Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056492R1 is a SACE Emax E3H2500 2500 A four-pole withdrawable air circuit breaker moving part with a PR122/P-LSI R2500 electronic overcurrent release providing long-time, short-time and instantaneous protection for high-current low-voltage power distribution systems.
£23,521.79
The ABB 1SDA056492R1 is a high-performance SACE Emax E3H air circuit breaker moving part designed for protection and switching in high-current low-voltage electrical distribution systems. Rated at 2500 A, this four-pole withdrawable configuration incorporates ABB’s PR122/P-LSI R2500 electronic overcurrent release for advanced protection of industrial, commercial and infrastructure power networks.
As part of the ABB SACE Emax range, the E3H2500 combines high short-circuit performance with configurable electronic protection. The PR122/P-LSI trip unit provides long-time, short-time and instantaneous protection functions, helping safeguard electrical installations against overloads and short circuits while supporting selective protection and coordination within low-voltage distribution systems.
The E3H2500 PR122/P-LSI has a rated uninterrupted current of 2500 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 100 kA at 400 V AC. This version is supplied as a four-pole withdrawable moving part, with four auxiliary contacts and circuit-breaker open/closed position indication for integration into maintainable high-current switchboards.
Air circuit breakers such as the ABB SACE Emax E3H2500 provide switching, isolation and protection for high-current low-voltage distribution circuits. The four-pole configuration enables switching of three phase conductors and the neutral, making it suitable for electrical systems where complete four-pole isolation is required.
The PR122/P-LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Combined with the withdrawable Emax construction and high short-circuit performance, this makes the 1SDA056492R1 particularly suitable for main incomers, high-current feeders and other critical circuits where selective protection, four-pole switching and convenient maintenance are required.
| Product group | 310513-New Emax |
|---|---|
| Series | SACE Emax |
| Order code / MPN | 1SDA056492R1 |
| Product type | Air circuit breaker moving part |
| Frame | E3H |
| Rated current | 2500 A |
| Rated operational current (Ie) | 2500 A |
| Rated uninterrupted current (Iu) | 2500 A |
| Number of poles | 4 |
| Execution | Withdrawable moving part |
| Current type | AC |
| Trip unit | PR122/P-LSI R2500 electronic overcurrent release |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 400 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 85 kA |
| Rated short-time withstand current (Icw) | 75 kA for 1 s |
| Short-circuit performance level | H |
| Power loss | 350 W |
| Electrical durability at up to 440 V | 8000 cycles |
| Electrical durability at 500–690 V | 7000 cycles |
| Mechanical durability | 20000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Standard | IEC |
| Product dimensions (W × H × D) | 558 × 461 × 396.5 mm |
| Product net weight | 81 kg |
| EAN | 8015644578329 |
| HS code | 85362090 |
The ABB 1SDA056492R1 is a SACE Emax E3H2500 air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits, particularly applications requiring four-pole switching and LSI protection.
The circuit breaker moving part has a rated uninterrupted current of 2500 A and is equipped with a PR122/P-LSI R2500 electronic overcurrent release.
The PR122/P-LSI electronic overcurrent release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The E3H2500 has a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC and 85 kA at 690 V AC, with a rated service short-circuit breaking capacity of 85 kA.
The 1SDA056492R1 is a four-pole withdrawable moving part for the ABB SACE Emax E3H2500 circuit breaker system, supporting convenient inspection, servicing and replacement within compatible switchgear.
ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution systems, combining high breaking performance with advanced electronic protection and maintainable withdrawable configurations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.