Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB E3H3200PR121/P-LI is a 3200 A four-pole fixed SACE Emax air circuit breaker with rear horizontal terminals and a PR121/P-LI R3200 electronic overcurrent release providing long-time and instantaneous protection for demanding high-current low-voltage power distribution systems.
£26,706.42
The ABB E3H3200PR121/P-LI is a high-performance four-pole fixed air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax E3H series, this configuration combines a 3200 A rated uninterrupted current with the PR121/P-LI R3200 electronic overcurrent release.
The PR121/P-LI R3200 electronic trip unit provides long-time overload and instantaneous short-circuit protection. These LI protection functions help safeguard conductors, busbars, switchgear and connected equipment against sustained overloads and severe short-circuit conditions, making the breaker well suited to high-current industrial, commercial and infrastructure distribution networks.
The ABB 1SDA056504R1 is specifically configured as a four-pole fixed E3H3200 circuit breaker with rear horizontal terminals. It is rated for operation up to 690 V AC, provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC, and is fitted with four auxiliary change-over contacts plus circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E3H provide protection, switching and isolation for major low-voltage distribution circuits. The E3H platform combines high short-circuit interruption capability with electronic protection, making it suitable for main incomers, high-current feeders and other critical circuits where substantial load and prospective fault currents may occur.
The PR121/P-LI R3200 release combines long-time protection against sustained overload conditions with instantaneous protection against severe short circuits. Together with its fixed four-pole construction and rear horizontal terminals, the E3H3200 provides a robust solution for permanently installed high-current switchboards and power-distribution assemblies.
| Series | SACE Emax E3H |
|---|---|
| Extended product type | E3H 3200 PR121/P-LI In=3200A 4p F HR |
| ABB order code | 1SDA056504R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker (ACB) |
| Frame | E3H3200 |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Trip unit | PR121/P-LI R3200 |
| Release type | Electronic overcurrent release |
| Protection functions | Long-time and instantaneous (LI) |
| Overload release current setting | 1280–3200 A |
| Instantaneous short-circuit release adjustment | 4800–48000 A |
| Integrated ground-fault protection | No |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 220–690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Short-circuit performance level | H |
| Power loss | 330 W |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability at up to 440 V | 6,000 cycles |
| Electrical durability at 500–690 V | 5,000 cycles |
| Electrical operating frequency | 20 cycles per hour |
| Mounting type | Fixed |
| Terminal arrangement | Rear horizontal terminals |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Complete device with protection unit | Yes |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Standard | IEC |
| Weight | 90 kg |
| HS code | 85362090 |
| EAN | 8015644578442 |
This SACE Emax air circuit breaker is designed for protection, switching and isolation of high-current low-voltage distribution circuits in industrial, commercial and infrastructure installations.
The ABB 1SDA056504R1 E3H3200 air circuit breaker has a rated uninterrupted current of 3200 A.
The PR121/P-LI R3200 electronic trip unit provides long-time overload and instantaneous short-circuit protection.
The 1SDA056504R1 is a four-pole fixed air circuit breaker supplied with rear horizontal terminals.
The E3H3200 configuration provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where dependable electronic protection, high fault-current interruption capability and reliable high-current switching are essential.
We use cookies