Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056589R1 is a SACE Emax E3V 1250 A four-pole withdrawable air circuit breaker moving part with a PR122/P-LSIG electronic overcurrent release for high-performance low-voltage power distribution protection.
£13,041.68
The ABB 1SDA056589R1 is a high-performance SACE Emax E3V air circuit breaker (ACB) moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Identified as E3V1250 PR122/P-LSIG In=1250A 4P W MP, this four-pole withdrawable circuit breaker moving part combines a 1250 A rated uninterrupted current with the ABB PR122/P-LSIG electronic overcurrent release.
As part of the ABB SACE Emax / New Emax range, the E3V1250 is engineered for industrial, commercial and infrastructure power distribution applications requiring advanced overcurrent protection and high fault-current interruption capability. The PR122/P-LSIG electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection, helping safeguard cables, busbars, transformers and connected equipment against overloads, short circuits and earth faults.
This version features a four-pole withdrawable moving-part construction for use with the corresponding ABB SACE Emax fixed part. Rated for operation up to 690 V AC, with an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC and a rated short-time withstand current of 85 kA for 1 s, it is well suited to demanding distribution systems requiring comprehensive protection and convenient breaker isolation for servicing.
Air circuit breakers such as the ABB E3V1250 provide switching and automatic protection for high-current low-voltage electrical distribution systems. The PR122/P electronic overcurrent release monitors circuit conditions and provides advanced protection functions to help safeguard cables, busbars, transformers and downstream electrical equipment against damaging overload, short-circuit and ground-fault conditions.
The LSIG configuration combines long-time overload protection, short-time selective short-circuit protection, instantaneous short-circuit protection and ground-fault protection. Combined with the four-pole withdrawable construction and high breaking performance of the E3V frame, this makes the 1SDA056589R1 suitable for critical installations requiring coordinated protection together with convenient breaker isolation, inspection and replacement.
| Series | SACE Emax / New Emax |
|---|---|
| ABB product group | 310513-New Emax |
| Order code | 1SDA056589R1 |
| Product type | Air circuit breaker moving part |
| Frame | E3V |
| Short-circuit performance level | V |
| Rated current | 1250 A |
| Rated uninterrupted current | 1250 A |
| Rated operational current | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | PR122/P-LSIG |
| Release rating | R1250 |
| Release type | Electronic overcurrent release |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Ultimate short-circuit breaking capacity | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Service short-circuit breaking capacity | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Rated short-time withstand current | 85 kA for 1 s; 65 kA for 3 s |
| Mounting type | Withdrawable |
| Breaker configuration | Moving part (MP) |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 12,000 cycles |
| Power loss | 90 W |
| Product dimensions (W × H × D) | 558 × 461 × 396.5 mm |
| Net weight | 81 kg |
| Standard | IEC |
| HS code | 85362090 |
| EAN | 8015644579296 |
The ABB 1SDA056589R1 is a 1250 A four-pole air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution systems in industrial, commercial and infrastructure installations.
The ABB 1SDA056589R1 has a rated uninterrupted current of 1250 A and uses the high-performance ABB SACE Emax E3V frame.
The PR122/P-LSIG electronic overcurrent release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
This model is a four-pole withdrawable moving part designed for use with the corresponding ABB SACE Emax fixed part, allowing the breaker to be disconnected and removed for inspection, maintenance or replacement.
The E3V1250 has an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC, a service short-circuit breaking capacity of 100 kA at the same voltages and a rated short-time withstand current of 85 kA for 1 s.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection of low-voltage power distribution systems, combining advanced electronic protection, high short-circuit performance and serviceable withdrawable construction for demanding industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.