ABB 1SDA056917R1 E4V4000 PR122/P-LSIG is a 4000 A three-pole fixed SACE Emax air circuit breaker with electronic LSIG protection, rear horizontal terminals and a 150 kA breaking capacity at 400 V AC.
£30,780.47
The ABB 1SDA056917R1, extended product type E4V4000PR122/P-LSIGIn=4000A3pFHR, is a high-performance SACE Emax air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax E4V series, this three-pole fixed circuit breaker combines a 4000 A current rating with the advanced PR122/P-LSIG electronic overcurrent release.
The E4V4000 is engineered for high-current industrial and commercial power distribution applications where comprehensive protection against overloads, short circuits and earth faults is required. Its PR122/P-LSIG R4000 electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection functions, helping safeguard switchgear, cables and connected equipment while supporting selective protection within complex electrical distribution networks.
With a rated uninterrupted current of 4000 A, rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 150 kA at 400 V AC, the E4V4000 is suited to substantial power distribution installations with high prospective fault currents. This model features a three-pole fixed configuration with rear horizontal terminals and is fitted with four auxiliary change-over contacts plus circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E4V4000 protect low-voltage distribution networks by interrupting potentially damaging currents when abnormal operating conditions occur. The E4V platform combines a high continuous current rating with substantial short-circuit breaking performance, making it suitable for main switchboards, industrial distribution systems and installations where high prospective fault currents must be safely controlled.
The PR122/P-LSIG electronic release provides four complementary protection functions. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during fault conditions, instantaneous protection provides rapid interruption of severe short circuits, and ground-fault protection helps protect the installation against earth-fault currents. Its fixed three-pole construction and rear horizontal terminals enable integration into high-capacity low-voltage switchgear assemblies.
| Series | SACE Emax E4V |
|---|---|
| ABB product group | 310513-New Emax |
| ABB order code | 1SDA056917R1 |
| Extended product type | E4V4000PR122/P-LSIGIn=4000A3pFHR |
| Product type | Air circuit breaker |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated operational current (Ie) | 4000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Version | Fixed |
| Terminal configuration | Rear horizontal |
| Trip unit | PR122/P-LSIG R4000 |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Overload release adjustment range | 1600–4000 A |
| Instantaneous short-circuit release adjustment range | 6000–60000 A |
| Integrated earth-fault protection | Yes |
| Short-circuit performance level | V |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 150 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 130 kA |
| Rated service short-circuit breaking capacity (Ics) at 660–690 V AC | 100 kA |
| Rated short-time withstand current (Icw) | 100 kA for 1 s; 75 kA for 3 s |
| Power loss | 360 W |
| Mechanical durability | 15,000 cycles |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open/closed |
| Motor drive | Optional |
| Weight | approx. 95 kg |
| EAN | 8015644582579 |
| Standard | IEC |
The ABB 1SDA056917R1 is a SACE Emax E4V air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems, including transformer, generator and installation protection applications.
The E4V4000 has a rated uninterrupted current of 4000 A, making it suitable for substantial industrial, commercial and infrastructure power distribution applications.
The PR122/P-LSIG electronic overcurrent release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection functions.
The E4V4000 has a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 130 kA at 500 V AC and 100 kA at 690 V AC.
The 1SDA056917R1 is a three-pole fixed air circuit breaker equipped with rear horizontal terminals.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance with advanced electronic protection for industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.