1SDA056410R1 ABB E3H1600 PR121/P-LSIG 1600 A 4-Pole Fixed Air Circuit Breaker

1SDA056410R1 ABB E3H1600 PR121/P-LSIG 1600 A 4-Pole Fixed Air Circuit Breaker

ABB 1SDA056410R1 E3H1600 is a 1600 A four-pole fixed SACE Emax air circuit breaker with a PR121/P-LSIG electronic overcurrent release, LSIG protection, rear horizontal terminals and 100 kA ultimate short-circuit breaking capacity at 400 V AC for demanding low-voltage power distribution.

SKU: 1SDA056410R1MPN: 1SDA056410R1
Price
List Price £18,122.10 ex VAT
Your Price (ex VAT) Save 25%
£13,591.58 25% OFF
You save £4,530.53 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £13,591.58
Trade pricing is personalised to your account

Manufacturer Lead Time

£13,591.58

Why Choose the ABB 1SDA056410R1 E3H1600 Air Circuit Breaker?

The ABB 1SDA056410R1 is a high-performance SACE Emax E3H air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB New Emax E3 series, this four-pole fixed circuit breaker combines a 1600 A rated current with the PR121/P-LSIG electronic overcurrent release for comprehensive protection of industrial, commercial and infrastructure power installations.

The E3H1600 is equipped with ABB's PR121/P-LSIG R1600 electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. This LSIG configuration provides comprehensive electronic protection against overloads, short circuits and earth faults, with adjustable protection ranges that support coordination with other protective devices in the distribution system.

With a 1600 A rated uninterrupted current, four-pole fixed construction and rear horizontal terminals, the 1SDA056410R1 is engineered for permanent integration into low-voltage switchboards. Its E3H high-performance configuration provides a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC, making it suitable for installations with substantial prospective fault currents.

Key Advantages

  • High-performance ABB SACE Emax E3H air circuit breaker for demanding low-voltage distribution.
  • 1600 A rated uninterrupted current for high-current industrial, commercial and infrastructure applications.
  • PR121/P-LSIG electronic overcurrent release provides comprehensive electronic circuit protection.
  • LSIG functionality provides long-time, short-time, instantaneous and ground-fault protection.
  • Four-pole construction supports three-phase systems requiring neutral switching.
  • Ultimate short-circuit breaking capacity of 100 kA at 400 V AC for high-fault-level installations.
  • Fixed mounting with rear horizontal terminals supports permanent switchboard integration.
  • Four auxiliary changeover contacts and open/closed position indication support monitoring and control.

Key Features

  • ABB SACE Emax E3H1600 series air circuit breaker.
  • 1600 A rated uninterrupted current.
  • Four-pole configuration.
  • Fixed circuit-breaker version.
  • Rear horizontal terminals.
  • PR121/P-LSIG R1600 electronic overcurrent release.
  • LSIG protection covering long-time, short-time, instantaneous and ground-fault functions.
  • Rated operational voltage of 690 V AC.
  • Ultimate short-circuit breaking capacity of 100 kA at 400 V AC.
  • Adjustable overload protection from 640–1600 A.
  • Adjustable short-time protection from 1600–16000 A.
  • Adjustable instantaneous protection from 2400–24000 A.

Advanced Protection for High-Current Power Distribution

Air circuit breakers such as the ABB E3H1600 provide switching, isolation and protection for high-current low-voltage distribution systems. The electronic trip unit monitors current conditions and enables the breaker to interrupt overload, short-circuit and ground-fault conditions, helping protect busbars, cables, transformers and connected electrical equipment from potentially damaging fault currents.

The integrated PR121/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. Combined with the E3H breaker's 1600 A current rating, four-pole construction, 100 kA ultimate breaking capacity at 400 V AC and fixed configuration, the 1SDA056410R1 is particularly suited to main distribution circuits requiring comprehensive electronic protection and high fault-clearing performance.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and large-building electrical distribution.
  • Main incomer and high-current feeder protection.
  • Three-phase four-wire electrical distribution systems.
  • Generator and transformer distribution circuits.
  • Installations requiring integrated ground-fault protection.
  • Power control centres and fixed switchgear assemblies.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax / New Emax E3
ABB order code 1SDA056410R1
Product type Air circuit breaker
Frame / performance type E3H
Short-circuit performance level H
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Number of poles 4
Mounting version Fixed
Terminal arrangement Rear horizontal terminals
Trip unit PR121/P-LSIG R1600 electronic overcurrent release
Release type Electronic
Protection functions LSIG – long-time, short-time, instantaneous and ground fault
Overload release setting range 640–1600 A
Short-time delayed short-circuit setting range 1600–16000 A
Instantaneous short-circuit setting range 2400–24000 A
Integrated earth-fault protection Yes
Rated operational voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Current type AC
Electrical durability 10,000 cycles at ≤440 V AC; 10,000 cycles at 500–690 V AC
Electrical operating frequency 20 cycles per hour
Mechanical durability 20,000 cycles
Auxiliary contacts 4 changeover contacts
Position indication Circuit breaker open / closed
Integrated motor drive No
Optional motor drive Yes
Dimensions (H × W × D) 418 × 530 × 302 mm
Net weight 76 kg
EAN 8015644577506
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA056410R1 used for?

The ABB 1SDA056410R1 is a fixed air circuit breaker used for switching and protecting high-current low-voltage electrical distribution circuits against overload, short-circuit and ground-fault conditions.

What is the rated current of the ABB E3H1600 1SDA056410R1?

The circuit breaker has a rated uninterrupted current of 1600 A, making it suitable for demanding industrial, commercial and infrastructure power distribution applications.

What protection unit is fitted to this circuit breaker?

The 1SDA056410R1 is fitted with an ABB PR121/P-LSIG R1600 electronic overcurrent release, providing long-time, short-time, instantaneous and ground-fault protection functions.

What does LSIG protection mean?

LSIG denotes long-time overload protection, short-time short-circuit protection, instantaneous short-circuit protection and ground-fault protection, providing comprehensive electronic protection for low-voltage distribution circuits.

What is the short-circuit breaking capacity of the ABB E3H1600?

The E3H1600 1SDA056410R1 has a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC, making it suitable for demanding distribution systems with high prospective fault currents.

Is the ABB 1SDA056410R1 fixed or withdrawable?

The 1SDA056410R1 is a four-pole fixed air circuit breaker with rear horizontal terminals for permanent integration into compatible low-voltage switchboards.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers provide robust high-current switching and advanced electronic protection for demanding low-voltage distribution systems, combining high short-circuit performance with comprehensive protection and dependable switchgear integration.