Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056563R1 SACE Emax E3V 1250 three-pole fixed air circuit breaker with 1250 A rated current, horizontal rear terminals, PR122/P-LI electronic protection and up to 130 kA ultimate short-circuit breaking capacity.
£9,237.89
The ABB 1SDA056563R1 is a high-performance SACE Emax E3V air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. Configured as an E3V 1250 PR122/P-LI, this three-pole fixed circuit breaker combines a rated uninterrupted current of 1250 A with ABB's advanced PR122/P electronic overcurrent release.
As part of the ABB SACE Emax series, the E3V 1250 is engineered for installations requiring high short-circuit performance, reliable operation and adjustable electronic protection. The PR122/P-LI release provides long-time overload and instantaneous short-circuit protection, helping safeguard switchboards, busbars, cables and connected equipment against damaging overcurrent conditions.
This configuration is a three-pole fixed circuit breaker with horizontal rear terminals and a rated operational voltage of 690 V AC. The E3V performance level provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC, making it suitable for high-fault-level industrial switchboards and critical power distribution systems.
Air circuit breakers such as the ABB SACE Emax E3V provide switching and protection for low-voltage electrical distribution systems where substantial prospective fault currents can occur. The E3V performance level offers high short-circuit interruption capability, helping protect switchboards, busbars, cables and connected equipment against damaging overload and short-circuit conditions.
The PR122/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection with adjustable current settings. Combined with the E3V's high breaking capacity and fixed switchboard construction, this makes the 1SDA056563R1 suitable for critical distribution circuits requiring dependable high-current protection.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| Order code | 1SDA056563R1 |
| EAN | 8015644579036 |
| Product type | Air circuit breaker |
| Frame | E3 |
| Performance level | V |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Installation | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Trip unit | PR122/P-LI R1250 |
| Release type | Electronic overcurrent release |
| Protection functions | Long-time and instantaneous (LI) |
| Overload release current setting | 500–1250 A |
| Instantaneous short-circuit adjustment range | 1875–18750 A |
| Ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 220–440 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 500–690 V AC | 85 kA |
| Short-time withstand current (Icw), 1 s | 85 kA |
| Short-time withstand current (Icw), 3 s | 65 kA |
| Power loss | 60 W |
| Electrical durability | 12000 cycles |
| Mechanical durability | 20000 cycles |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Open / closed |
| Integrated earth-fault protection | No |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Dimensions (W × H × D) | 404 × 418 × 302 mm |
| Net weight | approx. 60 kg |
| Standard | IEC |
The ABB 1SDA056563R1 is a 1250 A air circuit breaker used for switching and protecting low-voltage electrical distribution systems, including main incomers and high-performance distribution feeders.
The circuit breaker has a rated uninterrupted current of 1250 A and uses a PR122/P-LI R1250 electronic overcurrent release.
The PR122/P-LI electronic trip unit provides long-time overload protection and instantaneous short-circuit protection.
The E3V 1250 has an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
The 1SDA056563R1 is a three-pole fixed air circuit breaker equipped with horizontal rear terminals for integration into compatible low-voltage switchboards.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, adjustable electronic protection and robust construction for industrial and commercial installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.