Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056562R1 is a SACE Emax E3V 1250 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR121/P-LSIG R1250 electronic release providing long-time, short-time, instantaneous and earth-fault protection.
£10,602.93
The ABB E3V1250 PR121/P-LSIG, order code 1SDA056562R1, is a high-performance SACE Emax air circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. This three-pole fixed breaker has a rated uninterrupted current of 1250 A and is equipped with the PR121/P-LSIG R1250 electronic overcurrent release.
The PR121/P-LSIG release provides long-time, short-time, instantaneous and earth-fault protection. These LSIG functions help protect conductors, switchboards and connected equipment against sustained overloads, short circuits and earth faults, providing comprehensive electronic protection for critical power distribution applications.
This version features a fixed construction with rear horizontal terminals and is fitted with four auxiliary contacts together with circuit-breaker open/closed position indication. With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of up to 130 kA, the E3V1250 is engineered for demanding industrial, commercial and infrastructure switchboards.
Air circuit breakers such as the ABB SACE Emax E3V provide switching and overcurrent protection for major low-voltage distribution systems. The E3V performance level combines substantial short-circuit interruption capability with robust breaker construction, helping protect switchboards, conductors and connected equipment in installations where high prospective fault currents can occur.
The PR121/P-LSIG R1250 electronic release combines long-time protection against sustained overloads, short-time protection for coordinated fault clearing, instantaneous protection against severe short circuits and integrated earth-fault protection. Together with the 1250 A rating, up to 130 kA ultimate breaking capacity and fixed rear-horizontal-terminal construction, the 1SDA056562R1 provides comprehensive protection for demanding power distribution installations.
| Series | SACE Emax E3V |
|---|---|
| ABB order code | 1SDA056562R1 |
| Product type | Air circuit breaker |
| Frame / performance level | E3V |
| Rated current (In) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Current type | AC |
| Configuration | Fixed |
| Terminal connection | Rear horizontal |
| Trip unit | PR121/P-LSIG R1250 |
| Release type | Electronic |
| Protection functions | Long-time (L), short-time (S), instantaneous (I), earth fault (G) |
| Rated operational voltage | 690 V AC |
| Rated voltage | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Service short-circuit breaking capacity (Ics) | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Short-time withstand current (Icw) | 85 kA for 1 s; 65 kA for 3 s |
| Integrated earth-fault protection | Yes |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 60 W |
| Electrical durability | 12,000 cycles at ≤440 V; 12,000 cycles at 500–690 V |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 404 × 418 × 302 mm |
| Net weight | 60 kg |
| Standard | IEC |
| Customs tariff number | 85362090 |
| EAN | 8015644579029 |
The ABB 1SDA056562R1 is a SACE Emax E3V 1250 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR121/P-LSIG R1250 electronic overcurrent release.
The PR121/P-LSIG electronic release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.
The E3V1250 provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
This model is a fixed three-pole circuit breaker equipped with rear horizontal main terminals for integration into a compatible low-voltage switchboard.
Yes. The G in the PR121/P-LSIG designation identifies the integrated earth-fault protection function, complementing the long-time, short-time and instantaneous overcurrent protection functions.
ABB SACE Emax air circuit breakers combine high short-circuit performance, comprehensive electronic protection and robust switchboard integration to provide dependable protection for demanding industrial, commercial and infrastructure power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.