ABB 1SDA056544R1 is a SACE Emax E3V 800 A three-pole withdrawable air circuit breaker moving part with a PR121/P-LI electronic trip unit for high-performance low-voltage power distribution protection.
£8,844.63
The ABB 1SDA056544R1 is a high-performance SACE Emax E3V air circuit breaker (ACB) moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Identified as E3V800 PR121/P-LI In=800A 3P W MP, this three-pole withdrawable circuit breaker moving part combines an 800 A rated uninterrupted current with the ABB PR121/P-LI electronic overcurrent release.
As part of the ABB SACE Emax / New Emax range, the E3V800 is engineered for industrial, commercial and infrastructure power distribution applications requiring high fault-current interruption capability. The PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection, helping safeguard cables, busbars and connected electrical equipment against damaging overcurrent conditions.
This version features a three-pole withdrawable moving-part construction for use with the appropriate ABB SACE Emax fixed part. With an 800 A rated uninterrupted current, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC, the E3V800 is suited to distribution systems requiring high breaking performance together with convenient isolation and removal for servicing.
Air circuit breakers such as the ABB E3V800 provide switching and automatic protection for low-voltage electrical distribution systems. The PR121/P electronic release monitors circuit current and provides dedicated protection functions to help safeguard cables, busbars and downstream electrical equipment against overload and high-level short-circuit conditions.
The LI configuration combines long-time overload protection with instantaneous short-circuit protection. Together with the high breaking performance of the E3V frame and its withdrawable construction, this makes the 1SDA056544R1 suitable for distribution systems where dependable overcurrent protection, high fault-current interruption capability and convenient circuit breaker servicing are required.
| Series | SACE Emax / New Emax |
|---|---|
| ABB product group | 310513-New Emax |
| Order code | 1SDA056544R1 |
| Product type | Air circuit breaker moving part |
| Frame | E3V |
| Short-circuit performance level | V |
| Rated current | 800 A |
| Rated uninterrupted current | 800 A |
| Rated operational current | 800 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | PR121/P-LI |
| Release type | Electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Ultimate short-circuit breaking capacity | 130 kA at 220–440 V AC; 100 kA at 500–690 V AC |
| Service short-circuit breaking capacity | 100 kA at 220–440 V AC; 85 kA at 500–690 V AC |
| Rated short-time withstand current | 85 kA for 1 s; 65 kA for 3 s |
| Mounting type | Withdrawable |
| Breaker configuration | Moving part (MP) |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 12,000 cycles |
| Power loss | 36 W |
| Weight | 77 kg |
| Standard | IEC |
| EAN | 8015644578848 |
The ABB 1SDA056544R1 is an 800 A three-pole air circuit breaker moving part used for switching and protecting low-voltage electrical distribution systems in industrial, commercial and infrastructure installations.
The circuit breaker has a rated uninterrupted current of 800 A and uses the high-breaking-capacity ABB SACE Emax E3V frame.
The PR121/P-LI electronic release provides long-time overload protection and instantaneous short-circuit protection.
This model is a three-pole withdrawable moving part designed for use with the appropriate ABB SACE Emax fixed part, allowing the breaker to be disconnected and removed for inspection, maintenance or replacement.
The E3V800 has an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC and a rated short-time withstand current of 85 kA for 1 s.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection of low-voltage power distribution systems, combining high short-circuit performance, electronic protection and serviceable withdrawable construction for demanding industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.