ABB 1SDA056699R1 is a SACE Emax E3V3200 3200 A four-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LI R3200 electronic release providing long-time and instantaneous protection for high-current low-voltage power distribution systems.
£27,586.04
The ABB E3V3200 PR122/P-LI, order code 1SDA056699R1, is a high-performance SACE Emax air circuit breaker designed for switching and protection in demanding low-voltage power distribution systems. This E3 V configuration combines a 3200 A rated current, four-pole construction and a PR122/P-LI R3200 electronic overcurrent release.
Supplied as a fixed circuit breaker with rear horizontal terminals, the E3V3200 provides a robust arrangement for permanent installation in industrial, commercial and infrastructure switchboards. The PR122/P-LI electronic release provides long-time overload and instantaneous short-circuit protection for high-current distribution circuits.
The E3 V performance class provides substantial fault-interruption capability, with an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC. Rated for operation up to 690 V AC, the breaker combines high current capacity, strong short-circuit performance and electronic protection for critical distribution applications.
Air circuit breakers such as the ABB SACE Emax E3V3200 provide switching and overcurrent protection for main incomers, feeders and other high-current circuits in low-voltage distribution systems. The E3 V performance class provides substantial short-circuit interruption capability for switchboards where high prospective fault currents require robust and dependable protection.
The PR122/P-LI electronic release combines long-time protection against sustained overload conditions with instantaneous protection against severe short-circuit currents. Together with the fixed E3 V platform, four-pole construction and rear horizontal terminal arrangement, the 1SDA056699R1 provides a practical high-current protection solution for demanding industrial, commercial and infrastructure installations.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA056699R1 |
| Product group | New Emax |
| Product type | Air circuit breaker |
| Frame / subtype | E3 |
| Short-circuit performance level | V |
| Rated current (In) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Number of poles | 4P |
| Current type | AC |
| Release | PR122/P-LI R3200 |
| Release type | Electronic (EL) |
| Protection functions | Long-time and instantaneous (LI) |
| Version | Fixed (F) |
| Terminal configuration | Rear flat horizontal |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Rated short-time withstand current (Icw) | 85 kA for 1 s; 65 kA for 3 s |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Power loss | 330 W |
| Electrical durability | 6,000 cycles at Ue ≤ 440 V; 5,000 cycles at Ue 500–690 V |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 530 × 418 × 302 mm |
| Product net weight | 76 kg |
| EAN | 8015644580391 |
| Customs tariff number | 85362090 |
| Standard | IEC |
The ABB 1SDA056699R1 is a SACE Emax E3V3200 four-pole fixed air circuit breaker rated at 3200 A, supplied with rear horizontal terminals and a PR122/P-LI R3200 electronic overcurrent release.
The PR122/P-LI electronic release provides long-time overload protection and instantaneous short-circuit protection.
This configuration is a fixed air circuit breaker with rear flat horizontal terminals for permanent installation in a compatible low-voltage switchboard.
The E3V3200 has a rated current, operational current and uninterrupted current of 3200 A.
The rated ultimate short-circuit breaking capacity is 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
The rated short-time withstand current is 85 kA for 1 s and 65 kA for 3 s.
ABB SACE Emax air circuit breakers are widely used in demanding industrial, commercial and infrastructure power distribution systems, combining dependable switching, electronic overcurrent protection and high short-circuit performance for critical low-voltage electrical installations.