ABB 1SDA056673R1 is a SACE Emax E3 V 2500 A three-pole withdrawable air circuit breaker moving part with a PR121/P-LSI R2500 electronic release providing long-time, short-time and instantaneous overcurrent protection for demanding low-voltage power distribution systems.

SKU: 1SDA056673R1Alt SKU: E3V25,1SDA056673R1MPN: 1SDA056673R1
Price
List Price £29,426.72 ex VAT
Your Price (ex VAT) Save 25%
£22,070.04 25% OFF
You save £7,356.68 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £22,070.04
Trade pricing is personalised to your account

Manufacturer Lead Time

£22,070.04

Why Choose the ABB E3V2500 PR121/P-LSI 1SDA056673R1 Air Circuit Breaker?

The ABB 1SDA056673R1 is a high-performance SACE Emax E3 V withdrawable air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB SACE Emax series, this three-pole breaker combines a 2500 A rated uninterrupted current with high short-circuit performance for industrial, commercial and infrastructure power distribution applications.

The E3V2500 is equipped with an ABB PR121/P-LSI R2500 electronic overcurrent release, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection. These L, S and I protection functions protect against sustained overcurrents and short circuits while allowing selective coordination within complex electrical distribution networks.

With a rated uninterrupted current of 2500 A, a rated voltage of 690 V AC and a three-pole withdrawable configuration, the 1SDA056673R1 is well suited to main distribution boards, industrial switchgear and high-current feeder applications. The E3 V performance level provides a rated ultimate short-circuit breaking capacity of 130 kA at 400 V AC, while the withdrawable moving-part design supports efficient isolation, inspection and maintenance.

Key Advantages

  • High-performance ABB SACE Emax E3 V air circuit breaker moving part for demanding low-voltage distribution systems.
  • 2500 A rated uninterrupted current for high-current power distribution applications.
  • Three-pole withdrawable configuration supports flexible switchboard operation and maintenance.
  • PR121/P-LSI R2500 electronic release provides long-time, short-time and instantaneous overcurrent protection.
  • High 130 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Withdrawable construction allows efficient isolation, servicing and replacement within compatible SACE Emax switchgear.

Key Features

  • ABB SACE Emax E3 V series.
  • 2500 A rated uninterrupted current.
  • Three-pole withdrawable air circuit breaker moving part.
  • PR121/P-LSI R2500 electronic overcurrent release.
  • Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
  • 690 V AC rated voltage.
  • 130 kA Icu at 400 V AC.
  • 85 kA rated short-time withstand current for 1 s.
  • 1000–2500 A overload release setting range.
  • 2500–25000 A short-time delayed short-circuit setting range.
  • 3750–37500 A instantaneous short-circuit setting range.
  • Four auxiliary changeover contacts.
  • Open/closed circuit-breaker position indication.
  • Optional motor operating mechanism for automated switching applications.

Selective Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E3V2500 provide controlled switching and protection for high-current low-voltage distribution circuits. The PR121/P-LSI electronic release combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, helping safeguard switchboards, conductors and connected electrical equipment against damaging overcurrent and fault conditions.

The short-time protection function supports selective coordination between upstream and downstream protective devices, helping isolate faults at the appropriate level of the electrical distribution system. Combined with the high-breaking-capacity E3 V platform and withdrawable construction, the 1SDA056673R1 is particularly suited to high-capacity switchgear where dependable protection, system availability and maintainability are important.

Typical Applications

  • Main low-voltage electrical distribution boards.
  • Industrial withdrawable switchboards and switchgear assemblies.
  • Manufacturing plants and process facilities.
  • Commercial and infrastructure power distribution systems.
  • High-current incomer and feeder circuit protection.
  • Electrical networks requiring selective short-circuit protection.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax E3
ABB order code 1SDA056673R1
Product type Air circuit breaker moving part
Frame E3
Performance level V
Rated current (In) 2500 A
Rated uninterrupted current (Iu) 2500 A
Rated voltage 690 V AC
Number of poles 3
Release PR121/P-LSI R2500
Release type Electronic overcurrent release
Protection functions Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I)
Overload release setting range 1000–2500 A
Short-time delayed short-circuit release setting range 2500–25000 A
Instantaneous short-circuit release setting range 3750–37500 A
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 130 kA
Rated short-time withstand current (Icw), 1 s 85 kA
Version Withdrawable
Configuration Moving part
Complete device with protection unit Yes
Auxiliary contacts 4 changeover contacts
Position indication Open / closed
Integrated earth-fault protection No
Motor operating mechanism Optional
Net weight 77 kg
EAN 8015644580131
Customs tariff / HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA056673R1 used for?

The ABB 1SDA056673R1 is a SACE Emax E3 V air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits in compatible withdrawable switchgear installations.

What is the current rating of the ABB E3V2500 1SDA056673R1?

The circuit breaker has a rated uninterrupted current of 2500 A, making it suitable for high-capacity low-voltage power distribution applications.

What protection release is fitted to the ABB 1SDA056673R1?

The 1SDA056673R1 is fitted with an ABB PR121/P-LSI R2500 electronic overcurrent release, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB E3V2500?

The E3 V version provides a rated ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC and a rated short-time withstand current of 85 kA for 1 s.

Is the ABB 1SDA056673R1 fixed or withdrawable?

The 1SDA056673R1 is a three-pole withdrawable circuit breaker moving part designed for use with a compatible SACE Emax fixed section, supporting efficient isolation, servicing and replacement within the switchgear assembly.

Trusted for Industrial Power Distribution

ABB SACE Emax air circuit breakers are designed for dependable protection and switching in demanding low-voltage power distribution systems, combining electronic overcurrent protection with high short-circuit performance and serviceable withdrawable configurations.