ABB E3H1250PR122/P-LSI is a 1250 A four-pole fixed SACE Emax air circuit breaker with a PR122/P-LSI R1250 electronic overcurrent release and rear horizontal flat terminals for high-performance low-voltage power distribution protection.
£11,997.76
The ABB E3H1250PR122/P-LSI is a high-performance four-pole air circuit breaker (ACB) designed for reliable protection, switching and isolation in low-voltage electrical distribution systems. As part of the proven ABB SACE Emax E3H series, this fixed circuit breaker combines a 1250 A rated uninterrupted current with the PR122/P-LSI electronic overcurrent release for dependable protection in demanding industrial and commercial installations.
The PR122/P-LSI R1250 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. These LSI protection functions support effective selectivity and coordination within complex distribution networks while helping protect conductors, switchgear and connected equipment against sustained overloads and severe fault conditions.
The ABB 1SDA056380R1 is supplied as a four-pole fixed E3H 1250 circuit breaker with rear horizontal flat terminals. With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 100 kA at 400 V AC and four auxiliary contacts with open/closed position indication, it is well suited to main switchboards and high-current industrial power distribution systems.
Air circuit breakers such as the ABB SACE Emax E3H protect electrical distribution systems against overload and short-circuit conditions while providing dependable switching and isolation. Their high interrupting capability makes them particularly suitable for main distribution points, industrial switchboards and other installations where prospective fault currents can be substantial.
The PR122/P-LSI electronic release provides long-time, short-time and instantaneous protection functions for effective coordination within the distribution system. Long-time protection responds to sustained overloads, short-time protection supports selective fault clearing, and instantaneous protection provides rapid interruption of severe short circuits.
| Series | SACE Emax E3H |
|---|---|
| ABB order code | 1SDA056380R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker (ACB) |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Trip unit | PR122/P-LSI R1250 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 660–690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400–690 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Short-circuit performance level | H |
| Power loss | 60 W |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 12,000 cycles |
| Mounting type | Fixed |
| Terminal arrangement | Rear flat horizontal terminals |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Standard | IEC |
| Dimensions (W × H × D) | 530 × 418 × 302 mm |
| Net weight | 76 kg |
| EAN | 8015644577209 |
This air circuit breaker is designed for protection, switching and isolation of low-voltage power distribution circuits in industrial, commercial and infrastructure installations.
The ABB 1SDA056380R1 E3H1250 circuit breaker has a rated uninterrupted current of 1250 A.
The PR122/P-LSI R1250 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
This specific 1SDA056380R1 configuration is a fixed four-pole circuit breaker equipped with rear horizontal flat terminals.
The E3H configuration provides an ultimate short-circuit breaking capacity of 100 kA at 400–500 V AC and 85 kA at 660–690 V AC.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial power distribution systems where dependable circuit protection, high fault-current interruption capability and flexible electronic protection are essential.
We use cookies