Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056787R1 E4S4000PR122/P-LI is a 4000 A three-pole fixed SACE Emax air circuit breaker with rear horizontal terminals, PR122/P-LI R4000 electronic protection and a 75 kA breaking capacity up to 690 V AC.
£24,989.75
The ABB E4S4000PR122/P-LI, order code 1SDA056787R1, is a high-performance 4000 A three-pole air circuit breaker designed for reliable switching and protection of demanding low-voltage electrical distribution systems. As part of the proven ABB SACE Emax E4 series, this fixed breaker combines the E4S short-circuit performance class with the advanced PR122/P electronic overcurrent protection release.
The breaker is equipped with an ABB PR122/P-LI R4000 electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection. This combination delivers dependable protection for high-current circuits while supporting integration into industrial switchboards, main distribution assemblies, transformer secondary systems and critical infrastructure.
With a rated current of 4000 A, a three-pole fixed configuration and rear horizontal terminals, the E4S4000PR122/P-LI is engineered for permanent installation in high-capacity low-voltage switchgear. Its E4S performance class provides an ultimate short-circuit breaking capacity of 75 kA at 400/415 V AC, with a rated operational voltage of up to 690 V AC.
Air circuit breakers such as the ABB SACE Emax E4 protect low-voltage electrical networks against damaging overcurrents while providing dependable switching and isolation of high-current circuits. Their robust construction, high short-circuit withstand capability and electronic protection technology make them particularly suitable for main incomers, transformer secondaries, large feeders and other critical power distribution circuits.
The PR122/P electronic release monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded. In this LI configuration, long-time protection responds to sustained overload conditions while instantaneous protection provides rapid interruption of severe short-circuit faults.
| Series | SACE Emax E4 |
|---|---|
| ABB order code | 1SDA056787R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Frame / performance class | E4S 4000 |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated operational current (Ie) | 4000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Current type | AC |
| Execution | Fixed (F) |
| Terminal arrangement | Rear horizontal (HR) |
| Protection release | PR122/P-LI R4000 electronic overcurrent release |
| Protection functions | L (long-time overload) and I (instantaneous short-circuit) |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 75 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 400/415 V AC | 75 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 75 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 75 kA |
| Power loss | 360 W |
| Electrical durability at Ue ≤ 440 V | 5000 cycles |
| Electrical durability at Ue 500–690 V | 4000 cycles |
| Mechanical durability | 15000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed breaker indication |
| Dimensions (W × H × D) | 566 × 418 × 302 mm |
| Net weight | 81 kg |
| EAN | 8015644581275 |
| Customs tariff number | 85362090 |
This ABB SACE Emax air circuit breaker is designed for switching and protecting high-current low-voltage distribution circuits in industrial, commercial and infrastructure electrical systems.
The ABB 1SDA056787R1 has a rated current of 4000 A and uses a three-pole E4S fixed air circuit breaker configuration.
The breaker is fitted with an ABB PR122/P-LI R4000 electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection.
The E4S4000 configuration provides an ultimate short-circuit breaking capacity of 75 kA at 400/415 V AC and maintains a 75 kA rating at 690 V AC.
The ABB 1SDA056787R1 is a three-pole fixed air circuit breaker with rear horizontal terminals, designed for permanent integration into compatible low-voltage switchgear assemblies.
ABB SACE Emax air circuit breakers are engineered for dependable protection, switching and control of demanding low-voltage electrical distribution systems, combining high-current capability, robust short-circuit performance and advanced electronic protection technology.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.