Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056530R1 SACE Emax E3V 800 three-pole fixed air circuit breaker with 800 A rated current, horizontal rear terminals, PR121/P-LSIG electronic protection and up to 130 kA ultimate short-circuit breaking capacity.
£10,237.67
The ABB 1SDA056530R1 is a high-performance SACE Emax E3V air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. Configured as an E3V 800 PR121/P-LSIG, this three-pole fixed circuit breaker combines a rated uninterrupted current of 800 A with ABB's PR121/P electronic overcurrent release and comprehensive LSIG protection.
As part of the ABB SACE Emax series, the E3V 800 is engineered for installations requiring high short-circuit performance, selective protection and dependable operation. The PR121/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions, helping safeguard electrical installations against overloads, short circuits and earth faults.
This configuration is a three-pole fixed circuit breaker with horizontal rear terminals and a rated operational voltage of 690 V AC. The E3V performance level provides an ultimate short-circuit breaking capacity of 130 kA at 380–440 V AC and 100 kA at 500–690 V AC, making it suitable for high-fault-level industrial switchboards and critical power distribution systems.
Air circuit breakers such as the ABB SACE Emax E3V provide switching and protection for low-voltage electrical distribution systems where substantial prospective fault currents can occur. The E3V performance level offers high short-circuit interruption capability, helping protect switchboards, busbars, cables and connected equipment against damaging electrical faults.
The PR121/P-LSIG electronic trip unit combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection. These functions provide comprehensive protection for critical distribution circuits while supporting coordination with other protective devices throughout the electrical installation.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| Order code | 1SDA056530R1 |
| EAN | 8015644578701 |
| Product type | Air circuit breaker |
| Frame | E3 |
| Performance level | V |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational current (Ie) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Installation | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Trip unit | PR121/P-LSIG R800 |
| Release type | Electronic overcurrent release |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Overload release adjustment range | 320–800 A |
| Short-time delayed short-circuit adjustment range | 800–8000 A |
| Instantaneous short-circuit adjustment range | 1200–12000 A |
| Ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 220–440 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) at 500–690 V AC | 85 kA |
| Short-time withstand current (Icw), 1 s | 85 kA |
| Short-time withstand current (Icw), 3 s | 65 kA |
| Power loss | 22 W |
| Mechanical durability | 20000 cycles |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Open / closed |
| Integrated earth-fault protection | Yes |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Standard | IEC |
| Weight | approx. 72 kg |
The ABB 1SDA056530R1 is an 800 A air circuit breaker used for switching and protecting low-voltage electrical distribution systems, including main incomers and high-performance distribution feeders.
The circuit breaker has a rated uninterrupted current of 800 A and uses a PR121/P-LSIG R800 electronic overcurrent release.
The PR121/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
The E3V 800 has an ultimate short-circuit breaking capacity of 130 kA at 380–440 V AC and 100 kA at 500–690 V AC.
The 1SDA056530R1 is a three-pole fixed air circuit breaker equipped with horizontal rear terminals for integration into compatible low-voltage switchboards.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, comprehensive electronic protection and robust construction for industrial and commercial installations.
We use cookies