Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056325R1 is a SACE Emax E3S3200 three-pole withdrawable air circuit breaker moving part rated at 3200 A with a PR122/P-LSIG electronic overcurrent release for comprehensive high-current low-voltage circuit protection.
£22,578.51
The ABB E3S3200 PR122/P-LSIG, order code 1SDA056325R1, is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for switching and protection in high-current low-voltage electrical distribution systems. As part of the ABB SACE Emax E3 series, this three-pole withdrawable breaker combines a 3200 A rated uninterrupted current with the advanced PR122/P-LSIG electronic overcurrent release.
The PR122/P-LSIG trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. This comprehensive LSIG configuration supports selective coordination while protecting electrical distribution equipment against sustained overloads, short circuits and earth faults in demanding industrial, commercial and infrastructure installations.
With a 3200 A rated current, three-pole configuration and withdrawable moving-part construction, the E3S3200 is suited to main switchboards and high-current distribution systems where maintainability and comprehensive protection are important. The E3S performance level provides a rated ultimate short-circuit breaking capacity of 75 kA at 400 V AC, while the breaker is supplied with four auxiliary change-over contacts and open/closed position indication.
Air circuit breakers such as the ABB SACE Emax E3S3200 provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The electronic trip unit monitors electrical conditions and initiates circuit-breaker operation when configured protection thresholds are exceeded, helping protect cables, switchgear and connected equipment against damaging overloads, short circuits and earth faults.
The PR122/P-LSIG release provides four complementary protection functions for effective coordination within electrical distribution systems. Long-time protection responds to sustained overloads, short-time protection supports selective fault clearing, instantaneous protection rapidly interrupts severe short circuits, and ground-fault protection provides an additional protective function against earth-fault conditions. The withdrawable construction also enables the breaker moving part to be removed from its associated fixed part for inspection, servicing or replacement.
| Series | SACE Emax E3 |
|---|---|
| ABB order code | 1SDA056325R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E3S |
| Rated current | 3200 A |
| Rated uninterrupted current | 3200 A |
| Number of poles | 3 |
| Execution | Withdrawable |
| Component | Moving part (MP) |
| Trip unit | PR122/P-LSIG |
| Release rating | R3200 |
| Release type | Electronic overcurrent release |
| Protection functions | LSIG |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Ground-fault protection | G |
| Rated voltage | 690 V |
| Rated ultimate short-circuit breaking capacity at 400 V AC | 75 kA |
| Overload release adjustment range | 1280–3200 A |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Motor drive | Optional |
| Integrated earth-fault protection | Yes |
| Net weight | 77 kg |
| EAN | 8015644576653 |
| Customs tariff number | 85362090 |
The ABB 1SDA056325R1 is a SACE Emax E3S3200 air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits.
The E3S3200 has a rated uninterrupted current of 3200 A, making it suitable for demanding high-current low-voltage power distribution applications.
The PR122/P-LSIG electronic overcurrent release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection.
The E3S performance level provides a rated ultimate short-circuit breaking capacity of 75 kA at 400 V AC, providing robust fault interruption for demanding low-voltage power distribution systems.
The 1SDA056325R1 is a withdrawable three-pole circuit breaker moving part, allowing it to be withdrawn from its associated fixed part for inspection, servicing or replacement.
ABB SACE Emax air circuit breakers are designed for dependable protection and control of low-voltage electrical distribution systems, combining high-current switching capability with advanced electronic protection for demanding industrial, commercial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.