Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056740R1 E3L2000PR122/P-LSI is a 2000 A three-pole withdrawable SACE Emax air circuit breaker moving part with PR122/P-LSI electronic overcurrent protection for high-current low-voltage power distribution.
£16,736.93
The ABB E3L2000PR122/P-LSI, order code 1SDA056740R1, is a high-performance 2000 A three-pole air circuit breaker moving part designed for reliable protection and switching in demanding low-voltage electrical distribution systems. As part of the proven ABB SACE Emax E3 series, this withdrawable breaker configuration combines the E3L breaking-performance class with the advanced PR122/P electronic overcurrent protection release.
The breaker is equipped with an ABB PR122/P-LSI electronic overcurrent release, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection. This combination provides comprehensive overcurrent protection while supporting selective coordination in industrial switchboards, main distribution assemblies and other critical high-current electrical installations.
With a rated current of 2000 A, a three-pole configuration and a withdrawable moving-part design, the E3L2000PR122/P-LSI is engineered for installations where maintainability, protection selectivity and service continuity are important. The E3L version provides an ultimate short-circuit breaking capacity of 130 kA at 400 V AC and is fitted with four auxiliary contacts plus breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E3 are designed to protect low-voltage electrical networks against damaging overcurrents while providing reliable switching and isolation of high-current circuits. Their robust construction and electronic protection releases make them particularly suitable for main incomers, feeders and other critical circuits in industrial and commercial distribution systems.
The PR122/P release electronically monitors circuit current and executes the required protection functions when abnormal operating conditions occur. In this LSI configuration, long-time protection guards against sustained overloads, short-time protection supports selective coordination during short circuits, and instantaneous protection provides rapid intervention during severe fault conditions.
| Series | SACE Emax E3 |
|---|---|
| ABB order code | 1SDA056740R1 |
| Product type | Air circuit breaker moving part |
| Frame / performance class | E3L |
| Rated current | 2000 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 3 |
| Execution | Withdrawable moving part (W MP) |
| Protection release | PR122/P-LSI electronic overcurrent release |
| Protection functions | L (long-time), S (short-time) and I (instantaneous) |
| Overload release adjustment range | 800–2000 A |
| Short-time delayed short-circuit release adjustment range | 1200–20000 A |
| Instantaneous short-circuit release adjustment range | 3000–30000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 130 kA |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Auxiliary contacts | 4 |
| Position indication | Open / closed breaker indication |
| Earth-fault protection | Not integrated in LSI configuration |
| Motor operator | Optional |
| Protection rating | IP2X |
| EAN | 8015644580803 |
| Weight | approx. 77 kg |
This ABB SACE Emax air circuit breaker moving part is designed for switching and protecting high-current low-voltage distribution circuits in industrial, commercial and infrastructure electrical systems.
The ABB 1SDA056740R1 has a rated current of 2000 A and uses a three-pole E3L breaker configuration.
The breaker is fitted with an ABB PR122/P-LSI electronic overcurrent release, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection.
The E3L configuration provides an ultimate short-circuit breaking capacity of 130 kA at 400 V AC, 50 Hz.
Yes. ABB order code 1SDA056740R1 is the withdrawable moving part of the E3L 2000 A three-pole air circuit breaker and is designed for use with the corresponding fixed part.
ABB SACE Emax air circuit breakers are engineered for dependable protection, switching and control of demanding low-voltage electrical distribution systems, combining high breaking performance with advanced electronic protection technology.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.