ABB 1SDA056549R1 SACE Emax E3V 800 three-pole withdrawable air circuit breaker moving part with 800 A rated current, PR122/P-LSIG electronic protection and up to 130 kA ultimate short-circuit breaking capacity.
£10,442.57
The ABB 1SDA056549R1 is a high-performance SACE Emax E3V air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Configured as an E3V 800 PR122/P-LSIG, this three-pole withdrawable unit combines a rated uninterrupted current of 800 A with ABB's advanced PR122/P electronic overcurrent release and comprehensive LSIG protection.
As part of the ABB SACE Emax series, the E3V 800 is engineered for applications requiring high short-circuit performance, selective protection and dependable operation. The PR122/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions, helping protect electrical installations against overloads, short circuits and earth faults while supporting coordinated protection throughout the distribution system.
This configuration is a three-pole withdrawable moving part with a rated operational voltage of 690 V AC. The E3V performance level provides an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC, making it suitable for high-fault-level industrial switchboards and critical power distribution systems.
Air circuit breakers such as the ABB SACE Emax E3V provide switching and protection for low-voltage electrical distribution systems where substantial prospective fault currents can occur. The E3V performance level offers high short-circuit interruption capability, helping protect switchboards, busbars, cables and connected equipment against damaging electrical faults.
The PR122/P-LSIG electronic trip unit combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection. These functions provide comprehensive protection for critical distribution circuits, while the withdrawable construction allows the breaker moving part to be isolated and removed from compatible switchgear for inspection and maintenance.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| Order code | 1SDA056549R1 |
| EAN | 8015644578893 |
| Product type | Air circuit breaker moving part |
| Frame | E3 |
| Performance level | V |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational current (Ie) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Installation | Withdrawable |
| Trip unit | PR122/P-LSIG R800 |
| Release type | Electronic overcurrent release |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Overload release current setting | 320–800 A |
| Instantaneous short-circuit adjustment range | 1200–12000 A |
| Ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 220–440 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 500–690 V AC | 85 kA |
| Short-time withstand current (Icw), 1 s | 85 kA |
| Short-time withstand current (Icw), 3 s | 65 kA |
| Power loss | 36 W |
| Electrical durability | 12000 cycles |
| Mechanical durability | 20000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Integrated earth-fault protection | Yes |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Dimensions (W × H × D) | 432 × 461 × 396.5 mm |
| Net weight | approx. 64 kg |
The ABB 1SDA056549R1 is an 800 A withdrawable air circuit breaker moving part used for switching and protecting low-voltage electrical distribution systems, including main incomers and high-performance distribution feeders.
The circuit breaker has a rated uninterrupted current of 800 A and uses a PR122/P-LSIG R800 electronic overcurrent release.
The PR122/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
The E3V 800 has an ultimate short-circuit breaking capacity of 130 kA at 220–440 V AC and 100 kA at 500–690 V AC.
The 1SDA056549R1 is a three-pole withdrawable air circuit breaker moving part designed for use within a compatible ABB SACE Emax fixed part and switchgear assembly.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, comprehensive electronic protection and maintainable withdrawable construction for industrial and commercial installations.