ABB 1SDA056449R1 SACE Emax E3H2000 three-pole withdrawable air circuit breaker moving portion with a 2000 A rated current, 100 kA maximum breaking capacity and PR121/P-LSI electronic protection for demanding low-voltage power distribution systems.
£13,878.70
The ABB 1SDA056449R1 is a high-performance SACE Emax E3H2000 air circuit breaker moving portion designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax series, this three-pole withdrawable breaker combines a 2000 A rated current with the PR121/P-LSI electronic overcurrent release.
Designed for industrial power distribution, main switchboards and critical electrical installations, the E3H2000 provides dependable protection against overloads and short circuits. The PR121/P-LSI electronic trip unit provides long-time, short-time and instantaneous protection functions, supporting selective protection and reliable fault interruption across high-current distribution networks.
With a rated uninterrupted current of 2000 A, a three-pole configuration and rated operational voltage up to 690 V AC, the 1SDA056449R1 is suited to demanding power-distribution applications. The E3H performance level provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC, while its withdrawable moving-portion construction supports efficient servicing and maintenance within compatible SACE Emax switchgear.
Air circuit breakers such as the ABB SACE Emax E3H2000 provide switching, isolation and overcurrent protection for high-current low-voltage electrical networks. They are commonly installed as incoming, feeder or distribution protection devices in industrial switchboards where dependable interruption of substantial fault currents and coordinated circuit protection are essential.
The PR121/P-LSI electronic release provides long-time protection against sustained overloads, short-time protection that can support selective coordination during short-circuit conditions, and instantaneous protection against severe faults. Combined with the E3H breaker’s high breaking performance, 2000 A current rating and withdrawable construction, this makes the 1SDA056449R1 well suited to demanding industrial and infrastructure power-distribution installations.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| Order code | 1SDA056449R1 |
| Product type | Air circuit breaker moving portion |
| Frame | E3 |
| Performance level | H |
| Rated current (In) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 220–500 V AC; 85 kA at 660–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 85 kA at 220–690 V AC |
| Rated short-time withstand current (Icw) | 75 kA for 1 s; 65 kA for 3 s |
| Release | PR121/P-LSI |
| Release type | Electronic |
| Protection functions | LSI (long-time, short-time and instantaneous) |
| Overload release current setting | 800–2000 A |
| Short-time short-circuit release adjustment | 2000–20000 A |
| Instantaneous short-circuit release adjustment | 3000–30000 A |
| Integrated earth-fault protection | No |
| Installation type | Withdrawable moving portion |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Open / closed |
| Motor drive | Optional |
| Power loss | 225 W |
| Electrical durability | 9,000 cycles at up to 690 V AC |
| Mechanical durability | 20,000 cycles |
| Dimensions (H × W × D) | 461 × 432 × 396.5 mm |
| Net weight | 64 kg |
| Standards | IEC |
| EAN | 8015644577896 |
The ABB 1SDA056449R1 is a 2000 A SACE Emax air circuit breaker moving portion used for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.
The ABB 1SDA056449R1 has a rated uninterrupted current of 2000 A.
The 1SDA056449R1 is fitted with an ABB PR121/P-LSI electronic overcurrent release, providing long-time, short-time and instantaneous protection functions.
The E3H2000 has an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC.
The 1SDA056449R1 is a withdrawable SACE Emax circuit breaker moving portion designed for installation in compatible withdrawable switchgear assemblies.