1SDA056922R1 ABB E4V4000 PR121/P-LSIG 4000 A 4-Pole Fixed Air Circuit Breaker

1SDA056922R1 ABB E4V4000 PR121/P-LSIG 4000 A 4-Pole Fixed Air Circuit Breaker

ABB 1SDA056922R1 E4V4000 is a 4000 A four-pole fixed SACE Emax air circuit breaker with a PR121/P-LSIG electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection for demanding high-current low-voltage power distribution systems.

SKU: 1SDA056922R1MPN: 1SDA056922R1
Price
List Price £49,510.32 ex VAT
Your Price (ex VAT) Save 25%
£37,132.74 25% OFF
You save £12,377.58 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £37,132.74
Trade pricing is personalised to your account

Manufacturer Lead Time

£37,132.74

Why Choose the ABB E4V4000 PR121/P-LSIG Air Circuit Breaker?

The ABB 1SDA056922R1 is a high-performance SACE Emax E4V air circuit breaker designed for switching and comprehensive protection in high-current low-voltage electrical distribution systems. Identified as E4V4000 PR121/P-LSIG, this four-pole fixed circuit breaker combines a 4000 A rated current with ABB's PR121/P-LSIG R4000 electronic overcurrent release.

As part of the ABB SACE Emax / New Emax range, the E4V4000 is engineered for installations with very high prospective fault currents. Its V short-circuit performance level provides ultimate and service short-circuit breaking capacities of 150 kA at 400 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC. The fixed construction with rear horizontal terminals provides a robust arrangement for permanent integration into compatible low-voltage switchboards.

The integrated PR121/P-LSIG R4000 electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. With a rated operational voltage of 690 V AC, four-pole configuration and 4000 A rated uninterrupted current, the 1SDA056922R1 is well suited to critical main incoming, feeder and distribution protection duties requiring very high breaking capacity and comprehensive electronic protection.

Key Advantages

  • High-capacity 4000 A air circuit breaker for demanding low-voltage power distribution.
  • Four-pole configuration suitable for three-phase four-wire electrical systems.
  • PR121/P-LSIG R4000 electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection.
  • Exceptional 150 kA Icu and Ics at 400 V AC short-circuit breaking performance.
  • Maintains 130 kA Icu and Ics at 500 V AC and 100 kA Icu and Ics at 690 V AC.
  • 100 kA short-time withstand current for 1 s and 75 kA for 3 s.
  • Fixed construction with rear horizontal terminals for permanent switchboard installation.
  • Fitted with four auxiliary contacts and circuit breaker open/closed position indication.

Key Features

  • ABB SACE Emax E4V series.
  • 4000 A rated operational and uninterrupted current.
  • Four-pole circuit breaker configuration.
  • PR121/P-LSIG R4000 electronic overcurrent release.
  • Long-time overload (L) protection.
  • Short-time short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • Ground-fault (G) protection.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 150 kA Icu and Ics at 400 V AC.
  • 130 kA Icu and Ics at 500 V AC.
  • 100 kA Icu and Ics at 690 V AC.
  • Fixed design with rear horizontal terminals.

Very High Breaking Capacity with Comprehensive LSIG Protection

The ABB E4V4000 is designed for substantial low-voltage distribution systems where exceptionally high prospective fault currents require robust interruption capability. Its V performance level delivers ultimate and service short-circuit breaking capacities of 150 kA from 220–440 V AC, 130 kA at 500 V AC and 100 kA at 660–690 V AC, together with short-time withstand capabilities of 100 kA for 1 s and 75 kA for 3 s.

The PR121/P-LSIG electronic release combines long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. This comprehensive protection arrangement helps protect conductors, busbars, switchgear and connected equipment against multiple electrical fault conditions. Combined with its 4000 A rating and four-pole fixed construction, the 1SDA056922R1 is suited to critical power distribution systems where high breaking performance and integrated ground-fault protection are required.

Typical Applications

  • Main incoming circuit protection in high-current low-voltage switchboards.
  • Three-phase four-wire electrical distribution systems.
  • Industrial power distribution systems with very high prospective fault currents.
  • Transformer secondary distribution and protection.
  • Protection of high-current distribution feeders and busbar systems.
  • Electrical systems requiring integrated ground-fault protection.
  • Large commercial, infrastructure and manufacturing installations.
  • High-fault-level switchgear and critical power distribution assemblies.

Technical Specifications

Series SACE Emax / New Emax
Product group 310513-New Emax
Extended product type E4V4000PR121/P-LSIGIn=4000A4pFHR
ABB order code 1SDA056922R1
Product type Air circuit breaker
Frame E4
Short-circuit performance level V
Rated current (In) 4000 A
Rated operational current (Ie) 4000 A
Rated uninterrupted current (Iu) 4000 A
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 4
Current type AC
Trip unit PR121/P-LSIG
Trip unit rating R4000
Trip unit type Electronic
Protection functions L, S, I and G
Ultimate short-circuit breaking capacity (Icu) at 220 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 220 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 230 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 230 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 380 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 380 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 400 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 415 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 440 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 130 kA
Service short-circuit breaking capacity (Ics) at 500 V AC 130 kA
Ultimate short-circuit breaking capacity (Icu) at 660 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 660 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 100 kA
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 75 kA
Installation type Fixed
Terminal connection Rear horizontal
Version F
Auxiliary contacts 4
Position indication Open / closed
Mechanical endurance 15,000 operations
Electrical endurance at ≤440 V AC 5,000 operations
Electrical endurance at 500–690 V AC 4,000 operations
Power loss 360 W
Dimensions (W × H × D) 656 × 418 × 302 mm
Net weight 92 kg
Standard IEC
EAN 8015644582623
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA056922R1 used for?

The ABB 1SDA056922R1 is a 4000 A four-pole fixed air circuit breaker used for switching and protecting high-current low-voltage electrical distribution systems, particularly where very high short-circuit breaking capacity is required.

What trip unit is fitted to the ABB E4V4000?

This circuit breaker is fitted with the ABB PR121/P-LSIG R4000 electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.

What does LSIG mean on the PR121/P-LSIG trip unit?

LSIG denotes long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection, providing comprehensive protection against multiple electrical fault conditions.

What is the breaking capacity of the ABB E4V4000?

The E4V4000 has ultimate and service short-circuit breaking capacities of 150 kA at 400 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC, together with rated short-time withstand currents of 100 kA for 1 s and 75 kA for 3 s.

Is the ABB 1SDA056922R1 fixed or withdrawable?

The 1SDA056922R1 is a fixed four-pole SACE Emax air circuit breaker with rear horizontal terminals, designed for permanent installation within compatible low-voltage switchboards and distribution assemblies.

Trusted ABB Power Distribution Protection

ABB SACE Emax air circuit breakers are designed for demanding low-voltage power distribution applications, combining very high breaking performance, comprehensive electronic trip protection and robust construction for dependable high-current electrical system protection.