ABB E3H1600PR122/P-LSI is a 1600 A four-pole SACE Emax withdrawable air circuit breaker moving part with a PR122/P-LSI R1600 electronic overcurrent release providing long-time, short-time and instantaneous protection for demanding low-voltage power distribution systems.
£14,052.95
The ABB E3H1600PR122/P-LSI is a high-performance four-pole withdrawable air circuit breaker moving part designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax E3H series, this configuration combines a 1600 A rated uninterrupted current with the PR122/P-LSI electronic overcurrent release.
The PR122/P-LSI R1600 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. These LSI functions support selective coordination within complex distribution networks while helping protect conductors, switchgear and connected equipment against sustained overloads and severe short-circuit conditions.
The ABB 1SDA056428R1 is specifically configured as the four-pole moving portion of a withdrawable E3H1600 circuit breaker. It is rated for operation up to 690 V AC, provides an ultimate short-circuit breaking capacity of 100 kA at 400 V AC, and is fitted with four auxiliary contacts plus circuit-breaker open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E3H protect electrical distribution systems against overload and short-circuit conditions while providing dependable switching and isolation. The E3H platform combines high fault-current interruption capability with electronic protection, making it particularly suitable for main distribution switchboards and other high-current installations.
The PR122/P-LSI electronic release provides long-time, short-time and instantaneous protection for effective coordination within the distribution system. The withdrawable design allows the moving portion to interface with the appropriate fixed part, supporting inspection, servicing and replacement within suitably configured draw-out switchgear assemblies.
| Series | SACE Emax E3H |
|---|---|
| ABB order code | 1SDA056428R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame | E3H1600 |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Trip unit | PR122/P-LSI R1600 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 220–690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Power loss | 150 W |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 10,000 cycles |
| Execution | Withdrawable |
| Component | Moving part (MP) |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Weight | 96 kg |
| EAN | 8015644577681 |
This SACE Emax moving part is designed for protection, switching and isolation of high-current low-voltage distribution circuits when installed with the appropriate E3 withdrawable fixed part.
The ABB 1SDA056428R1 E3H1600 circuit breaker moving part has a rated uninterrupted current of 1600 A.
The PR122/P-LSI R1600 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The 1SDA056428R1 is a four-pole withdrawable moving part (W MP) designed for use with the appropriate E3 withdrawable fixed part.
The E3H1600 configuration provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where dependable circuit protection, high fault-current interruption capability and maintainable withdrawable switchgear configurations are essential.