1SDA056428R1 ABB E3H1600PR122/P-LSI 1600 A 4-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA056428R1 ABB E3H1600PR122/P-LSI 1600 A 4-Pole Withdrawable Air Circuit Breaker Moving Part

ABB E3H1600PR122/P-LSI is a 1600 A four-pole SACE Emax withdrawable air circuit breaker moving part with a PR122/P-LSI R1600 electronic overcurrent release providing long-time, short-time and instantaneous protection for demanding low-voltage power distribution systems.

SKU: 1SDA056428R1MPN: 1SDA056428R1
Price
List Price £18,737.26 ex VAT
Your Price (ex VAT) Save 25%
£14,052.95 25% OFF
You save £4,684.32 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £14,052.95
Trade pricing is personalised to your account

Manufacturer Lead Time

£14,052.95

Why Choose the ABB E3H1600PR122/P-LSI Air Circuit Breaker?

The ABB E3H1600PR122/P-LSI is a high-performance four-pole withdrawable air circuit breaker moving part designed for protection, switching and isolation in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax E3H series, this configuration combines a 1600 A rated uninterrupted current with the PR122/P-LSI electronic overcurrent release.

The PR122/P-LSI R1600 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. These LSI functions support selective coordination within complex distribution networks while helping protect conductors, switchgear and connected equipment against sustained overloads and severe short-circuit conditions.

The ABB 1SDA056428R1 is specifically configured as the four-pole moving portion of a withdrawable E3H1600 circuit breaker. It is rated for operation up to 690 V AC, provides an ultimate short-circuit breaking capacity of 100 kA at 400 V AC, and is fitted with four auxiliary contacts plus circuit-breaker open/closed position indication.

Key Advantages

  • High-performance ABB SACE Emax E3H air circuit breaker moving part for low-voltage power distribution.
  • 1600 A rated uninterrupted current for high-current electrical systems.
  • Four-pole configuration for four-conductor switching and protection.
  • PR122/P-LSI electronic trip unit provides long-time, short-time and instantaneous protection.
  • 100 kA Icu at 400 V AC for demanding prospective fault-current conditions.
  • Withdrawable moving-part construction supports maintainable draw-out switchgear installations.
  • Four auxiliary contacts and open/closed position indication support switchboard monitoring and control.

Key Features

  • ABB SACE Emax E3H series.
  • 1600 A rated uninterrupted current.
  • Four-pole circuit breaker configuration.
  • PR122/P-LSI R1600 electronic overcurrent release.
  • LSI protection functions: long-time, short-time and instantaneous.
  • 690 V AC rated operational voltage.
  • 100 kA Icu at 220–500 V AC.
  • 85 kA Icu at 660–690 V AC.
  • Withdrawable moving part (W MP) configuration.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E3H protect electrical distribution systems against overload and short-circuit conditions while providing dependable switching and isolation. The E3H platform combines high fault-current interruption capability with electronic protection, making it particularly suitable for main distribution switchboards and other high-current installations.

The PR122/P-LSI electronic release provides long-time, short-time and instantaneous protection for effective coordination within the distribution system. The withdrawable design allows the moving portion to interface with the appropriate fixed part, supporting inspection, servicing and replacement within suitably configured draw-out switchgear assemblies.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Withdrawable industrial switchgear assemblies.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing plants and process facilities.
  • Power distribution centres and electrical substations.
  • Generator and transformer distribution systems.

Technical Specifications

Series SACE Emax E3H
ABB order code 1SDA056428R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Frame E3H1600
Rated uninterrupted current (Iu) 1600 A
Rated operational current (Ie) 1600 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Number of poles 4
Trip unit PR122/P-LSI R1600
Release type Electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 380–400 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 220–690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Power loss 150 W
Mechanical durability 20,000 cycles
Electrical durability 10,000 cycles
Execution Withdrawable
Component Moving part (MP)
Auxiliary contacts 4
Position indication Open / closed
Weight 96 kg
EAN 8015644577681

Frequently Asked Questions

What is the ABB E3H1600PR122/P-LSI 1SDA056428R1 used for?

This SACE Emax moving part is designed for protection, switching and isolation of high-current low-voltage distribution circuits when installed with the appropriate E3 withdrawable fixed part.

What is the rated current of the ABB 1SDA056428R1?

The ABB 1SDA056428R1 E3H1600 circuit breaker moving part has a rated uninterrupted current of 1600 A.

What protection does the PR122/P-LSI trip unit provide?

The PR122/P-LSI R1600 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

Is the ABB 1SDA056428R1 fixed or withdrawable?

The 1SDA056428R1 is a four-pole withdrawable moving part (W MP) designed for use with the appropriate E3 withdrawable fixed part.

What is the breaking capacity of the ABB E3H1600PR122/P-LSI?

The E3H1600 configuration provides an ultimate short-circuit breaking capacity of 100 kA at 220–500 V AC and 85 kA at 660–690 V AC.

Trusted by Electrical Professionals Worldwide

ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where dependable circuit protection, high fault-current interruption capability and maintainable withdrawable switchgear configurations are essential.