uninterrupted current.
  • Three-pole circuit-breaker configuration.
  • Fixed installation version.
  • PR121/P-LI R6300 electronic overcurrent release.
  • Long-time (L) overload protection.
  • Instantaneous (I) short-circuit protection.
  • 100 kA Icu and Ics from 220–690 V AC.
  • 100 kA short-time withstand current for 1 s.
  • 85 kA short-time withstand current for 3 s.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 690 V AC rated operational voltage.
  • Rear flat horizontal main terminals.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

High-Current Protection for Critical Power Distribution

Air circuit breakers such as the ABB SACE Emax E6H provide switching and protection for high-current low-voltage distribution networks. The electronic trip release monitors electrical conditions and initiates circuit interruption when configured protection thresholds are exceeded, helping protect switchgear, cables, busbars and connected equipment against potentially damaging overload and short-circuit conditions.

The PR121/P-LI release combines long-time overload protection with instantaneous short-circuit protection. Together with the E6H circuit breaker's 6300 A current rating, 100 kA ultimate and service breaking capacities through 690 V AC and robust fixed construction, the 1SDA057008R1 is particularly suitable for high-capacity main distribution and industrial installations requiring dependable fault interruption.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • High-current industrial power distribution systems.
  • Manufacturing and process plants.
  • Large commercial and infrastructure electrical installations.
  • Transformer secondary circuit protection.
  • Main incomer protection.
  • High-current feeder protection.
  • Generator and installation protection systems.
  • Electrical installations with high prospective short-circuit currents.

Technical Specifications

Series SACE Emax / New Emax
ABB order code 1SDA057008R1
Product type Air circuit breaker
Product group 310513-New Emax
Frame / performance level E6H
Rated current (In) 6300 A
Rated operational current (Ie) 6300 A
Rated uninterrupted current (Iu) 6300 A
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu), 220–690 V AC 100 kA
Rated service short-circuit breaking capacity (Ics), 220–690 V AC 100 kA
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 85 kA
Number of poles 3
Current type AC
Protection release PR121/P-LI R6300
Release type Electronic
Protection functions L and I
Long-time overload protection Integrated
Instantaneous short-circuit protection Integrated
Installation version Fixed
Terminal connection Rear flat horizontal
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 650 W
Electrical durability 2000 cycles at ≤440 V AC; 1500 cycles at 500–690 V AC
Mechanical durability 12000 cycles
Product net dimensions (W × H × D) 782 × 418 × 302 mm
Product net weight 112 kg
EAN 8015644583484
HS code 85362090
Standards IEC

Frequently Asked Questions

What is the ABB 1SDA057008R1 used for?

The ABB 1SDA057008R1 is a 6300 A three-pole air circuit breaker designed for switching and protection in high-current low-voltage electrical distribution systems, including main incomers, transformer secondary circuits and high-capacity feeders.

What protection release is fitted to the ABB 1SDA057008R1?

The circuit breaker is fitted with an ABB PR121/P-LI R6300 electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection.

What is the short-circuit breaking capacity of the ABB E6H 6300?

The E6H 6300 has rated ultimate and service short-circuit breaking capacities of 100 kA across operating voltages from 220 V to 690 V AC.

What is the short-time withstand current of the ABB 1SDA057008R1?

The E6H 6300 has a rated short-time withstand current of 100 kA for 1 s and 85 kA for 3 s.

Is the ABB 1SDA057008R1 fixed or withdrawable?

The 1SDA057008R1 is a fixed three-pole air circuit breaker with rear flat horizontal terminals for permanent integration into a compatible low-voltage switchboard.

Trusted High-Current Circuit Protection

ABB SACE Emax E6H air circuit breakers are engineered for demanding low-voltage power-distribution applications, combining very high current-carrying capability, electronic overcurrent protection and robust short-circuit performance for industrial, commercial and infrastructure electrical systems.