1SDA056396R1 ABB E3H1250PR122/P-LSI 1250 A 4-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA056396R1 ABB E3H1250PR122/P-LSI 1250 A 4-Pole Withdrawable Air Circuit Breaker Moving Part

ABB E3H1250PR122/P-LSI is a 1250 A four-pole SACE Emax withdrawable air circuit breaker moving part with a PR122/P-LSI R1250 electronic overcurrent release, four auxiliary change-over contacts and open/closed position indication.

SKU: 1SDA056396R1MPN: 1SDA056396R1
Price
List Price £15,820.33 ex VAT
Your Price (ex VAT) Save 25%
£11,865.25 25% OFF
You save £3,955.08 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,865.25
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,865.25

Why Choose the ABB E3H1250PR122/P-LSI Air Circuit Breaker?

The ABB E3H1250PR122/P-LSI is a high-performance four-pole withdrawable air circuit breaker moving part designed for reliable protection, switching and isolation in low-voltage electrical distribution systems. As part of the proven ABB SACE Emax E3H series, this moving portion combines a 1250 A rated current with the PR122/P-LSI electronic overcurrent release for dependable protection in demanding industrial and commercial installations.

The PR122/P-LSI R1250 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. These LSI protection functions support selective coordination within complex distribution networks while helping protect conductors, switchgear and connected equipment against sustained overloads and severe short-circuit conditions.

The ABB 1SDA056396R1 is specifically configured as a four-pole withdrawable moving part (W MP) for use with a compatible E3 withdrawable fixed part. With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 100 kA at 400 V AC, four auxiliary change-over contacts and open/closed position indication, it is well suited to high-current switchboards requiring maintainable draw-out construction.

Key Advantages

  • High-performance ABB SACE Emax E3H air circuit breaker moving part for low-voltage power distribution.
  • 1250 A rated uninterrupted current for high-current electrical systems.
  • Four-pole configuration for four-conductor switching and protection.
  • PR122/P-LSI electronic trip unit provides long-time, short-time and instantaneous protection.
  • 100 kA ultimate breaking capacity at 400 V AC for demanding fault-current conditions.
  • Withdrawable moving-part construction supports maintainable draw-out switchgear installations.
  • Four auxiliary change-over contacts and open/closed position indication support switchboard monitoring and control.

Key Features

  • ABB SACE Emax E3H series.
  • 1250 A rated uninterrupted current.
  • Four-pole circuit breaker configuration.
  • PR122/P-LSI R1250 electronic overcurrent release.
  • LSI protection functions: long-time, short-time and instantaneous.
  • 690 V AC rated operational voltage.
  • 100 kA Icu at 400–500 V AC.
  • 85 kA Icu at 660–690 V AC.
  • Withdrawable moving part (W MP) configuration.
  • Four auxiliary change-over contacts with open/closed circuit-breaker position indication.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E3H protect electrical distribution systems against overload and short-circuit conditions while providing dependable switching and isolation. The E3H platform combines high fault-current interruption capability with electronic protection, making it particularly suitable for main distribution switchboards and other high-current installations.

The PR122/P-LSI electronic release provides long-time, short-time and instantaneous protection for effective coordination within the distribution system. The withdrawable design also allows the breaker moving portion to be disconnected from its compatible fixed part, supporting inspection, servicing and replacement in appropriately designed draw-out switchgear assemblies.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Withdrawable industrial switchgear assemblies.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing plants and process facilities.
  • Power distribution centres and electrical substations.
  • Generator and transformer distribution systems.

Technical Specifications

Series SACE Emax E3H
ABB order code 1SDA056396R1
Product group 310513-New Emax
Product type Air circuit breaker withdrawable moving part
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Number of poles 4
Trip unit PR122/P-LSI R1250
Release type Electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Overload release adjustment range 500–1250 A
Instantaneous short-circuit release adjustment range 1875–18750 A
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 400–690 V AC 85 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Short-circuit performance level H
Power loss 90 W
Mechanical durability 20,000 cycles
Electrical durability 12,000 cycles
Execution Withdrawable
Component Moving part (MP)
Auxiliary contacts 4 change-over contacts
Position indication Open / closed
Integrated earth-fault protection No
Motor drive Optional
Weight 96 kg
EAN 8015644577360

Frequently Asked Questions

What is the ABB E3H1250PR122/P-LSI 1SDA056396R1 used for?

This SACE Emax moving part is designed for protection, switching and isolation of high-current low-voltage distribution circuits when installed with a compatible E3 withdrawable fixed part.

What is the rated current of the ABB 1SDA056396R1?

The ABB 1SDA056396R1 E3H1250 circuit breaker moving part has a rated uninterrupted current of 1250 A.

What protection does the PR122/P-LSI trip unit provide?

The PR122/P-LSI R1250 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

Is the ABB 1SDA056396R1 fixed or withdrawable?

The 1SDA056396R1 is a four-pole withdrawable moving part (W MP) intended for installation with a compatible E3 withdrawable fixed part.

What is the breaking capacity of the ABB E3H1250PR122/P-LSI?

The E3H configuration provides an ultimate short-circuit breaking capacity of 100 kA at 400–500 V AC and 85 kA at 660–690 V AC.

Trusted by Electrical Professionals Worldwide

ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where dependable circuit protection, high fault-current interruption capability and maintainable withdrawable switchgear configurations are essential.