ABB 1SDA056604R1 is a SACE Emax E3V 1600 A four-pole fixed air circuit breaker with rear flat horizontal terminals and a PR122/P-LSI electronic overcurrent release for high-performance low-voltage power distribution protection.
£13,045.86
The ABB 1SDA056604R1 is a high-performance SACE Emax E3V air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Identified as E3V1600 PR122/P-LSI In=1600A 4P F HR, this four-pole fixed circuit breaker combines a 1600 A rated uninterrupted current with the ABB PR122/P-LSI electronic overcurrent release.
As part of the ABB SACE Emax / New Emax range, the E3V1600 is engineered for industrial, commercial and infrastructure power distribution applications requiring selective overcurrent protection and high fault-current interruption capability. The PR122/P-LSI electronic trip unit provides long-time, short-time and instantaneous protection, helping safeguard cables, busbars, transformers and connected equipment against overloads and short-circuit faults.
This version features a four-pole fixed construction with rear flat horizontal terminals for permanent installation within low-voltage switchboards. Rated for operation up to 690 V AC, with an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC and a rated short-time withstand current of 85 kA for 1 s, the E3V1600 is well suited to high-fault-level distribution systems requiring dependable and selective circuit protection.
Air circuit breakers such as the ABB E3V1600 provide switching and automatic protection for high-current low-voltage electrical distribution systems. The PR122/P electronic overcurrent release monitors circuit conditions and provides advanced protection functions to help safeguard cables, busbars, transformers and downstream electrical equipment against damaging overload and short-circuit conditions.
The LSI configuration combines long-time overload protection, short-time selective short-circuit protection and instantaneous short-circuit protection. Combined with the four-pole fixed construction, rear horizontal terminal arrangement and high breaking performance of the E3V frame, this makes the 1SDA056604R1 suitable for installations requiring coordinated protection and dependable interruption of high prospective fault currents.
| Series | SACE Emax / New Emax |
|---|---|
| ABB product group | 310513-New Emax |
| Order code | 1SDA056604R1 |
| Product type | Air circuit breaker |
| Frame | E3V |
| Short-circuit performance level | V |
| Rated current | 1600 A |
| Rated uninterrupted current | 1600 A |
| Rated operational current | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | PR122/P-LSI |
| Release rating | R1600 |
| Release type | Electronic overcurrent release |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload release adjustment | 640–1600 A |
| Instantaneous short-circuit adjustment | 2400–24000 A |
| Ultimate short-circuit breaking capacity | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Service short-circuit breaking capacity | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Rated short-time withstand current | 85 kA for 1 s; 65 kA for 3 s |
| Mounting type | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 10,000 cycles |
| Power loss | 85 W |
| Product dimensions (W × H × D) | 530 × 418 × 302 mm |
| Net weight | 76 kg |
| Degree of protection | IP20 |
| Standard | IEC |
| HS code | 85362090 |
| EAN | 8015644579449 |
The ABB 1SDA056604R1 is a 1600 A four-pole air circuit breaker used for switching and protecting high-current low-voltage electrical distribution systems in industrial, commercial and infrastructure installations.
The ABB 1SDA056604R1 has a rated uninterrupted current of 1600 A and uses the high-performance ABB SACE Emax E3V frame.
The PR122/P-LSI electronic overcurrent release provides long-time overload protection, short-time short-circuit protection and instantaneous short-circuit protection.
This model is a four-pole fixed air circuit breaker with rear flat horizontal terminals for permanent installation within a low-voltage switchboard.
The E3V1600 has an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC, a service short-circuit breaking capacity of 100 kA at the same voltages and a rated short-time withstand current of 85 kA for 1 s.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection of low-voltage power distribution systems, combining advanced electronic overcurrent protection, high short-circuit performance and robust fixed construction for demanding industrial, commercial and infrastructure installations.