1SDA056331R1 ABB E3S3200 PR122/P-LI 3200A 4P Withdrawable Air Circuit Breaker

1SDA056331R1 ABB E3S3200 PR122/P-LI 3200A 4P Withdrawable Air Circuit Breaker

ABB 1SDA056331R1 is a SACE Emax E3S 3200 A four-pole withdrawable air circuit breaker moving part with a PR122/P-LI R3200 electronic overcurrent release for high-current low-voltage power distribution protection.

SKU: 1SDA056331R1MPN: 1SDA056331R1
Price
List Price £36,838.99 ex VAT
Your Price (ex VAT) Save 25%
£27,629.24 25% OFF
You save £9,209.75 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £27,629.24
Trade pricing is personalised to your account

Manufacturer Lead Time

£27,629.24

Why Choose the ABB E3S3200 PR122/P-LI 3200A 4P Withdrawable Air Circuit Breaker?

The ABB E3S3200 PR122/P-LI, order code 1SDA056331R1, is a high-performance SACE Emax air circuit breaker moving part designed for protection and switching in demanding low-voltage electrical distribution systems. This E3S breaker is rated at 3200 A, has a four-pole configuration and incorporates ABB's electronic PR122/P-LI overcurrent release.

Designed for a withdrawable installation, the E3S3200 moving part enables convenient isolation and servicing within compatible SACE Emax switchgear. Its S performance level provides a rated ultimate short-circuit breaking capacity of 75 kA at 400 V AC, supporting high-capacity industrial and infrastructure distribution systems.

The PR122/P-LI electronic release provides long-time overload and instantaneous short-circuit protection, with an overload adjustment range of 1280–3200 A. Its four-pole construction, 690 V AC rated voltage and withdrawable format make the 1SDA056331R1 suitable for main incomers, feeders and other critical high-current distribution circuits.

Key Advantages

  • High-current 3200 A SACE Emax air circuit breaker moving part.
  • Four-pole configuration for suitable three-phase systems incorporating a neutral conductor.
  • PR122/P-LI electronic overcurrent release provides long-time and instantaneous protection.
  • Withdrawable construction supports convenient isolation, inspection and switchboard maintenance.
  • 75 kA short-circuit breaking capacity at 400 V AC for demanding distribution systems.
  • Supplied with four auxiliary contacts for circuit-breaker open/closed status indication.

Key Features

  • ABB SACE Emax E3S air circuit breaker moving part.
  • 3200 A rated uninterrupted current.
  • Four-pole configuration.
  • PR122/P-LI R3200 electronic overcurrent release.
  • LI protection functions for long-time overload and instantaneous short-circuit protection.
  • Overload release adjustment range of 1280–3200 A.
  • Instantaneous short-circuit release adjustment range of 4800–48000 A.
  • S performance level with 75 kA breaking capacity at 400 V AC.
  • Withdrawable moving-part construction for compatible Emax switchgear.
  • Rated voltage of 690 V AC.
  • Four auxiliary contacts configured as two normally open and two normally closed contacts.
  • Integrated circuit-breaker open/closed position indication.

Reliable High-Current Protection for Low-Voltage Distribution

Air circuit breakers such as the ABB SACE Emax E3S3200 protect high-current electrical distribution circuits against damaging overload and short-circuit conditions. The PR122/P-LI electronic release combines adjustable long-time overload protection with instantaneous short-circuit protection, helping safeguard cables, busbars and connected distribution equipment.

The withdrawable moving-part design is particularly suited to industrial switchboards where serviceability and operational flexibility are important. The breaker can be disconnected from its compatible fixed part for isolation and maintenance, while its 3200 A rating and four-pole architecture support demanding three-phase power distribution systems.

Typical Applications

  • Main incoming protection for industrial low-voltage switchboards.
  • High-current feeder and distribution circuit protection.
  • Manufacturing plants and process facilities.
  • Commercial and infrastructure power distribution systems.
  • Large motor control centres and electrical distribution assemblies.
  • Withdrawable switchgear requiring high-current circuit protection and serviceability.

Technical Specifications

Series SACE Emax
ABB order code 1SDA056331R1
Product group New Emax
Product type Air circuit breaker moving part
Frame E3
Performance level S
Rated current (In) 3200 A
Rated uninterrupted current (Iu) 3200 A
Number of poles 4
Release PR122/P-LI
Release type Electronic overcurrent release
Release rating R3200
Protection functions LI (long-time and instantaneous)
Overload release adjustment range 1280–3200 A
Instantaneous short-circuit release adjustment range 4800–48000 A
Rated voltage 690 V AC
Rated ultimate short-circuit breaking capacity at 400 V AC 75 kA
Installation Withdrawable moving part
Main circuit connection Connection through separate fixed part
Auxiliary contacts 4 total — 2 NO + 2 NC
Position indication Circuit breaker open / closed
Integrated earth-fault protection No
Motor operator Optional
Protection rating IP2X
EAN 8015644576714

Frequently Asked Questions

What is the ABB 1SDA056331R1?

The ABB 1SDA056331R1 is a SACE Emax E3S air circuit breaker moving part rated at 3200 A, with four poles and a PR122/P-LI R3200 electronic overcurrent release.

What is the rated current of the ABB E3S3200 PR122/P-LI?

The circuit breaker has a rated uninterrupted current of 3200 A, with an overload release adjustment range of 1280–3200 A.

What protection does the PR122/P-LI release provide?

The PR122/P-LI electronic release provides LI protection functions, comprising long-time overload protection and instantaneous short-circuit protection.

Is the ABB 1SDA056331R1 fixed or withdrawable?

The ABB 1SDA056331R1 is a withdrawable circuit-breaker moving part designed to connect through the appropriate separate fixed part in compatible SACE Emax switchgear.

How many poles does the ABB E3S3200 1SDA056331R1 have?

The breaker has a four-pole configuration, making it suitable for applications requiring switching and protection of three phases together with a neutral conductor.

What is the breaking capacity of the ABB E3S3200 1SDA056331R1?

The E3S3200 has a rated ultimate short-circuit breaking capacity of 75 kA at 400 V AC, supporting demanding high-current low-voltage distribution applications.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax air circuit breakers are designed for demanding low-voltage power distribution applications, combining high-current switching capability, electronic protection and service-friendly withdrawable construction for industrial and infrastructure systems.