1SDA056530R1 ABB E3V 800 PR121/P-LSIG 800 A Air Circuit Breaker

1SDA056530R1 ABB E3V 800 PR121/P-LSIG 800 A Air Circuit Breaker

ABB 1SDA056530R1 SACE Emax E3V 800 three-pole fixed air circuit breaker with 800 A rated current, horizontal rear terminals, PR121/P-LSIG electronic protection and up to 130 kA ultimate short-circuit breaking capacity.

SKU: 1SDA056530R1MPN: 1SDA056530R1
Price
List Price £13,650.22 ex VAT
Your Price (ex VAT) Save 25%
£10,237.67 25% OFF
You save £3,412.56 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,237.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,237.67

Why Choose the ABB 1SDA056530R1 E3V 800 Air Circuit Breaker?

The ABB 1SDA056530R1 is a high-performance SACE Emax E3V air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. Configured as an E3V 800 PR121/P-LSIG, this three-pole fixed circuit breaker combines a rated uninterrupted current of 800 A with ABB's PR121/P electronic overcurrent release and comprehensive LSIG protection.

As part of the ABB SACE Emax series, the E3V 800 is engineered for installations requiring high short-circuit performance, selective protection and dependable operation. The PR121/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions, helping safeguard electrical installations against overloads, short circuits and earth faults.

This configuration is a three-pole fixed circuit breaker with horizontal rear terminals and a rated operational voltage of 690 V AC. The E3V performance level provides an ultimate short-circuit breaking capacity of 130 kA at 380–440 V AC and 100 kA at 500–690 V AC, making it suitable for high-fault-level industrial switchboards and critical power distribution systems.

Key Advantages

  • High-performance ABB SACE Emax E3V air circuit breaker for demanding low-voltage distribution systems.
  • 800 A rated uninterrupted current for industrial and commercial power distribution.
  • PR121/P-LSIG electronic trip unit providing comprehensive adjustable circuit protection.
  • High 130 kA ultimate short-circuit breaking capacity at 380–440 V AC.
  • LSIG protection covers long-time, short-time, instantaneous and ground-fault functions.
  • Fixed three-pole construction with horizontal rear terminals for switchboard installation.
  • Fitted with four auxiliary change-over contacts and circuit breaker open/closed position indication.

Key Features

  • ABB SACE Emax E3V 800 series.
  • 800 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed circuit breaker construction.
  • Horizontal rear terminals.
  • PR121/P-LSIG electronic overcurrent release.
  • LSIG protection functions for overload, selective short-circuit, instantaneous short-circuit and ground-fault protection.
  • 690 V AC rated operational voltage.
  • 130 kA Icu at 220–440 V AC.
  • 100 kA Icu at 500–690 V AC.
  • 85 kA short-time withstand current for 1 s.
  • Integrated earth-fault protection.

Comprehensive Protection for High-Performance Power Distribution

Air circuit breakers such as the ABB SACE Emax E3V provide switching and protection for low-voltage electrical distribution systems where substantial prospective fault currents can occur. The E3V performance level offers high short-circuit interruption capability, helping protect switchboards, busbars, cables and connected equipment against damaging electrical faults.

The PR121/P-LSIG electronic trip unit combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and ground-fault protection. These functions provide comprehensive protection for critical distribution circuits while supporting coordination with other protective devices throughout the electrical installation.

Typical Applications

  • Main incoming circuit protection in low-voltage switchboards.
  • Industrial power distribution systems.
  • High-fault-level distribution feeders.
  • Manufacturing and process plant electrical systems.
  • Commercial and infrastructure power distribution.
  • Generator and transformer distribution systems.
  • Fixed switchgear requiring comprehensive LSIG electronic protection.

Technical Specifications

Series SACE Emax
Product group 310513-New Emax
Order code 1SDA056530R1
EAN 8015644578701
Product type Air circuit breaker
Frame E3
Performance level V
Rated current (In) 800 A
Rated uninterrupted current (Iu) 800 A
Rated operational current (Ie) 800 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Installation Fixed
Terminal arrangement Horizontal rear terminals
Trip unit PR121/P-LSIG R800
Release type Electronic overcurrent release
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Overload release adjustment range 320–800 A
Short-time delayed short-circuit adjustment range 800–8000 A
Instantaneous short-circuit adjustment range 1200–12000 A
Ultimate short-circuit breaking capacity (Icu) at 220–440 V AC 130 kA
Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 220–440 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 500–690 V AC 85 kA
Short-time withstand current (Icw), 1 s 85 kA
Short-time withstand current (Icw), 3 s 65 kA
Power loss 22 W
Mechanical durability 20000 cycles
Auxiliary contacts 4 change-over contacts
Position indication Open / closed
Integrated earth-fault protection Yes
Integrated motor operator No
Optional motor operator Yes
Standard IEC
Weight approx. 72 kg

Frequently Asked Questions

What is the ABB 1SDA056530R1 used for?

The ABB 1SDA056530R1 is an 800 A air circuit breaker used for switching and protecting low-voltage electrical distribution systems, including main incomers and high-performance distribution feeders.

What is the rated current of the ABB 1SDA056530R1?

The circuit breaker has a rated uninterrupted current of 800 A and uses a PR121/P-LSIG R800 electronic overcurrent release.

What protection does the PR121/P-LSIG trip unit provide?

The PR121/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.

What is the breaking capacity of the E3V 800?

The E3V 800 has an ultimate short-circuit breaking capacity of 130 kA at 380–440 V AC and 100 kA at 500–690 V AC.

Is the ABB 1SDA056530R1 fixed or withdrawable?

The 1SDA056530R1 is a three-pole fixed air circuit breaker equipped with horizontal rear terminals for integration into compatible low-voltage switchboards.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, comprehensive electronic protection and robust construction for industrial and commercial installations.