1SDA056480R1 ABB E3H2500 PR121/P-LI 2500A 3-Pole Withdrawable Air Circuit Breaker

1SDA056480R1 ABB E3H2500 PR121/P-LI 2500A 3-Pole Withdrawable Air Circuit Breaker

ABB 1SDA056480R1 is a SACE Emax E3H2500 2500 A three-pole withdrawable air circuit breaker moving part with a PR121/P-LI R2500 electronic overcurrent release for high-current low-voltage power distribution protection.

SKU: 1SDA056480R1MPN: 1SDA056480R1
Price
List Price £26,104.80 ex VAT
Your Price (ex VAT) Save 25%
£19,578.60 25% OFF
You save £6,526.20 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £19,578.60
Trade pricing is personalised to your account

Manufacturer Lead Time

£19,578.60

Why Choose the ABB E3H2500 PR121/P-LI 2500A Air Circuit Breaker?

The ABB 1SDA056480R1 is a high-performance SACE Emax E3H air circuit breaker moving part designed for protection and switching in high-current low-voltage electrical distribution systems. Rated at 2500 A, this three-pole withdrawable configuration incorporates ABB’s PR121/P-LI R2500 electronic overcurrent release for dependable overload and short-circuit protection in industrial, commercial and infrastructure power networks.

As part of the ABB SACE Emax range, the E3H2500 combines high short-circuit performance with electronic protection. The PR121/P-LI trip unit provides long-time overload and instantaneous short-circuit protection, helping safeguard switchboards, cables and connected electrical equipment against damaging overcurrents.

The E3H2500 PR121/P-LI has a rated uninterrupted current of 2500 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 100 kA at 400 V AC. This version is supplied as a three-pole withdrawable moving part with four auxiliary contacts and circuit-breaker open/closed position indication, making it particularly suitable for maintainable high-current switchboards and critical power distribution assemblies.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker moving part for low-voltage power distribution.
  • 2500 A rated current for demanding high-current installations.
  • PR121/P-LI R2500 electronic overcurrent release for dependable circuit protection.
  • LI protection provides long-time overload and instantaneous short-circuit protection.
  • 100 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Three-pole withdrawable construction supports efficient inspection, servicing and circuit-breaker replacement.

Key Features

  • ABB SACE Emax E3H2500 circuit breaker moving part.
  • 2500 A rated uninterrupted current.
  • Three-pole withdrawable configuration.
  • PR121/P-LI R2500 electronic overcurrent release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • 690 V AC rated operational voltage.
  • 100 kA Icu at 400 V AC.
  • 85 kA Ics at 400 V AC.
  • 75 kA short-time withstand current for 1 s.
  • 12 kV rated impulse withstand voltage.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Advanced Circuit Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E3H2500 provide switching and protection for high-current low-voltage distribution circuits. The E3H high-breaking-capacity design enables substantial fault currents to be interrupted safely, helping protect switchboards, cables and connected electrical equipment in demanding industrial and commercial power distribution environments.

The PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. Combined with the withdrawable Emax construction and 2500 A current rating, this makes the 1SDA056480R1 particularly suitable for main incomers, high-current feeders and other critical circuits where dependable protection and convenient switchboard maintenance are required.

Typical Applications

  • Low-voltage main distribution switchboards.
  • High-current industrial power distribution systems.
  • Main incomer and feeder circuit protection.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Power distribution centres and withdrawable switchgear assemblies.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax
Extended product type E3H2500PR121/P-LIIn=2500A3pWMP
Order code / MPN 1SDA056480R1
Product type Air circuit breaker moving part
Frame E3H
Rated current 2500 A
Rated operational current (Ie) 2500 A
Rated uninterrupted current (Iu) 2500 A
Number of poles 3
Execution Withdrawable moving part
Current type AC
Trip unit PR121/P-LI R2500 electronic overcurrent release
Protection functions Long-time and instantaneous (LI)
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 85 kA
Rated short-time withstand current (Icw) 75 kA for 1 s
Instantaneous short-circuit adjustment range 3750–37500 A
Short-circuit performance level H
Power loss 350 W
Electrical durability at up to 440 V 8000 cycles
Electrical durability at 500–690 V 7000 cycles
Mechanical durability 20000 cycles
Auxiliary contacts 4 (2 normally open and 2 normally closed)
Position indication Circuit breaker open/closed
Standard IEC
Product dimensions (W × H × D) 432 × 461 × 396.5 mm
Product net weight 64 kg
EAN 8015644578206
HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA056480R1 used for?

The ABB 1SDA056480R1 is a SACE Emax E3H2500 air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure switchboards.

What is the rated current of the ABB E3H2500 1SDA056480R1?

The circuit breaker moving part has a rated uninterrupted current of 2500 A and is equipped with a PR121/P-LI R2500 electronic overcurrent release.

What protection functions does the PR121/P-LI trip unit provide?

The PR121/P-LI electronic overcurrent release provides long-time overload and instantaneous short-circuit protection.

What is the breaking capacity of the ABB E3H2500?

The E3H2500 has a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC and 85 kA at 690 V AC, with a rated service short-circuit breaking capacity of 85 kA.

Is the ABB 1SDA056480R1 fixed or withdrawable?

The 1SDA056480R1 is a three-pole withdrawable moving part for the ABB SACE Emax E3H2500 circuit breaker system, supporting convenient inspection, servicing and replacement within compatible switchgear.

Trusted ABB Protection for Critical Power Systems

ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution systems, combining high breaking performance with electronic protection and maintainable withdrawable configurations.