Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056541R1 is a SACE Emax E3V800 800 A four-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSIG R800 electronic overcurrent release providing long-time, short-time, instantaneous and earth-fault protection for demanding low-voltage power distribution systems.
£12,766.60
The ABB 1SDA056541R1 is a high-performance SACE Emax E3V air circuit breaker designed for protection and switching in demanding low-voltage electrical distribution systems. Rated at 800 A, this four-pole fixed circuit breaker incorporates ABB’s PR122/P-LSIG R800 electronic overcurrent release for comprehensive protection of industrial, commercial and infrastructure power networks.
As part of the ABB SACE Emax range, the E3V800 combines very high short-circuit performance with advanced electronic protection. The PR122/P-LSIG trip unit provides long-time, short-time, instantaneous and earth-fault protection functions, helping protect electrical installations against overloads, short circuits and earth faults while supporting selective protection and coordination within low-voltage distribution systems.
The E3V800 PR122/P-LSIG has a rated uninterrupted current of 800 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 130 kA at 400 V AC. This version is supplied as a four-pole fixed circuit breaker with rear horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication for integration into demanding switchboard applications.
Air circuit breakers such as the ABB SACE Emax E3V800 provide switching, isolation and protection for important low-voltage distribution circuits. The four-pole configuration enables switching of three phase conductors and the neutral, making it suitable for electrical systems where complete four-pole isolation is required.
The PR122/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the E3V frame’s 130 kA ultimate breaking capacity at 400 V AC and fixed rear-horizontal-terminal construction, this makes the 1SDA056541R1 particularly suitable for main incomers, feeders and critical distribution circuits requiring comprehensive electronic protection and high fault-interruption performance.
| Product group | 310513-New Emax |
|---|---|
| Series | SACE Emax |
| Order code / MPN | 1SDA056541R1 |
| Product type | Air circuit breaker |
| Frame | E3V |
| Rated current (In) | 800 A |
| Rated operational current (Ie) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 4 |
| Execution | Fixed |
| Current type | AC |
| Trip unit | PR122/P-LSIG R800 electronic overcurrent release |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and earth-fault (LSIG) |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics) at 400 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 85 kA |
| Rated short-time withstand current (Icw) | 85 kA for 1 s |
| Main terminal arrangement | Rear horizontal |
| Power loss | 22 W |
| Electrical durability at up to 440 V | 12000 cycles |
| Electrical durability at 500–690 V | 12000 cycles |
| Mechanical durability | 20000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Standard | IEC |
| EAN | 8015644578817 |
| HS code | 85362090 |
| Product net weight | 90 kg |
The ABB 1SDA056541R1 is a SACE Emax E3V800 air circuit breaker used for switching and protecting low-voltage electrical distribution circuits, particularly applications requiring four-pole switching, high breaking capacity and comprehensive LSIG protection.
The circuit breaker has a rated uninterrupted current of 800 A and is equipped with a PR122/P-LSIG R800 electronic overcurrent release.
The PR122/P-LSIG electronic overcurrent release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.
The E3V800 has a rated ultimate short-circuit breaking capacity of 130 kA at 400 V AC and 100 kA at 690 V AC. Its rated service short-circuit breaking capacity is 100 kA at 400 V AC and 85 kA at 690 V AC.
The 1SDA056541R1 is a four-pole fixed air circuit breaker with rear horizontal terminals for integration into compatible ABB SACE Emax low-voltage switchgear assemblies.
ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution systems, combining high breaking performance with advanced electronic protection for industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.