1SDA056641R1 ABB E3V2000 PR121/P-LSI 2000 A 3-Pole Withdrawable Air Circuit Breaker

1SDA056641R1 ABB E3V2000 PR121/P-LSI 2000 A 3-Pole Withdrawable Air Circuit Breaker

ABB 1SDA056641R1 is a SACE Emax E3 V 2000 A three-pole withdrawable air circuit breaker moving part with a PR121/P-LSI electronic release for selective high-performance protection of low-voltage power distribution systems.

SKU: 1SDA056641R1Alt SKU: E3V20,1SDA056641R1MPN: 1SDA056641R1
Price
List Price £21,548.35 ex VAT
Your Price (ex VAT) Save 25%
£16,161.26 25% OFF
You save £5,387.09 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £16,161.26
Trade pricing is personalised to your account

Manufacturer Lead Time

£16,161.26

Why Choose the ABB E3V2000 PR121/P-LSI 1SDA056641R1 Air Circuit Breaker?

The ABB 1SDA056641R1 is a high-performance SACE Emax E3 V withdrawable air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB SACE Emax series, this three-pole breaker combines a 2000 A rated uninterrupted current with high short-circuit performance for industrial, commercial and infrastructure power distribution applications.

The E3V2000 is equipped with an ABB PR121/P-LSI R2000 electronic overcurrent release, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection. These L, S and I protection functions support effective selectivity and coordination within complex electrical distribution networks while protecting conductors and connected equipment against damaging overcurrent conditions.

With a rated uninterrupted current of 2000 A, a rated operational voltage of 690 V AC and a three-pole withdrawable configuration, the 1SDA056641R1 is well suited to main distribution boards, industrial switchgear and high-current feeder applications. The E3 V performance level provides a rated ultimate short-circuit breaking capacity of 130 kA at 400 V AC, while the withdrawable moving-part design supports efficient isolation and maintenance.

Key Advantages

  • High-performance ABB SACE Emax E3 V air circuit breaker moving part for low-voltage power distribution.
  • 2000 A rated uninterrupted current for demanding high-current installations.
  • Three-pole withdrawable configuration for flexible switchboard operation and maintenance.
  • PR121/P-LSI electronic release provides long-time, short-time and instantaneous overcurrent protection.
  • High 130 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Withdrawable construction supports efficient isolation, inspection and replacement within compatible switchgear assemblies.

Key Features

  • ABB SACE Emax E3 V series.
  • 2000 A rated uninterrupted current.
  • Three-pole withdrawable air circuit breaker moving part.
  • PR121/P-LSI R2000 electronic overcurrent release.
  • Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
  • 690 V AC rated operational voltage.
  • 130 kA Icu at 400 V AC.
  • 100 kA Ics at 400 V AC.
  • 85 kA short-time withstand current for 1 s.
  • 800–2000 A overload release adjustment range.
  • 2000–20000 A short-time delayed short-circuit adjustment range.
  • 3000–30000 A instantaneous short-circuit adjustment range.
  • Four auxiliary changeover contacts and open/closed position indication.

Selective Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E3V2000 provide controlled switching and protection for high-current low-voltage distribution circuits. The PR121/P-LSI electronic release combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, helping safeguard switchboards, conductors and connected electrical equipment against a broad range of overcurrent and fault conditions.

The short-time protection function supports selective coordination between protective devices, helping isolate faults at the appropriate level of the distribution system. Combined with the high-breaking-capacity E3 V platform and withdrawable construction, the 1SDA056641R1 is particularly suited to industrial switchgear where dependable protection, system availability and maintainability are important.

Typical Applications

  • Main low-voltage electrical distribution boards.
  • Industrial withdrawable switchboards and switchgear assemblies.
  • Manufacturing plants and process facilities.
  • Commercial and infrastructure power distribution systems.
  • High-current feeder and distribution circuit protection.
  • Electrical networks requiring selective short-circuit protection.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax E3
ABB order code 1SDA056641R1
Product type Air circuit breaker moving part
Frame E3
Performance level V
Rated current (In) 2000 A
Rated operational current (Ie) 2000 A
Rated uninterrupted current (Iu) 2000 A
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Release PR121/P-LSI R2000
Release type Electronic
Protection functions Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I)
Overload release adjustment range 800–2000 A
Short-time delayed short-circuit adjustment range 2000–20000 A
Instantaneous short-circuit adjustment range 3000–30000 A
Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 660–690 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 220–440 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 85 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Current type AC
Version Withdrawable
Configuration Moving part
Auxiliary contacts 4 changeover contacts
Position indication Open / closed
Integrated earth-fault protection No
Motor operating mechanism Optional
Electrical durability 9,000 operating cycles
Mechanical durability 20,000 operating cycles
Power loss 225 W
Dimensions (W × H × D) 432 × 461 × 396.5 mm
Net weight 64 kg
Standard IEC
EAN 8015644579814
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA056641R1 used for?

The ABB 1SDA056641R1 is a SACE Emax E3 V air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits in compatible withdrawable switchgear installations.

What is the current rating of the ABB E3V2000 1SDA056641R1?

The circuit breaker has a rated current and rated uninterrupted current of 2000 A.

What protection release is fitted to this circuit breaker?

The 1SDA056641R1 is fitted with an ABB PR121/P-LSI R2000 electronic overcurrent release, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB E3V2000?

The E3 V version provides a rated ultimate short-circuit breaking capacity of 130 kA at 400 V AC and a rated service short-circuit breaking capacity of 100 kA at 400 V AC.

Is the ABB 1SDA056641R1 a fixed or withdrawable circuit breaker?

The 1SDA056641R1 is a three-pole withdrawable circuit breaker moving part designed for use with a compatible SACE Emax fixed section in a withdrawable switchgear installation.

Trusted for Industrial Power Distribution

ABB SACE Emax air circuit breakers are designed for dependable protection and switching in demanding low-voltage power distribution systems, combining electronic protection technology with high short-circuit performance and serviceable withdrawable configurations.