ABB 1SDA056328R1 E3S3200 is a 3200 A four-pole withdrawable SACE Emax air circuit breaker moving part with a PR121/P-LI electronic overcurrent release and 75 kA short-circuit breaking capacity for high-current low-voltage power distribution.
£27,551.03
The ABB 1SDA056328R1 is a high-performance SACE Emax E3S air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB New Emax E3 series, this four-pole withdrawable circuit breaker combines a 3200 A rated current with the PR121/P-LI electronic overcurrent release for dependable protection of high-current industrial, commercial and infrastructure installations.
The E3S3200 is equipped with ABB's PR121/P-LI R3200 electronic trip unit, providing long-time overload and instantaneous short-circuit protection. This LI protection configuration provides essential electronic overcurrent protection, while the four-pole construction enables switching across three phase conductors and the neutral conductor in compatible low-voltage distribution systems.
With a rated uninterrupted current of 3200 A, a four-pole withdrawable moving-part configuration and a rated ultimate short-circuit breaking capacity of 75 kA at 400 V AC, the 1SDA056328R1 is engineered for high-current switchboards where protection performance, maintainability and operational flexibility are important. Its withdrawable design allows the moving part to be removed from the corresponding fixed cradle for inspection, servicing or replacement.
Air circuit breakers such as the ABB E3S3200 provide switching and protection for high-current low-voltage distribution systems. The electronic trip unit monitors current conditions and enables the breaker to interrupt overload and short-circuit faults, helping protect busbars, cables, transformers and connected electrical equipment from potentially damaging overcurrents.
The integrated PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. Combined with the breaker's 3200 A current rating, four-pole construction, 75 kA short-circuit performance and withdrawable design, the 1SDA056328R1 is particularly suited to main distribution circuits where dependable protection and maintainable switchgear are required.
| Product group | 310513-New Emax |
|---|---|
| Series | SACE Emax / New Emax E3 |
| ABB order code | 1SDA056328R1 |
| Product type | Air circuit breaker moving part |
| Frame / performance type | E3S |
| Rated current (In) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Number of poles | 4 |
| Version | Withdrawable (W) |
| Configuration | Moving part (MP) |
| Trip unit | PR121/P-LI R3200 electronic overcurrent release |
| Protection functions | LI – long-time and instantaneous |
| Overload release setting range | 1280–3200 A |
| Instantaneous short-circuit release setting range | 4800–48000 A |
| Rated voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 75 kA |
| Integrated earth-fault protection | No |
| Current type | AC |
| Electrical durability | 6000 cycles at ≤440 V AC; 5000 cycles at 500–690 V AC |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Motor drive | Optional |
| DIN rail mounting | No |
| Dimensions (H × W × D) | 461 × 558 × 396.5 mm |
| Net weight | 81 kg |
| EAN | 8015644576684 |
| Customs tariff number | 85362090 |
The ABB 1SDA056328R1 is a withdrawable air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits against overload and short-circuit conditions.
The circuit breaker has a rated uninterrupted current of 3200 A, making it suitable for high-current power distribution applications.
The 1SDA056328R1 is fitted with an ABB PR121/P-LI R3200 electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection.
LI denotes long-time overload protection and instantaneous short-circuit protection, providing electronic overcurrent protection for low-voltage distribution circuits.
The E3S3200 1SDA056328R1 has a rated ultimate short-circuit breaking capacity of 75 kA at 400 V AC, making it suitable for demanding systems with high prospective fault currents.
The 1SDA056328R1 is a four-pole withdrawable circuit-breaker moving part designed for use with the corresponding ABB SACE Emax fixed part within compatible low-voltage switchgear.
ABB SACE Emax air circuit breakers provide robust high-current switching and electronic circuit protection for demanding low-voltage distribution systems, combining dependable fault protection with flexible and maintainable withdrawable switchgear configurations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.