1SDA056839R1 ABB E4H3200PR123/P-LSIG 3200A 3-Pole Air Circuit Breaker Moving Part

1SDA056839R1 ABB E4H3200PR123/P-LSIG 3200A 3-Pole Air Circuit Breaker Moving Part

ABB 1SDA056839R1 E4H3200PR123/P-LSIG is a 3200 A three-pole withdrawable SACE Emax air circuit breaker moving part with a PR123/P-LSIG R3200 electronic release providing long-time, short-time, instantaneous and earth-fault protection.

SKU: 1SDA056839R1MPN: 1SDA056839R1
Price
List Price £43,697.64 ex VAT
Your Price (ex VAT) Save 25%
£32,773.23 25% OFF
You save £10,924.41 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £32,773.23
Trade pricing is personalised to your account

Manufacturer Lead Time

£32,773.23

Why Choose the ABB E4H3200PR123/P-LSIG 3200A Air Circuit Breaker?

The ABB E4H3200PR123/P-LSIG, order code 1SDA056839R1, is a high-performance 3200 A three-pole air circuit breaker moving part designed for demanding low-voltage power distribution systems. Part of the proven ABB SACE Emax E4 series, this withdrawable configuration combines the E4H high short-circuit performance level with the advanced PR123/P electronic overcurrent protection release.

The breaker is equipped with an ABB PR123/P-LSIG R3200 electronic overcurrent release, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. The PR123/P is an advanced Emax protection release designed for sophisticated protection and coordination requirements in critical electrical distribution networks.

With a rated uninterrupted current of 3200 A, a three-pole withdrawable moving-part configuration and E4H high fault-interruption capability, the E4H3200PR123/P-LSIG is engineered for installations where protection performance, maintainability and continuity of service are critical. Its withdrawable construction allows the moving part to be isolated and removed from the corresponding fixed part for inspection, maintenance or replacement.

Key Advantages

  • High-capacity 3200 A air circuit breaker moving part for demanding low-voltage distribution systems.
  • Three-pole withdrawable configuration supports convenient servicing, inspection and replacement.
  • Advanced PR123/P-LSIG R3200 electronic protection release.
  • Comprehensive long-time, short-time, instantaneous and earth-fault protection.
  • High 100 kA ultimate short-circuit breaking capacity at 400/415 V AC.
  • Breaking capacity remains 85 kA at 690 V AC.
  • 100 kA short-time withstand current for 1 s for demanding fault conditions.
  • Fitted with four auxiliary contacts for signalling and control.
  • Integrated open/closed breaker position indication.
  • Part of the established ABB SACE Emax air circuit breaker platform.

Key Features

  • ABB SACE Emax E4H air circuit breaker platform.
  • 3200 A rated uninterrupted current.
  • Three-pole construction.
  • Withdrawable moving part (W MP) configuration.
  • PR123/P-LSIG R3200 electronic overcurrent release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • Earth-fault protection.
  • 100 kA Icu at 400/415 V AC.
  • 100 kA Icu at 500 V AC.
  • 85 kA Icu at 690 V AC.
  • 100 kA Icw for 1 s.
  • 75 kA Icw for 3 s.
  • Four auxiliary contacts and breaker open/closed position indication.
  • Designed for use with the corresponding E4H withdrawable fixed part.

Reliable Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E4 protect low-voltage electrical networks against damaging overcurrents while providing dependable switching and isolation of high-current circuits. The E4H performance class offers particularly high fault-interruption capability, making it suitable for main incomers, transformer secondaries, large feeders and other circuits where substantial prospective short-circuit currents can occur.

The PR123/P electronic release continuously monitors electrical conditions and initiates breaker operation when configured protection thresholds are exceeded. In this LSIG configuration, long-time protection responds to sustained overloads, short-time protection supports selective short-circuit coordination, instantaneous protection rapidly interrupts severe faults, and earth-fault protection provides an additional layer of protection against ground-fault conditions.

Typical Applications

  • Main low-voltage switchboards and power distribution assemblies.
  • Industrial high-current power distribution systems.
  • Transformer secondary and main incomer protection.
  • Large feeder circuits requiring selective protection.
  • Distribution systems requiring integrated earth-fault protection.
  • Networks with high prospective short-circuit currents.
  • Manufacturing and process plant electrical systems.
  • Commercial buildings, utilities and critical infrastructure installations.

Technical Specifications

Series SACE Emax E4
ABB order code 1SDA056839R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Frame / performance class E4H 3200
Short-circuit performance level H
Rated current (In) 3200 A
Rated uninterrupted current (Iu) 3200 A
Number of poles 3
Current type AC
Execution Withdrawable moving part (W MP)
Protection release PR123/P-LSIG R3200 electronic overcurrent release
Release type Electronic
Protection functions L (long-time), S (short-time), I (instantaneous) and G (earth-fault)
Ultimate short-circuit breaking capacity (Icu) at 220/230 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 380/400 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 660/690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 75 kA
Electrical durability at Ue ≤ 440 V 7000 cycles
Electrical durability at Ue 500–690 V 7000 cycles
Mechanical durability 15000 cycles
Auxiliary contacts 4
Position indication Open / closed breaker indication
Standard IEC
Dimensions (W × H × D) 594 × 461 × 396.5 mm
Net weight 85 kg
EAN 8015644581794
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB E4H3200PR123/P-LSIG used for?

This ABB SACE Emax air circuit breaker moving part is designed for protecting high-current low-voltage distribution systems requiring high short-circuit performance and advanced electronic LSIG protection.

What is the rated current of ABB 1SDA056839R1?

The ABB 1SDA056839R1 has a rated uninterrupted current of 3200 A and is a three-pole withdrawable moving part for the E4H air circuit breaker system.

What protection release is fitted to ABB 1SDA056839R1?

The breaker is fitted with an ABB PR123/P-LSIG R3200 electronic overcurrent release, providing long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

What is the short-circuit breaking capacity of the E4H3200?

The E4H3200 provides an ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC. The rating remains 100 kA through 500 V AC and is 85 kA at 660–690 V AC.

Is ABB 1SDA056839R1 a withdrawable breaker?

Yes. ABB order code 1SDA056839R1 is the three-pole withdrawable moving part of the E4H 3200 A air circuit breaker and is designed for use with the corresponding fixed part.

Trusted for Critical Power Distribution

ABB SACE Emax air circuit breakers are engineered for dependable protection, switching and control of demanding low-voltage electrical distribution systems, combining high-current capability, high short-circuit performance and advanced electronic protection technology.