ABB 1SDA056595R1 is a SACE Emax E3V 1600 A three-pole fixed air circuit breaker with rear flat horizontal terminals and a PR122/P-LI R1600 electronic release providing long-time and instantaneous overcurrent protection.
£9,654.59
The ABB E3V1600 PR122/P-LI, order code 1SDA056595R1, is a high-performance SACE Emax air circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. This three-pole fixed breaker has a rated uninterrupted current of 1600 A and incorporates the PR122/P-LI R1600 electronic overcurrent release.
The PR122/P-LI release provides long-time and instantaneous overcurrent protection, helping protect conductors, switchboards and connected equipment against sustained overloads and severe short-circuit faults. Combined with the E3V short-circuit performance level, it provides dependable protection for installations with substantial prospective fault currents.
This version features a fixed construction with rear flat horizontal terminals and is supplied with four auxiliary contacts plus circuit-breaker open/closed position indication. With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of up to 130 kA, the E3V1600 is suited to demanding industrial, commercial and infrastructure switchboards.
Air circuit breakers such as the ABB SACE Emax E3V provide switching and overcurrent protection for major low-voltage distribution systems. The E3V short-circuit performance level combines substantial fault-interruption capability with robust fixed construction, helping safeguard switchboards, conductors and connected equipment in installations where high prospective fault currents can occur.
The PR122/P-LI R1600 electronic release combines long-time protection against sustained overloads with instantaneous protection against severe short-circuit conditions. Together with the 1600 A rating, up to 130 kA ultimate breaking capacity and fixed rear-horizontal-terminal construction, the 1SDA056595R1 provides dependable protection for demanding power distribution installations.
| Series | SACE Emax E3V |
|---|---|
| ABB order code | 1SDA056595R1 |
| Product type | Air circuit breaker |
| Frame / performance level | E3V |
| Sub-type | E3 |
| Rated current (In) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 3 |
| Current type | AC |
| Configuration | Fixed |
| Terminal connection | Rear flat horizontal |
| Trip unit | PR122/P-LI R1600 |
| Release type | Electronic |
| Protection functions | Long-time (L), instantaneous (I) |
| Rated operational voltage | 690 V AC |
| Rated voltage | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Service short-circuit breaking capacity (Ics) | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Short-time withstand current (Icw) | 85 kA for 1 s; 65 kA for 3 s |
| Earth-fault protection | Not included in LI configuration |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 85 W |
| Electrical durability | 10,000 cycles at ≤440 V; 10,000 cycles at 500–690 V |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 404 × 418 × 302 mm |
| Net weight | 60 kg |
| Standard | IEC |
| Customs tariff number | 85362090 |
| EAN | 8015644579357 |
The ABB 1SDA056595R1 is a SACE Emax E3V 1600 A three-pole fixed air circuit breaker with rear flat horizontal terminals and a PR122/P-LI R1600 electronic overcurrent release.
The PR122/P-LI electronic release provides long-time overload protection and instantaneous short-circuit protection.
The E3V1600 provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
This model is a fixed three-pole circuit breaker equipped with rear flat horizontal terminals for integration into a compatible low-voltage switchboard.
No. The PR122/P-LI release provides long-time and instantaneous overcurrent protection. Corresponding LSIG release configurations additionally incorporate earth-fault protection.
ABB SACE Emax air circuit breakers combine high short-circuit performance, electronic overcurrent protection and robust switchboard integration to provide dependable protection for demanding industrial, commercial and infrastructure power distribution systems.