Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB E3H3200PR121/P-LSIG is a 3200 A four-pole SACE Emax withdrawable air circuit breaker moving part with a PR121/P-LSIG R3200 electronic overcurrent release providing long-time, short-time, instantaneous and ground-fault protection for demanding high-current low-voltage power distribution systems.
£33,399.27
The ABB E3H3200PR121/P-LSIG is a high-performance four-pole withdrawable air circuit breaker moving part designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax E3H series, this configuration combines a 3200 A rated uninterrupted current with the PR121/P-LSIG R3200 electronic overcurrent release.
The PR121/P-LSIG R3200 electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. These LSIG functions provide comprehensive protection for conductors, busbars, switchgear and connected equipment while supporting selective coordination in high-current distribution networks.
The ABB 1SDA056522R1 is specifically configured as the four-pole moving portion of a withdrawable E3H3200 circuit breaker. Rated for operation up to 690 V AC, it provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and incorporates four auxiliary contacts with circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E3H provide protection, switching and isolation for major low-voltage distribution circuits. The E3H platform combines high short-circuit interruption capability with electronic protection, making it suitable for main incomers, bus couplers, high-current feeders and other critical circuits where substantial load and prospective fault currents may occur.
The PR121/P-LSIG R3200 release combines long-time protection against sustained overloads, short-time delayed protection for selective short-circuit clearing, instantaneous protection against severe faults and dedicated ground-fault protection. Its withdrawable construction allows the moving portion to interface with the appropriate E3 fixed part, supporting inspection, servicing and replacement within suitably configured draw-out switchgear assemblies.
| Series | SACE Emax E3H |
|---|---|
| Extended product type | E3H3200PR121/P-LSIGIn=3200A4pWMP |
| ABB order code | 1SDA056522R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame | E3H3200 |
| Rated current (In) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Trip unit | PR121/P-LSIG R3200 |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Short-circuit performance level | H |
| Power loss | 570 W |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability at ≤440 V | 6,000 cycles |
| Electrical durability at 500–690 V | 5,000 cycles |
| Electrical operating frequency | 20 cycles per hour |
| Execution | Withdrawable |
| Component | Moving part (W MP) |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Standard | IEC |
| Product net width | 558 mm |
| Product net height | 461 mm |
| Product net depth | 396.5 mm |
| Product net weight | 81 kg |
| HS code | 85362090 |
| EAN | 8015644578626 |
This SACE Emax moving part is designed for protection, switching and isolation of high-current low-voltage distribution circuits when installed with the appropriate E3 withdrawable fixed part.
The ABB 1SDA056522R1 E3H3200 circuit breaker moving part has a rated uninterrupted current of 3200 A.
The PR121/P-LSIG R3200 electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection.
The 1SDA056522R1 is a four-pole withdrawable moving part (W MP) designed for use with the appropriate ABB E3 withdrawable fixed part.
The E3H3200 configuration provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC, with a rated service breaking capacity of 85 kA.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where comprehensive electronic protection, high fault-current interruption capability and maintainable withdrawable switchgear configurations are essential.
We use cookies