ABB 1SDA056506R1 E3H3200 is a 3200 A four-pole fixed SACE Emax air circuit breaker with rear horizontal terminals and a PR121/P-LSIG R3200 electronic release providing comprehensive LSIG protection for high-current low-voltage power distribution systems.
£28,149.95
The ABB E3H3200 PR121/P-LSIG, order code 1SDA056506R1, is a high-performance 3200 A four-pole fixed air circuit breaker from the ABB SACE Emax E3 series, engineered for switching and protection in demanding low-voltage power distribution systems. This E3H configuration combines high-current switching capability with the PR121/P-LSIG R3200 electronic overcurrent release.
The PR121/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection, helping protect cables, busbars, transformers and connected equipment against overloads, short circuits and earth faults. Its LSIG protection functions make the breaker suitable for coordinated distribution systems requiring comprehensive electronic fault protection.
With a rated uninterrupted current of 3200 A, a four-pole configuration and operation up to 690 V AC, the E3H3200 is suited to substantial three-phase distribution systems requiring neutral switching. The fixed breaker uses rear horizontal terminals and provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC.
Air circuit breakers such as the ABB SACE Emax E3H3200 provide switching, isolation and electronic overcurrent protection for high-current low-voltage electrical systems. The PR121/P-LSIG release provides long-time, short-time, instantaneous and ground-fault functions to protect distribution equipment against a broad range of abnormal current conditions.
The fixed SACE Emax construction is suitable for switchboards requiring a permanently installed high-current protection device. Its four-pole design, 3200 A current rating, comprehensive LSIG protection and high short-circuit performance make this E3H3200 configuration suitable for main distribution boards, industrial switchgear and critical power distribution installations.
| Series | SACE Emax E3 |
|---|---|
| ABB order code | 1SDA056506R1 |
| EAN | 8015644578466 |
| Product type | Air circuit breaker |
| Short-circuit performance level | H |
| Rated current (In) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Number of poles | 4P |
| Version | Fixed |
| Terminal arrangement | Rear horizontal |
| Release | PR121/P-LSIG R3200 |
| Release type | Electronic |
| Protection functions | L, S, I, G |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 220–500 V AC; 85 kA at 660–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 85 kA at 220–690 V AC |
| Rated short-time withstand current (Icw) | 75 kA for 1 s; 65 kA for 3 s |
| Overload release setting range | 1280–3200 A |
| Short-time short-circuit setting range | 3200–32000 A |
| Instantaneous short-circuit setting range | 4800–48000 A |
| Integrated ground-fault protection | Yes |
| Degree of protection | IP2X |
| Auxiliary contacts | 4 (2 NO + 2 NC) |
| Position indication | Circuit breaker open / closed |
| Motor operator | Optional |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 6,000 cycles at up to 440 V AC; 5,000 cycles at 500–690 V AC |
| Power loss | 330 W |
| Dimensions (W × H × D) | 530 × 418 × 302 mm |
| Net weight | 76 kg |
| Standard | IEC |
It is a 3200 A four-pole fixed SACE Emax air circuit breaker designed for switching and protecting high-current low-voltage power distribution circuits.
The breaker is fitted with an ABB PR121/P-LSIG R3200 electronic overcurrent release, providing long-time, short-time, instantaneous and ground-fault protection.
The E3H3200 has a rated uninterrupted current of 3200 A and uses a four-pole configuration.
The E3H3200 H-performance breaker provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC.
The 1SDA056506R1 is a fixed-version SACE Emax E3H3200 air circuit breaker equipped with rear horizontal terminals.
ABB SACE Emax air circuit breakers are engineered for demanding low-voltage power distribution applications, combining electronic protection, high fault-clearing performance and robust fixed construction for industrial and commercial electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.