Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056932R1 E4V4000 PR122/P-LSI is a 4000 A three-pole withdrawable SACE Emax air circuit breaker moving part with electronic LSI protection and high short-circuit performance for demanding low-voltage power distribution systems.
£37,327.54
The ABB 1SDA056932R1, extended product type E4V4000PR122/P-LSIIn=4000A3pWMP, is a high-performance SACE Emax air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax E4V series, this three-pole withdrawable unit combines a 4000 A current rating with the PR122/P-LSI R4000 electronic overcurrent release.
The E4V4000 is engineered for high-current industrial, commercial and infrastructure power distribution applications where dependable overload and short-circuit protection is essential. Its PR122/P-LSI electronic trip unit provides long-time, short-time and instantaneous protection functions, helping safeguard switchgear, cables and connected electrical equipment while supporting selective coordination within complex distribution networks.
With a rated uninterrupted current of 4000 A, rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 150 kA at 400 V AC, the E4V4000 delivers substantial fault-clearing performance. This version is a three-pole withdrawable moving part designed for use with a compatible SACE Emax fixed part and is supplied with four auxiliary contacts and open/closed circuit-breaker position indication.
Air circuit breakers such as the ABB SACE Emax E4V4000 protect low-voltage distribution networks by interrupting potentially damaging currents when overload or short-circuit conditions occur. The E4V platform combines a high continuous current rating with substantial short-circuit performance, making it suitable for main switchboards, industrial distribution systems and critical installations where high prospective fault currents must be safely controlled.
The PR122/P-LSI electronic release provides three complementary protection functions. Long-time protection responds to sustained overloads, short-time protection supports selective coordination between protective devices, and instantaneous protection provides rapid interruption during severe short-circuit faults. The withdrawable construction allows the circuit-breaker moving part to be disconnected and removed from its compatible fixed section, supporting inspection, servicing and replacement in critical switchgear installations.
| Series | SACE Emax E4V |
|---|---|
| ABB product group | 310513-New Emax |
| ABB order code | 1SDA056932R1 |
| Extended product type | E4V4000PR122/P-LSIIn=4000A3pWMP |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 4000 A |
| Rated operational current (Ie) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Version | Withdrawable |
| Component type | Moving part |
| Trip unit | PR122/P-LSI R4000 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Short-circuit performance level | V |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 150 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 130 kA |
| Rated service short-circuit breaking capacity (Ics) at 660–690 V AC | 100 kA |
| Rated short-time withstand current (Icw) | 100 kA for 1 s; 75 kA for 3 s |
| Mechanical durability | 15,000 cycles |
| Electrical durability at 500–690 V | 4,000 cycles |
| Power loss | 660 W |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Weight | approx. 100 kg |
| EAN | 8015644582722 |
| HS code | 85362090 |
| Standard | IEC |
The ABB 1SDA056932R1 is a SACE Emax E4V withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.
The E4V4000 has a rated uninterrupted current of 4000 A, making it suitable for substantial industrial, commercial and infrastructure power distribution applications.
The PR122/P-LSI electronic overcurrent release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection functions.
The E4V4000 provides an ultimate and service short-circuit breaking capacity of 150 kA at 400 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC.
The 1SDA056932R1 is a three-pole withdrawable moving part designed for use with the corresponding ABB SACE Emax fixed part, allowing removal for servicing, inspection or replacement.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance with electronic overcurrent protection for industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.