ABB E3H1600PR122/P-LI is a 1600 A four-pole fixed SACE Emax air circuit breaker with a PR122/P-LI R1600 electronic overcurrent release and rear horizontal flat terminals for high-performance low-voltage power distribution protection.
£12,226.48
The ABB E3H1600PR122/P-LI is a high-performance four-pole air circuit breaker (ACB) designed for reliable protection, switching and isolation in low-voltage electrical distribution systems. As part of the proven ABB SACE Emax E3H series, this fixed circuit breaker combines a 1600 A rated uninterrupted current with the PR122/P-LI electronic overcurrent release for dependable protection in demanding industrial and commercial installations.
The PR122/P-LI R1600 electronic trip unit provides long-time overload and instantaneous short-circuit protection. These LI protection functions help safeguard conductors, switchgear and connected equipment against sustained overcurrents and severe short circuits, while the E3H high-breaking-capacity design is engineered for power distribution systems with substantial prospective fault currents.
The ABB 1SDA056411R1 is supplied as a four-pole fixed E3H 1600 circuit breaker with rear horizontal flat terminals. With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 100 kA at 400 V AC and four auxiliary contacts with open/closed position indication, it is well suited to main switchboards and high-current industrial distribution systems.
Air circuit breakers such as the ABB SACE Emax E3H protect electrical distribution systems against overload and short-circuit conditions while providing dependable switching and isolation. Their high interrupting capability makes them particularly suitable for main distribution points, industrial switchboards and other installations where prospective fault currents can be substantial.
The PR122/P-LI electronic release combines long-time overload protection with rapid instantaneous protection against severe short circuits. Together with the E3H platform's high breaking capacity and short-time withstand capability, these functions provide dependable protection for important low-voltage distribution equipment and circuits.
| Series | SACE Emax E3H |
|---|---|
| ABB order code | 1SDA056411R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker (ACB) |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Trip unit | PR122/P-LI R1600 |
| Release type | Electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 380–400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 220–690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Short-circuit performance level | H |
| Power loss | 85 W |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 10,000 cycles |
| Mounting type | Fixed |
| Terminal arrangement | Rear flat horizontal terminals |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Dimensions (W × H × D) | 530 × 418 × 302 mm |
| Net weight | 76 kg |
| EAN | 8015644577513 |
This air circuit breaker is designed for protection, switching and isolation of high-current low-voltage power distribution circuits in industrial, commercial and infrastructure installations.
The ABB 1SDA056411R1 E3H1600 circuit breaker has a rated uninterrupted current of 1600 A.
The PR122/P-LI R1600 electronic trip unit provides long-time overload and instantaneous short-circuit protection.
This specific 1SDA056411R1 configuration is a fixed four-pole circuit breaker equipped with rear horizontal flat terminals.
The E3H configuration provides an ultimate short-circuit breaking capacity of 100 kA at 400–500 V AC and 85 kA at 660–690 V AC.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where dependable circuit protection, high fault-current interruption capability and flexible electronic protection are essential.