Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056745R1 E3L2000 is a 2000 A four-pole withdrawable SACE Emax air circuit breaker moving part with a PR121/P-LSI R2000 electronic release providing long-time, short-time and instantaneous overcurrent protection.
£21,294.59
The ABB E3L2000 PR121/P-LSI, order code 1SDA056745R1, is a high-performance SACE Emax air circuit breaker moving part designed for switching and overcurrent protection in demanding low-voltage power-distribution systems. Part of the ABB SACE Emax E3 series, this four-pole withdrawable configuration combines a 2000 A rated current with the PR121/P-LSI R2000 electronic overcurrent release.
The PR121/P-LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. These LSI functions help protect conductors, switchboards and downstream electrical equipment while allowing coordinated protection between devices in complex industrial and commercial distribution networks.
This model is the four-pole withdrawable moving part of the E3L circuit breaker and is intended for use with the corresponding SACE Emax fixed part. It is fitted with four auxiliary contacts and open/closed position indication, while the withdrawable design facilitates inspection and servicing in switchboards where maintainability and continuity of operation are important.
The ABB SACE Emax E3L2000 is designed for switching and protection at main incomer and feeder levels within substantial low-voltage distribution systems. Its PR121/P-LSI electronic release provides long-time protection against sustained overload conditions, short-time protection for selective fault coordination and instantaneous intervention against severe short-circuit currents.
The combination of a 2000 A current rating, four-pole construction and withdrawable design makes the 1SDA056745R1 particularly suitable for switchboards where both electrical performance and serviceability are important. When installed with the corresponding fixed part, the moving circuit breaker can be withdrawn for inspection and maintenance, while the E3L performance level provides robust short-circuit interruption for demanding power-distribution networks.
| Series | SACE Emax E3 |
|---|---|
| ABB order code | 1SDA056745R1 |
| Product type | Air circuit breaker moving part |
| Frame | E3 |
| Short-circuit performance level | L |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Number of poles | 4P |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Release | PR121/P-LSI R2000 |
| Release type | Electronic |
| Protection functions | LSI — long-time, short-time and instantaneous |
| Version | Withdrawable moving part |
| Terminal connection type | Withdrawable circuit breaker |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 110 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 400 V AC | 130 kA |
| Rated service short-circuit breaking capacity (Ics) at 440 V AC | 110 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw) | 15 kA for 1 s |
| Power loss | 330 W |
| Electrical durability at Ue ≤ 440 V | 2000 cycles |
| Electrical durability at Ue 500–690 V | 1500 cycles |
| Mechanical durability | 15,000 cycles |
| Product dimensions (W × H × D) | 558 × 461 × 396.5 mm |
| Product net weight | 81 kg |
| EAN | 8015644580858 |
| HS code | 85362090 |
| Standard | IEC |
The ABB 1SDA056745R1 is a 2000 A four-pole SACE Emax air circuit breaker moving part designed for switching and overcurrent protection in high-current low-voltage power-distribution systems.
This circuit breaker is fitted with the ABB PR121/P-LSI R2000 electronic overcurrent release, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The circuit breaker has a rated uninterrupted current of 2000 A.
The 1SDA056745R1 is a four-pole withdrawable moving part designed for use with the corresponding ABB SACE Emax fixed part.
LSI denotes long-time overload, short-time short-circuit and instantaneous short-circuit protection, providing coordinated electronic protection against a range of overcurrent and fault conditions.
ABB SACE Emax air circuit breakers provide dependable switching and electronic protection for demanding low-voltage distribution systems, combining high current capability, robust short-circuit performance and service-friendly withdrawable construction.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.