Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB E3H3200PR121/P-LSI is a 3200 A four-pole fixed SACE Emax air circuit breaker with rear horizontal terminals and a PR121/P-LSI R3200 electronic overcurrent release providing long-time, short-time and instantaneous protection for demanding high-current low-voltage power distribution systems.
£27,254.00
The ABB E3H3200PR121/P-LSI is a high-performance four-pole fixed air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax E3H series, this configuration combines a 3200 A rated uninterrupted current with the PR121/P-LSI R3200 electronic overcurrent release.
The PR121/P-LSI R3200 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. These LSI functions help protect conductors, busbars, switchgear and connected equipment against sustained overloads and severe short circuits while supporting selective coordination within high-current distribution networks.
The ABB 1SDA056505R1 is specifically configured as a four-pole fixed E3H3200 circuit breaker with rear horizontal terminals. It is rated for operation up to 690 V AC, provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC, and incorporates four auxiliary contacts with circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E3H provide protection, switching and isolation for major low-voltage distribution circuits. The E3H platform combines high short-circuit interruption capability with electronic protection, making it suitable for main incomers, bus couplers, high-current feeders and other critical circuits where substantial load and prospective fault currents may occur.
The PR121/P-LSI R3200 release combines long-time protection against sustained overloads, short-time delayed protection for coordinated short-circuit clearing and instantaneous protection against severe faults. Together with its fixed four-pole construction and rear horizontal terminals, the E3H3200 provides a robust solution for permanently installed high-current switchboards and power-distribution assemblies.
| Series | SACE Emax E3H |
|---|---|
| Extended product type | E3H 3200 PR121/P-LSI In=3200A 4p F HR |
| ABB order code | 1SDA056505R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker (ACB) |
| Frame | E3H3200 |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 4 |
| Trip unit | PR121/P-LSI R3200 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload release current setting | 400–3200 A |
| Short-time delayed short-circuit adjustment | 3200–32000 A |
| Instantaneous short-circuit adjustment | 4800–48000 A |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 220–690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Short-circuit performance level | H |
| Mounting type | Fixed |
| Terminal arrangement | Rear horizontal terminals |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Standard | IEC |
| Weight | 90 kg |
| HS code | 85362090 |
| EAN | 8015644578459 |
This SACE Emax air circuit breaker is designed for protection, switching and isolation of high-current low-voltage distribution circuits in industrial, commercial and infrastructure installations.
The ABB 1SDA056505R1 E3H3200 air circuit breaker has a rated uninterrupted current of 3200 A.
The PR121/P-LSI R3200 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The 1SDA056505R1 is a four-pole fixed air circuit breaker supplied with rear horizontal terminals.
The E3H3200 configuration provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC, with a service breaking capacity of 85 kA.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where selective electronic protection, high fault-current interruption capability and dependable high-current switching are essential.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.