1SDA056653R1 ABB E3V 2000 PR122/P-LSIG 2000 A 4-Pole Air Circuit Breaker

1SDA056653R1 ABB E3V 2000 PR122/P-LSIG 2000 A 4-Pole Air Circuit Breaker

ABB 1SDA056653R1 SACE Emax E3V 2000 four-pole withdrawable air circuit breaker moving part with 2000 A rated current, PR122/P-LSIG electronic protection, 125 kA short-circuit current rating at 480 V and 85 kA short-time withstand current.

SKU: 1SDA056653R1MPN: 1SDA056653R1
Price
List Price £28,987.65 ex VAT
Your Price (ex VAT) Save 25%
£21,740.74 25% OFF
You save £7,246.91 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £21,740.74
Trade pricing is personalised to your account

Manufacturer Lead Time

£21,740.74

Why Choose the ABB 1SDA056653R1 E3V 2000 Air Circuit Breaker?

The ABB 1SDA056653R1 is a high-performance SACE Emax E3V air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Configured as an E3V 2000 PR122/P-LSIG, this four-pole withdrawable unit combines a rated current of 2000 A with ABB's PR122/P electronic overcurrent release.

As part of the ABB SACE Emax series, the E3V 2000 is engineered for installations requiring high short-circuit performance, selective protection and dependable operation. The PR122/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions, helping protect electrical installations against overloads, short circuits and earth faults while supporting coordinated protection throughout the distribution system.

This configuration is a four-pole withdrawable moving part intended for use with a compatible SACE Emax fixed part. The E3V 2000 performance level provides a 125 kA short-circuit current rating at 480 V and a short-time withstand current of 85 kA, making it suitable for high-current, high-fault-level industrial and commercial power distribution systems.

Key Advantages

  • High-performance ABB SACE Emax E3V air circuit breaker moving part for demanding low-voltage distribution systems.
  • 2000 A rated current for high-current industrial and commercial power distribution.
  • PR122/P-LSIG electronic trip unit providing comprehensive adjustable circuit protection.
  • LSIG protection provides long-time, short-time, instantaneous and ground-fault protection functions.
  • Four-pole configuration supports applications requiring switching and isolation of the neutral conductor.
  • 125 kA short-circuit current rating at 480 V for demanding high-fault-level applications.
  • 85 kA short-time withstand current supports selective protection within complex distribution networks.
  • Withdrawable construction supports convenient isolation, inspection and maintenance within compatible SACE Emax switchgear.

Key Features

  • ABB SACE Emax E3V 2000 series.
  • 2000 A rated current.
  • Four-pole configuration.
  • Withdrawable moving-part construction.
  • PR122/P-LSIG electronic overcurrent release.
  • LSIG protection functions for long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
  • 125 kA short-circuit current rating at 480 V.
  • 85 kA short-time withstand current.
  • Integrated ground-fault protection through the LSIG electronic release.
  • Four-pole design suitable for three-phase and neutral distribution arrangements.
  • Withdrawable construction facilitates breaker isolation, inspection and maintenance.

Comprehensive Four-Pole Protection for High-Current Distribution

Air circuit breakers such as the ABB SACE Emax E3V provide switching and protection for low-voltage electrical distribution systems where substantial prospective fault currents can occur. The E3V 2000 combines a 2000 A current rating with high short-circuit performance, helping protect switchboards, busbars, cables and connected equipment against damaging overload, short-circuit and ground-fault conditions.

The PR122/P-LSIG electronic trip unit combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection. Together with the four-pole and withdrawable construction, these functions make the 1SDA056653R1 well suited to high-current three-phase distribution systems where neutral switching, selective coordination, earth-fault protection and maintainable circuit protection are required.

Typical Applications

  • Main incoming circuit protection in low-voltage switchboards.
  • Industrial power distribution systems.
  • High-current distribution feeders.
  • High-fault-level electrical distribution systems.
  • Manufacturing and process plant electrical systems.
  • Commercial and infrastructure power distribution.
  • Generator and transformer distribution systems.
  • Three-phase systems requiring four-pole switching and neutral isolation.
  • Critical circuits requiring comprehensive LSIG electronic protection.
  • Withdrawable switchgear requiring maintainable 2000 A circuit protection.

Technical Specifications

Series SACE Emax
Product group 310513-New Emax
Order code 1SDA056653R1
Product type Air circuit breaker moving part
Frame E3
Performance level V
Frame size 2000 A
Rated current (In) 2000 A
Number of poles 4
Installation Withdrawable
Version Moving part
Trip unit PR122/P-LSIG
Release type Electronic overcurrent release
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Short-circuit current at 480 V 125 kA
Short-time withstand current 85 kA
Ground-fault protection Integrated through LSIG release

Frequently Asked Questions

What is the ABB 1SDA056653R1 used for?

The ABB 1SDA056653R1 is a 2000 A four-pole withdrawable air circuit breaker moving part used for switching and protecting demanding low-voltage electrical distribution systems, including main incomers and high-current distribution feeders.

What is the rated current of the ABB 1SDA056653R1?

The circuit breaker moving part has a rated current of 2000 A and is equipped with a PR122/P-LSIG electronic overcurrent release.

What protection does the PR122/P-LSIG trip unit provide?

The PR122/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.

What is the short-circuit performance of the E3V 2000?

The E3V 2000 has a 125 kA short-circuit current rating at 480 V and a short-time withstand current of 85 kA, making it suitable for demanding high-fault-level distribution systems.

Is the ABB 1SDA056653R1 fixed or withdrawable?

The 1SDA056653R1 is a four-pole withdrawable air circuit breaker moving part designed for use with a compatible ABB SACE Emax fixed part and switchgear assembly.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, comprehensive electronic protection and maintainable withdrawable construction for industrial and commercial installations.