ABB 1SDA056853R1 E4H4000PR122/P-LSIG is a 4000 A three-pole fixed SACE Emax air circuit breaker with rear horizontal terminals, a PR122/P-LSIG R4000 electronic release and 100 kA breaking capacity at 400/415 V AC.
£29,377.59
The ABB E4H4000PR122/P-LSIG, order code 1SDA056853R1, is a high-performance 4000 A three-pole air circuit breaker designed for demanding low-voltage power distribution systems. Part of the proven ABB SACE Emax E4 series, this fixed breaker combines the E4H high short-circuit performance level with the advanced PR122/P electronic overcurrent protection release.
The breaker is equipped with an ABB PR122/P-LSIG R4000 electronic overcurrent release, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. This comprehensive LSIG protection package supports selective coordination while protecting cables, busbars, transformers and downstream equipment against overloads, phase faults and earth faults.
With a rated uninterrupted current of 4000 A, a three-pole fixed configuration and rear horizontal terminals, the E4H4000PR122/P-LSIG is engineered for permanent installation in high-capacity low-voltage switchgear. The E4H performance class provides an ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC, retaining 85 kA at 690 V AC for demanding distribution networks.
Air circuit breakers such as the ABB SACE Emax E4 protect low-voltage electrical networks against damaging overcurrents while providing dependable switching and isolation of high-current circuits. The E4H performance class offers high fault-interruption capability, making it suitable for main incomers, transformer secondaries, large feeders and other circuits where substantial prospective short-circuit currents can occur.
The PR122/P electronic release continuously monitors circuit conditions and initiates breaker operation when configured protection thresholds are exceeded. In this LSIG configuration, long-time protection responds to sustained overloads, short-time protection supports selective short-circuit coordination, instantaneous protection rapidly interrupts severe faults, and earth-fault protection provides additional protection against ground-fault conditions.
| Series | SACE Emax E4 |
|---|---|
| ABB order code | 1SDA056853R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Frame / performance class | E4H 4000 |
| Short-circuit performance level | H |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated operational current (Ie) | 4000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Current type | AC |
| Execution | Fixed (F) |
| Terminal connection | Rear horizontal (HR) |
| Protection release | PR122/P-LSIG R4000 electronic overcurrent release |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous) and G (earth-fault) |
| Ultimate short-circuit breaking capacity (Icu) at 220/230 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380/400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660/690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400/415 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 660/690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 75 kA |
| Power loss | 360 W |
| Electrical durability at Ue ≤ 440 V | 5000 cycles |
| Electrical durability at Ue 500–690 V | 4000 cycles |
| Mechanical durability | 15000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed breaker indication |
| Standard | IEC |
| Dimensions (W × H × D) | 566 × 418 × 302 mm |
| Net weight | 81 kg |
| EAN | 8015644581930 |
| HS code | 85362090 |
This ABB SACE Emax air circuit breaker is designed for switching and protecting high-current low-voltage distribution systems requiring high short-circuit performance and comprehensive electronic LSIG protection.
The ABB 1SDA056853R1 has a rated uninterrupted current of 4000 A and uses a three-pole fixed E4H air circuit breaker configuration.
The breaker is fitted with an ABB PR122/P-LSIG R4000 electronic overcurrent release, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.
The E4H4000 provides an ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC. The rating remains 100 kA through 500 V AC and is 85 kA at 660–690 V AC.
The ABB 1SDA056853R1 is a three-pole fixed air circuit breaker with rear horizontal terminals, designed for permanent integration into compatible low-voltage switchgear assemblies.
ABB SACE Emax air circuit breakers are engineered for dependable protection, switching and control of demanding low-voltage electrical distribution systems, combining high-current capability, high short-circuit performance and advanced electronic protection technology.