1SDA056813R1 ABB E4S4000 PR122/P-LSIG 4000A 4P Withdrawable Air Circuit Breaker Moving Part

1SDA056813R1 ABB E4S4000 PR122/P-LSIG 4000A 4P Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA056813R1 E4S4000 PR122/P-LSIG is a 4000 A four-pole withdrawable SACE Emax air circuit breaker moving part with a PR122/P-LSIG R4000 electronic release providing long-time, short-time, instantaneous and earth-fault protection.

SKU: 1SDA056813R1MPN: 1SDA056813R1
Price
List Price £52,651.91 ex VAT
Your Price (ex VAT) Save 25%
£39,488.93 25% OFF
You save £13,162.98 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £39,488.93
Trade pricing is personalised to your account

Manufacturer Lead Time

£39,488.93

Why Choose the ABB E4S4000 PR122/P-LSIG 4000A 4P Withdrawable Air Circuit Breaker?

The ABB E4S4000 PR122/P-LSIG, order code 1SDA056813R1, is a high-performance SACE Emax E4S air circuit breaker moving part designed for protection and switching in high-current low-voltage electrical distribution systems. Rated at 4000 A, this four-pole withdrawable configuration combines the robust ABB SACE Emax platform with a PR122/P-LSIG R4000 electronic overcurrent release.

The PR122/P-LSIG release provides long-time (L), short-time (S), instantaneous (I) and earth-fault (G) protection, delivering comprehensive protection against overload, short-circuit and earth-fault conditions. The electronic protection platform supports dependable and selective protection for main distribution switchboards, industrial power systems and other high-capacity installations.

This version is supplied as the four-pole withdrawable moving part of the E4S4000 circuit breaker and is designed for use with the corresponding ABB SACE Emax fixed part. It is rated for 4000 A continuous current and 690 V AC operation, with 75 kA ultimate and service short-circuit breaking capacity across its specified AC voltage range.

Key Advantages

  • High-current 4000 A SACE Emax E4S circuit breaker moving part for demanding low-voltage distribution.
  • Four-pole configuration provides switching and protection across four conductors.
  • PR122/P-LSIG electronic overcurrent release provides L, S, I and G protection functions.
  • Integrated earth-fault protection provides additional protection against ground-fault conditions.
  • Short-time protection supports selective coordination between upstream and downstream protective devices.
  • Withdrawable moving-part construction facilitates inspection, servicing and replacement.
  • 75 kA ultimate and service short-circuit breaking capacity across the specified AC voltage range.
  • Four auxiliary change-over contacts provide circuit-breaker status signalling.

Key Features

  • ABB SACE Emax E4S series.
  • 4000 A rated current.
  • Four-pole circuit-breaker configuration.
  • PR122/P-LSIG R4000 electronic overcurrent release.
  • Long-time overload protection (L).
  • Short-time short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Earth-fault protection (G).
  • Withdrawable moving-part execution.
  • 690 V AC rated operational voltage.
  • 75 kA rated short-time withstand current for 1 s and 3 s.
  • Four auxiliary change-over contacts with open/closed circuit-breaker position indication.

Comprehensive High-Current Protection with Withdrawable Serviceability

Air circuit breakers such as the ABB SACE Emax E4S are designed to protect high-capacity low-voltage distribution systems against damaging overload, short-circuit and earth-fault conditions. The PR122/P-LSIG electronic release combines long-time, short-time, instantaneous and earth-fault protection, helping safeguard busbars, feeders and connected electrical equipment while supporting coordinated system protection.

The withdrawable E4S4000 configuration is particularly suitable for switchboards where serviceability and operational flexibility are important. The circuit-breaker moving part can be withdrawn from its corresponding fixed section for inspection, maintenance or replacement, while its 4000 A rating and 75 kA short-circuit performance make it suitable for substantial industrial, commercial and infrastructure distribution systems.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • High-capacity industrial power distribution systems.
  • Main incoming and high-current feeder protection.
  • Commercial and infrastructure electrical distribution.
  • Manufacturing and process-industry switchgear.
  • Transformer and generator distribution systems.
  • Switchboards requiring withdrawable circuit breakers for improved serviceability.
  • Electrical installations requiring four-pole switching and earth-fault protection.

Technical Specifications

Series SACE Emax E4S
ABB order code 1SDA056813R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Rated current (In) 4000 A
Rated operational current (Ie) 4000 A
Rated uninterrupted current (Iu) 4000 A
Number of poles 4
Execution Withdrawable
Component Moving part
Protection release PR122/P-LSIG R4000
Release technology Electronic
Protection functions Long-time (L), short-time (S), instantaneous (I) and earth-fault (G)
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 75 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 75 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 75 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 75 kA
Service short-circuit breaking capacity (Ics) at 400 V AC 75 kA
Service short-circuit breaking capacity (Ics) at 440 V AC 75 kA
Service short-circuit breaking capacity (Ics) at 500 V AC 75 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 75 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 75 kA
Short-circuit performance level S
Overload release setting range 1600–4000 A
Instantaneous short-circuit release setting range 6000–60000 A
Mechanical endurance 15000 cycles
Electrical endurance at ≤440 V AC 5000 cycles
Electrical endurance at 500–690 V AC 4000 cycles
Power loss 660 W
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Dimensions (W × H × D) 684 × 461 × 396.5 mm
Weight 96 kg
Standard IEC
EAN 8015644581534
HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA056813R1?

The ABB 1SDA056813R1 is the withdrawable moving part of an E4S4000 SACE Emax air circuit breaker rated at 4000 A, with four poles and a PR122/P-LSIG R4000 electronic overcurrent release.

What is the rated current of the E4S4000 PR122/P-LSIG?

The ABB E4S4000 PR122/P-LSIG 1SDA056813R1 has a rated operational and uninterrupted current of 4000 A.

What protection functions does the PR122/P-LSIG release provide?

The PR122/P-LSIG electronic release provides long-time overload protection (L), short-time short-circuit protection (S), instantaneous short-circuit protection (I) and earth-fault protection (G).

Is ABB 1SDA056813R1 fixed or withdrawable?

ABB 1SDA056813R1 is a withdrawable circuit-breaker moving part designed for use with the corresponding ABB SACE Emax fixed part.

What is the rated operational voltage of ABB 1SDA056813R1?

The E4S4000 PR122/P-LSIG has a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V and a rated impulse withstand voltage of 12 kV.

What is the short-circuit breaking capacity of ABB 1SDA056813R1?

The E4S4000 provides rated ultimate and service short-circuit breaking capacities of 75 kA across its specified AC operating-voltage range, including 400 V, 440 V, 500 V and 690 V AC.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax air circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable high-current switching, comprehensive electronic protection and serviceable withdrawable switchgear construction are required.