1SDA056458R1 ABB E3H2000PR121/P-LSIG 2000 A 4-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA056458R1 ABB E3H2000PR121/P-LSIG 2000 A 4-Pole Withdrawable Air Circuit Breaker Moving Part

ABB E3H2000PR121/P-LSIG is a 2000 A four-pole SACE Emax withdrawable air circuit breaker moving part with a PR121/P-LSIG R2000 electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection for demanding low-voltage power distribution systems.

SKU: 1SDA056458R1MPN: 1SDA056458R1
Price
List Price £24,719.61 ex VAT
Your Price (ex VAT) Save 25%
£18,539.71 25% OFF
You save £6,179.90 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £18,539.71
Trade pricing is personalised to your account

Manufacturer Lead Time

£18,539.71

Why Choose the ABB E3H2000PR121/P-LSIG Air Circuit Breaker?

The ABB E3H2000PR121/P-LSIG is a high-performance four-pole withdrawable air circuit breaker moving part designed for comprehensive protection, switching and isolation in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax E3H series, this configuration combines a 2000 A rated uninterrupted current with the PR121/P-LSIG electronic overcurrent release.

The PR121/P-LSIG R2000 electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. These LSIG functions help protect conductors, switchgear and connected equipment against sustained overloads, severe phase faults and ground-fault conditions while supporting coordinated protection throughout low-voltage distribution networks.

The ABB 1SDA056458R1 is specifically configured as the four-pole moving portion of a withdrawable E3H2000 circuit breaker. It is rated for operation up to 690 V AC, offers an ultimate short-circuit breaking capacity of 100 kA at 400 V AC, and is fitted with four auxiliary change-over contacts plus open/closed circuit-breaker position indication.

Key Advantages

  • High-performance ABB SACE Emax E3H air circuit breaker moving part for demanding low-voltage distribution systems.
  • 2000 A rated uninterrupted current for high-current electrical installations.
  • Four-pole configuration for four-conductor switching and protection.
  • PR121/P-LSIG electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection.
  • 100 kA Icu at 400 V AC for installations with high prospective fault currents.
  • Withdrawable moving-part construction supports maintainable draw-out switchgear installations.
  • Four auxiliary change-over contacts and open/closed position indication support switchboard monitoring and control.

Key Features

  • ABB SACE Emax E3H series.
  • 2000 A rated uninterrupted current.
  • Four-pole circuit breaker configuration.
  • PR121/P-LSIG R2000 electronic overcurrent release.
  • LSIG protection functions: long-time, short-time, instantaneous and ground fault.
  • 690 V AC rated operational voltage.
  • 100 kA Icu at 220–500 V AC.
  • 85 kA Icu at 660–690 V AC.
  • Withdrawable moving part (W MP) configuration.
  • Four auxiliary change-over contacts with circuit-breaker open/closed position indication.

Comprehensive LSIG Protection for High-Current Distribution

Air circuit breakers such as the ABB SACE Emax E3H provide switching, isolation and protection for major low-voltage distribution circuits. The E3H platform combines high short-circuit interruption capability with electronic protection, making it suitable for main incomers, bus couplers and other critical circuits where substantial load and prospective fault currents may occur.

The PR121/P-LSIG release combines long-time, short-time, instantaneous and ground-fault protection to provide comprehensive coverage against common distribution-system fault conditions. Its withdrawable construction allows the moving portion to interface with the appropriate fixed part, supporting inspection, servicing and replacement within suitably configured draw-out switchgear assemblies.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Withdrawable industrial switchgear assemblies.
  • Main incomer and bus-coupler applications.
  • Industrial power distribution systems requiring ground-fault protection.
  • Manufacturing plants and process facilities.
  • Power distribution centres and electrical substations.
  • Generator and transformer distribution systems.

Technical Specifications

Series SACE Emax E3H
ABB order code 1SDA056458R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Frame E3H2000
Rated uninterrupted current (Iu) 2000 A
Rated operational current (Ie) 2000 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 4
Trip unit PR121/P-LSIG R2000
Release type Electronic
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Overload release current setting 800–2000 A
Short-time delayed short-circuit adjustment 2000–20000 A
Instantaneous short-circuit adjustment 3000–30000 A
Integrated ground-fault protection Yes
Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 380–400 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 220–690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Short-circuit performance level H
Power loss 225 W
Mechanical durability 20,000 cycles
Mechanical operating frequency 60 cycles per hour
Electrical durability at 690 V 9,000 cycles
Electrical operating frequency 20 cycles per hour
Execution Withdrawable
Component Moving part (MP)
Auxiliary contacts 4 change-over contacts
Position indication Open / closed
Motor drive integrated No
Motor drive Optional
Standard IEC
Weight 96 kg
HS code 85362090
EAN 8015644577988

Frequently Asked Questions

What is the ABB E3H2000PR121/P-LSIG 1SDA056458R1 used for?

This SACE Emax moving part is designed for protection, switching and isolation of high-current low-voltage distribution circuits when installed with the appropriate E3 withdrawable fixed part.

What is the rated current of the ABB 1SDA056458R1?

The ABB 1SDA056458R1 E3H2000 circuit breaker moving part has a rated uninterrupted current of 2000 A.

What protection does the PR121/P-LSIG trip unit provide?

The PR121/P-LSIG R2000 electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection.

Is the ABB 1SDA056458R1 fixed or withdrawable?

The 1SDA056458R1 is a four-pole withdrawable moving part (W MP) designed for use with the appropriate E3 withdrawable fixed part.

What is the breaking capacity of the ABB E3H2000PR121/P-LSIG?

The E3H2000 configuration provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC.