1SDA056596R1 ABB E3V1600 PR122/P-LSI 1600A 3P Fixed Air Circuit Breaker

1SDA056596R1 ABB E3V1600 PR122/P-LSI 1600A 3P Fixed Air Circuit Breaker

ABB 1SDA056596R1 is a SACE Emax E3V 1600 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSI R1600 electronic release providing long-time, short-time and instantaneous overcurrent protection.

SKU: 1SDA056596R1MPN: 1SDA056596R1
Price
List Price £13,641.40 ex VAT
Your Price (ex VAT) Save 25%
£10,231.05 25% OFF
You save £3,410.35 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,231.05
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,231.05

Why Choose the ABB E3V1600 PR122/P-LSI 1600A 3P Fixed Air Circuit Breaker?

The ABB E3V1600 PR122/P-LSI, order code 1SDA056596R1, is a high-performance SACE Emax air circuit breaker engineered for protection and switching in demanding low-voltage power distribution systems. This three-pole fixed breaker has a rated uninterrupted current of 1600 A and incorporates the PR122/P-LSI R1600 electronic overcurrent release.

The PR122/P-LSI release provides long-time, short-time and instantaneous overcurrent protection. These LSI protection functions help safeguard conductors, switchboards and connected equipment against sustained overloads and short-circuit faults, while short-time protection provides the functionality required for selective coordination in appropriately engineered electrical distribution systems.

This version features a fixed construction with rear flat horizontal terminals and is fitted with four auxiliary contacts together with circuit-breaker open/closed position indication. Rated for operation up to 690 V AC and offering an ultimate short-circuit breaking capacity of 130 kA at voltages up to 440 V AC, the E3V1600 provides substantial fault-interruption capability for critical power distribution.

Key Advantages

  • High-performance ABB SACE Emax E3V air circuit breaker.
  • 1600 A rated uninterrupted current for high-current low-voltage distribution.
  • Three-pole fixed configuration with rear flat horizontal terminals.
  • Advanced PR122/P-LSI R1600 electronic overcurrent release.
  • Long-time, short-time and instantaneous protection against overload and short-circuit conditions.
  • 130 kA ultimate short-circuit breaking capacity at 220–440 V AC.
  • 100 kA service short-circuit breaking capacity at 220–440 V AC.
  • Four auxiliary contacts support circuit-breaker status monitoring and control.

Key Features

  • ABB SACE Emax E3V series.
  • 1600 A rated current.
  • 3-pole fixed circuit-breaker construction.
  • Rear flat horizontal terminals.
  • PR122/P-LSI R1600 electronic release.
  • Long-time (L) overload protection.
  • Short-time (S) short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 85 kA short-time withstand current for 1 s.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

High-Performance LSI Protection for Critical Distribution

Air circuit breakers such as the ABB SACE Emax E3V provide switching and overcurrent protection for major low-voltage distribution systems. The E3V performance level combines substantial fault-interruption capability with robust fixed construction, helping safeguard switchboards, conductors and connected equipment in installations where high prospective fault currents can occur.

The PR122/P-LSI R1600 electronic release combines long-time protection against sustained overloads with short-time and instantaneous protection against short-circuit conditions. Together with the 1600 A rating, up to 130 kA ultimate breaking capacity and fixed rear-horizontal-terminal construction, the 1SDA056596R1 provides dependable and selective protection for demanding power distribution installations.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Transformer secondary protection.
  • Main incoming circuit-breaker applications.
  • High-fault-level outgoing feeder protection.
  • Power distribution centres and fixed switchgear assemblies.

Technical Specifications

Series SACE Emax E3V
ABB order code 1SDA056596R1
Product type Air circuit breaker
Frame / performance level E3V
Sub-type E3
Rated current (In) 1600 A
Rated operational current (Ie) 1600 A
Rated uninterrupted current (Iu) 1600 A
Number of poles 3
Current type AC
Configuration Fixed
Terminal connection Rear flat horizontal
Trip unit PR122/P-LSI R1600
Release type Electronic
Protection functions Long-time (L), short-time (S), instantaneous (I)
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) 130 kA at 220–440 V AC; 100 kA at 500–690 V AC
Service short-circuit breaking capacity (Ics) 100 kA at 220–440 V AC; 85 kA at 500–690 V AC
Short-time withstand current (Icw) 85 kA for 1 s; 65 kA for 3 s
Earth-fault protection Not included in LSI configuration
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 85 W
Electrical durability 10,000 cycles at ≤440 V; 10,000 cycles at 500–690 V
Electrical operating frequency 20 cycles per hour
Mechanical durability 20,000 cycles
Mechanical operating frequency 60 cycles per hour
Dimensions (W × H × D) 404 × 418 × 302 mm
Net weight 60 kg
Standard IEC
Customs tariff number 85362090
EAN 8015644579364

Frequently Asked Questions

What is the ABB 1SDA056596R1?

The ABB 1SDA056596R1 is a SACE Emax E3V 1600 A three-pole fixed air circuit breaker with rear flat horizontal terminals and a PR122/P-LSI R1600 electronic overcurrent release.

What protection functions does the PR122/P-LSI provide?

The PR122/P-LSI electronic release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB E3V1600?

The E3V1600 provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.

Is the ABB 1SDA056596R1 fixed or withdrawable?

This model is a fixed three-pole circuit breaker equipped with rear flat horizontal terminals for integration into a compatible low-voltage switchboard.

Does the ABB 1SDA056596R1 include earth-fault protection?

No. The PR122/P-LSI release provides long-time, short-time and instantaneous overcurrent protection. Corresponding PR122/P-LSIG configurations additionally incorporate earth-fault protection.

Trusted Protection for Critical Power Systems

ABB SACE Emax air circuit breakers combine high short-circuit performance, advanced electronic protection and robust switchboard integration to provide dependable protection for demanding industrial, commercial and infrastructure power distribution systems.