Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056327R1 E3S3200 is a 3200 A three-pole withdrawable SACE Emax air circuit breaker moving part with a PR123/P-LSIG electronic overcurrent release and 75 kA short-circuit breaking capacity for high-current low-voltage power distribution.
£28,067.39
The ABB 1SDA056327R1 is a high-performance SACE Emax E3S air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB New Emax E3 series, this three-pole withdrawable circuit breaker combines a 3200 A rated current with the advanced PR123/P-LSIG electronic overcurrent release for comprehensive protection of high-current industrial, commercial and infrastructure installations.
The E3S3200 is equipped with ABB's PR123/P-LSIG electronic trip unit, providing long-time, short-time, instantaneous and ground-fault protection. This LSIG configuration provides comprehensive protection against overloads, short circuits and earth faults, making the breaker particularly suitable for critical distribution systems requiring advanced electronic protection and selective coordination.
With a rated uninterrupted current of 3200 A, a three-pole withdrawable moving-part configuration and a rated ultimate short-circuit breaking capacity of 75 kA across its specified low-voltage operating range, the 1SDA056327R1 is engineered for high-current switchboards where protection performance, maintainability and operational flexibility are essential.
Air circuit breakers such as the ABB E3S3200 provide switching and protection for high-current low-voltage distribution systems. By detecting overload, short-circuit and ground-fault conditions, the electronic protection system enables the breaker to interrupt potentially damaging fault currents and help protect busbars, cables, transformers and connected electrical equipment.
The integrated PR123/P-LSIG electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection for comprehensive fault management. Combined with the E3S breaker's 3200 A current rating, 75 kA short-circuit performance and withdrawable construction, the 1SDA056327R1 is particularly suitable for main incomers, high-current feeders and critical distribution circuits requiring advanced protection and maintainable switchgear.
| Product group | 310513-New Emax |
|---|---|
| Series | SACE Emax / New Emax E3 |
| ABB order code | 1SDA056327R1 |
| Product type | Air circuit breaker moving part |
| Frame / performance type | E3S |
| Short-circuit performance level | S |
| Rated current (In) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Number of poles | 3 |
| Version | Withdrawable (W) |
| Configuration | Moving part (MP) |
| Trip unit | PR123/P-LSIG R3200 electronic overcurrent release |
| Release type | Electronic (EL) |
| Protection functions | LSIG – long-time, short-time, instantaneous and ground fault |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) | 75 kA |
| Rated service short-circuit breaking capacity (Ics) | 75 kA |
| Rated short-time withstand current (Icw) | 75 kA for 1 s; 65 kA for 3 s |
| Current type | AC |
| Power loss | 570 W |
| Electrical durability | 6000 cycles at ≤440 V AC; 5000 cycles at 500–690 V AC |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Standards | IEC |
| Dimensions (H × W × D) | 461 × 432 × 396.5 mm |
| Net weight | 64 kg |
| EAN | 8015644576677 |
| Customs tariff number | 85362090 |
The ABB 1SDA056327R1 is a withdrawable air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits against overload, short-circuit and ground-fault conditions.
The circuit breaker has a rated current of 3200 A, making it suitable for high-current power distribution applications.
The 1SDA056327R1 is fitted with an ABB PR123/P-LSIG R3200 electronic overcurrent release, providing long-time, short-time, instantaneous and ground-fault protection functions.
LSIG denotes long-time overload protection, short-time short-circuit protection, instantaneous short-circuit protection and ground-fault protection, providing comprehensive protection for low-voltage distribution circuits.
The E3S performance level provides rated ultimate and service short-circuit breaking capacities of 75 kA across the specified 220–690 V AC range.
The 1SDA056327R1 is a three-pole withdrawable circuit-breaker moving part designed for use with a compatible ABB SACE Emax fixed part within low-voltage switchgear.
ABB SACE Emax air circuit breakers provide robust high-current switching and advanced electronic protection for demanding low-voltage distribution systems, combining high short-circuit performance with sophisticated protection and maintainable withdrawable switchgear configurations.