ABB 1SDA056583R1 SACE Emax E3V 1250 three-pole withdrawable air circuit breaker moving part with 1250 A rated current, PR123/P-LSIG electronic protection, advanced monitoring and up to 130 kA ultimate short-circuit breaking capacity.
£16,259.65
The ABB 1SDA056583R1 is a high-performance SACE Emax E3V air circuit breaker moving part designed for protection, switching and advanced monitoring in demanding low-voltage electrical distribution systems. Configured as an E3V 1250 PR123/P-LSIG, this three-pole withdrawable unit combines a rated uninterrupted current of 1250 A with ABB's advanced PR123/P electronic overcurrent release.
As part of the ABB SACE Emax series, the E3V 1250 is engineered for installations requiring high short-circuit performance, selective protection and comprehensive electrical system monitoring. The PR123/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions, helping protect electrical installations against overloads, short circuits and earth faults.
This configuration is a three-pole withdrawable moving part with a rated operational voltage of 690 V AC. The E3V performance level provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC, making it suitable for high-fault-level industrial switchboards and critical power distribution systems.
Air circuit breakers such as the ABB SACE Emax E3V provide switching and protection for low-voltage electrical distribution systems where substantial prospective fault currents can occur. The E3V performance level offers high short-circuit interruption capability, helping protect switchboards, busbars, cables and connected equipment against damaging overload, short-circuit and earth-fault conditions.
The PR123/P-LSIG electronic trip unit combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection with advanced measurement and monitoring capabilities. These functions make the 1SDA056583R1 particularly suitable for critical distribution circuits where comprehensive protection, selective coordination and visibility of electrical system performance are required.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| Order code | 1SDA056583R1 |
| EAN | 8015644579234 |
| Product type | Air circuit breaker moving part |
| Frame | E3 |
| Performance level | V |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Installation | Withdrawable |
| Version | Moving part |
| Trip unit | PR123/P-LSIG R1250 |
| Release type | Electronic overcurrent release |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Overload release adjustment range | 400–1250 A |
| Short-time delayed short-circuit adjustment range | 750–12500 A |
| Instantaneous short-circuit adjustment range | 1875–18750 A |
| Ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 220–440 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 500–690 V AC | 85 kA |
| Short-time withstand current (Icw), 1 s | 85 kA |
| Short-time withstand current (Icw), 3 s | 65 kA |
| Power loss | 90 W |
| Electrical durability at ≤440 V | 12000 cycles |
| Electrical durability at 500–690 V | 12000 cycles |
| Mechanical durability | 20000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Integrated earth-fault protection | Yes |
| Optional motor operator | Yes |
| Product net width | 432 mm |
| Product net height | 461 mm |
| Product net depth | 396.5 mm |
| Product net weight | 64 kg |
| Standard | IEC |
The ABB 1SDA056583R1 is a 1250 A withdrawable air circuit breaker moving part used for switching and protecting demanding low-voltage electrical distribution systems, including main incomers and critical high-current distribution feeders.
The circuit breaker moving part has a rated uninterrupted current of 1250 A and is equipped with a PR123/P-LSIG R1250 electronic overcurrent release.
The PR123/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection together with advanced measurement and monitoring functionality.
The E3V 1250 has an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
The 1SDA056583R1 is a three-pole withdrawable air circuit breaker moving part designed for use with a compatible ABB SACE Emax fixed part and switchgear assembly.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, advanced electronic protection and maintainable withdrawable construction for critical industrial and commercial installations.