Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056712R1 is a SACE Emax E3V3200 3200 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LI R3200 electronic release providing long-time and instantaneous protection for high-current low-voltage distribution systems.
£37,515.93
The ABB E3V3200 PR121/P-LI, order code 1SDA056712R1, is a high-performance SACE Emax E3 V air circuit breaker moving part designed for demanding low-voltage power distribution systems. This configuration combines a 3200 A rated current, four-pole construction and a PR121/P-LI R3200 electronic overcurrent release.
Supplied as a withdrawable moving part (W MP), the E3V3200 is designed for use with a compatible ABB SACE Emax E3 withdrawable fixed part. The draw-out arrangement supports isolation, inspection, servicing and replacement, making it well suited to critical switchboards where maintainability and operational flexibility are important.
The PR121/P-LI electronic release provides long-time overload and instantaneous short-circuit protection. The E3 V performance class provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC, while four auxiliary contacts and open/closed position indication support switchboard signalling and control.
Air circuit breakers such as the ABB SACE Emax E3V3200 provide switching and overcurrent protection for main incomers, feeders and other high-current circuits in low-voltage distribution systems. The E3 V performance class provides substantial short-circuit interruption capability for installations where high prospective fault currents require robust and dependable protection.
The PR121/P-LI electronic release combines long-time protection against sustained overload conditions with instantaneous protection against severe short-circuit currents. Together with the withdrawable moving-part construction, the 1SDA056712R1 provides effective high-current protection while supporting efficient servicing and equipment replacement within compatible ABB SACE Emax switchgear.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA056712R1 |
| Product group | New Emax |
| Product type | Air circuit breaker moving part |
| Frame / subtype | E3 |
| Short-circuit performance level | V |
| Rated current (In) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Number of poles | 4P |
| Current type | AC |
| Release | PR121/P-LI R3200 |
| Release type | Electronic (EL) |
| Protection functions | Long-time and instantaneous (LI) |
| Version | Withdrawable (W) |
| Configuration | Withdrawable moving part (W MP) |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Rated short-time withstand current (Icw) | 85 kA for 1 s; 65 kA for 3 s |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Power loss | 570 W |
| Electrical durability | 6,000 cycles at Ue ≤ 440 V; 5,000 cycles at Ue 500–690 V |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Net dimensions (W × H × D) | 558 × 461 × 396.5 mm |
| Net weight | 81 kg |
| Packaged gross weight | 96 kg |
| EAN | 8015644580520 |
| Customs tariff / HS code | 85362090 |
| Standard | IEC |
The ABB 1SDA056712R1 is a SACE Emax E3V3200 four-pole withdrawable air circuit breaker moving part rated at 3200 A and equipped with a PR121/P-LI R3200 electronic overcurrent release.
The PR121/P-LI electronic release provides long-time overload protection and instantaneous short-circuit protection.
This configuration is a withdrawable moving part designed for use with a compatible ABB SACE Emax E3 withdrawable fixed part.
The ABB E3V3200 1SDA056712R1 has a rated uninterrupted current of 3200 A and uses a PR121/P-LI R3200 electronic release.
The rated ultimate short-circuit breaking capacity is 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
The rated short-time withstand current is 85 kA for 1 s and 65 kA for 3 s.
ABB SACE Emax air circuit breakers are widely used in demanding industrial, commercial and infrastructure power distribution systems, combining dependable switching, electronic circuit protection and maintainable withdrawable configurations for critical low-voltage electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.