1SDA056883R1 ABB E4V3200PR122/P-LI 3200A 3-Pole Air Circuit Breaker

1SDA056883R1 ABB E4V3200PR122/P-LI 3200A 3-Pole Air Circuit Breaker

ABB 1SDA056883R1 E4V3200PR122/P-LI is a 3200 A three-pole fixed SACE Emax air circuit breaker with rear horizontal terminals, a PR122/P-LI R3200 electronic release and 150 kA breaking capacity at 400/415 V AC.

SKU: 1SDA056883R1MPN: 1SDA056883R1
Price
List Price £30,307.66 ex VAT
Your Price (ex VAT) Save 25%
£22,730.75 25% OFF
You save £7,576.92 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £22,730.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£22,730.75

Why Choose the ABB E4V3200PR122/P-LI 3200A Air Circuit Breaker?

The ABB E4V3200PR122/P-LI, order code 1SDA056883R1, is a high-performance 3200 A three-pole air circuit breaker designed for demanding low-voltage power distribution systems. Part of the ABB SACE Emax E4 series, this fixed breaker combines the E4V very-high short-circuit performance class with a PR122/P electronic overcurrent protection release.

The breaker is equipped with an ABB PR122/P-LI R3200 electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection. Its electronic protection system is suited to main incomers, transformer secondary circuits and high-current feeders where accurate overload protection and rapid interruption of severe short-circuit faults are required.

With a rated uninterrupted current of 3200 A, a three-pole fixed configuration and rear horizontal terminals, the E4V3200PR122/P-LI is engineered for permanent integration into high-capacity low-voltage switchgear. The E4V performance class provides an ultimate short-circuit breaking capacity of 150 kA at 400/415 V AC and 100 kA at 690 V AC, making it suitable for networks with exceptionally high prospective fault currents.

Key Advantages

  • High-capacity 3200 A air circuit breaker for demanding low-voltage power distribution.
  • Three-pole fixed configuration for permanent switchboard installation.
  • Rear horizontal terminals for integration with compatible switchgear busbar systems.
  • Advanced PR122/P-LI R3200 electronic protection release.
  • Long-time overload and instantaneous short-circuit protection.
  • Exceptional 150 kA Icu at 400/415 V AC.
  • Maintains 100 kA breaking capacity at 690 V AC.
  • 100 kA short-time withstand current for 1 s for demanding fault conditions.
  • Fitted with four auxiliary contacts for signalling and control.
  • Part of the established ABB SACE Emax air circuit breaker platform.

Key Features

  • ABB SACE Emax E4V air circuit breaker platform.
  • 3200 A rated uninterrupted current.
  • Three-pole construction.
  • Fixed (F) breaker execution.
  • Rear horizontal (HR) terminal connection.
  • PR122/P-LI R3200 electronic overcurrent release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • 690 V AC rated operational voltage.
  • 150 kA Icu and Ics at 400/415 V AC.
  • 130 kA Icu and Ics at 500 V AC.
  • 100 kA Icu and Ics at 660/690 V AC.
  • 100 kA Icw for 1 s and 75 kA Icw for 3 s.
  • 1000 V rated insulation voltage and 12 kV impulse withstand voltage.
  • Four auxiliary contacts and breaker open/closed position indication.

Reliable Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E4 protect low-voltage electrical networks against damaging overcurrents while providing dependable switching and isolation of high-current circuits. The E4V performance class delivers exceptionally high fault-interruption capability, making it suitable for main incomers, transformer secondaries and major feeders where very high prospective short-circuit currents can occur.

The PR122/P electronic release continuously monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded. In this LI configuration, long-time protection responds to sustained overload conditions while instantaneous protection provides rapid interruption of severe short-circuit faults.

Typical Applications

  • Main low-voltage switchboards and power distribution assemblies.
  • Industrial high-current power distribution systems.
  • Transformer secondary and main incomer protection.
  • Large feeder and busbar circuits.
  • Networks with exceptionally high prospective short-circuit currents.
  • Manufacturing and process plant electrical systems.
  • Data centres and mission-critical electrical infrastructure.
  • Commercial buildings, utilities and critical infrastructure installations.

Technical Specifications

Series SACE Emax E4
ABB order code 1SDA056883R1
Product group 310513-New Emax
Product type Air circuit breaker
Frame / performance class E4V 3200
Short-circuit performance level V
Rated current (In) 3200 A
Rated uninterrupted current (Iu) 3200 A
Rated operational current (Ie) 3200 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Current type AC
Execution Fixed (F)
Terminal connection Rear horizontal (HR)
Protection release PR122/P-LI R3200 electronic overcurrent release
Release type Electronic
Protection functions L (long-time) and I (instantaneous)
Overload release setting range 1280–3200 A
Instantaneous short-circuit release adjustment range 4800–48000 A
Ultimate short-circuit breaking capacity (Icu) at 220/230 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 380/400 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 130 kA
Ultimate short-circuit breaking capacity (Icu) at 660/690 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 400/415 V AC 150 kA
Service short-circuit breaking capacity (Ics) at 500 V AC 130 kA
Service short-circuit breaking capacity (Ics) at 660/690 V AC 100 kA
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 75 kA
Power loss 235 W
Electrical durability at Ue ≤ 440 V 7000 cycles
Electrical durability at Ue 500–690 V 7000 cycles
Mechanical durability 15000 cycles
Auxiliary contacts 4
Position indication Open / closed circuit-breaker indication
Motor drive Optional
Standard IEC
Net weight 95 kg
EAN 8015644582234
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB E4V3200PR122/P-LI used for?

This ABB SACE Emax air circuit breaker is designed for switching and protecting high-current low-voltage distribution circuits where very high short-circuit interruption capability and electronic LI protection are required.

What is the rated current of ABB 1SDA056883R1?

The ABB 1SDA056883R1 has a rated uninterrupted current of 3200 A and uses a three-pole fixed E4V air circuit breaker configuration.

What protection release is fitted to ABB 1SDA056883R1?

The breaker is fitted with an ABB PR122/P-LI R3200 electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection.

What is the short-circuit breaking capacity of the E4V3200?

The E4V3200 provides an ultimate short-circuit breaking capacity of 150 kA at 400/415 V AC, 130 kA at 500 V AC and 100 kA at 660/690 V AC.

What type of installation and terminals does ABB 1SDA056883R1 use?

The ABB 1SDA056883R1 is a three-pole fixed air circuit breaker with rear horizontal terminals, designed for permanent integration into compatible low-voltage switchgear assemblies.

Trusted for Critical Power Distribution

ABB SACE Emax air circuit breakers are engineered for dependable protection, switching and control of demanding low-voltage electrical distribution systems, combining high-current capability, exceptional short-circuit performance and advanced electronic protection technology.