1SDA056324R1 ABB E3S3200 PR122/P-LSI 3200A 3-Pole Withdrawable Air Circuit Breaker

1SDA056324R1 ABB E3S3200 PR122/P-LSI 3200A 3-Pole Withdrawable Air Circuit Breaker

ABB 1SDA056324R1 is a SACE Emax E3S3200 three-pole withdrawable air circuit breaker moving part rated at 3200 A with a PR122/P-LSI electronic overcurrent release for high-current low-voltage circuit protection.

SKU: 1SDA056324R1MPN: 1SDA056324R1
Price
List Price £28,847.07 ex VAT
Your Price (ex VAT) Save 25%
£21,635.30 25% OFF
You save £7,211.77 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £21,635.30
Trade pricing is personalised to your account

Manufacturer Lead Time

£21,635.30

Why Choose the ABB E3S3200 PR122/P-LSI 3200A 3-Pole Withdrawable Air Circuit Breaker?

The ABB E3S3200 PR122/P-LSI, order code 1SDA056324R1, is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for switching and protection in high-current low-voltage electrical distribution systems. As part of the ABB SACE Emax E3 series, this three-pole withdrawable breaker combines a 3200 A rated uninterrupted current with the PR122/P-LSI electronic overcurrent release.

The PR122/P-LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. This LSI configuration supports selective coordination and dependable protection against sustained overloads and short-circuit faults, making the breaker suitable for demanding industrial, commercial and infrastructure power distribution applications.

With a 3200 A rated current, three-pole configuration and withdrawable moving-part construction, the E3S3200 is suited to main switchboards and high-current distribution systems where maintainability is important. The E3S performance level provides rated ultimate and service short-circuit breaking capacities of 75 kA at 415 V AC, together with short-time withstand ratings of 75 kA for 1 s and 65 kA for 3 s.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker moving part for low-voltage power distribution.
  • 3200 A rated uninterrupted current for demanding high-current installations.
  • Three-pole configuration for three-phase electrical distribution systems.
  • Advanced PR122/P-LSI electronic overcurrent release.
  • Long-time, short-time and instantaneous overcurrent protection.
  • 75 kA ultimate and service short-circuit breaking capacity at 415 V AC.
  • High short-time withstand capability supports selective protection and system coordination.
  • Withdrawable construction facilitates inspection, servicing and replacement.

Key Features

  • ABB SACE Emax E3S3200 air circuit breaker moving part.
  • 3200 A rated uninterrupted current.
  • Three-pole (3P) configuration.
  • PR122/P-LSI electronic overcurrent release rated R3200.
  • Long-time overload protection (L).
  • Short-time short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Withdrawable (W) execution.
  • Moving part (MP) for the withdrawable SACE Emax system.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 75 kA rated ultimate and service short-circuit breaking capacity at 415 V AC.
  • 75 kA short-time withstand current for 1 s and 65 kA for 3 s.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Reliable Circuit Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E3S3200 provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The electronic trip unit monitors electrical current and initiates circuit-breaker operation when configured protection thresholds are exceeded, helping protect cables, switchgear and connected electrical equipment against damaging overloads and short circuits.

The PR122/P-LSI release provides three levels of overcurrent protection for effective coordination within electrical distribution systems. Long-time protection responds to sustained overloads, short-time protection enables a controlled response to short-circuit conditions for improved selectivity, and instantaneous protection provides rapid interruption of severe short-circuit currents. The withdrawable construction also enables the breaker moving part to be removed from its associated fixed part for maintenance or replacement.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing and process facilities.
  • High-current incomer and feeder protection.
  • Transformer and generator distribution systems.

Technical Specifications

Series SACE Emax E3
ABB order code 1SDA056324R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Frame / performance level E3S
Rated current 3200 A
Rated uninterrupted current 3200 A
Rated operational current 3200 A
Number of poles 3
Execution Withdrawable
Component Moving part (MP)
Trip unit PR122/P-LSI
Release rating R3200
Release type Electronic overcurrent release
Protection functions LSI
Long-time protection L
Short-time protection S
Instantaneous protection I
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated ultimate short-circuit breaking capacity at 415 V AC 75 kA
Rated service short-circuit breaking capacity at 415 V AC 75 kA
Rated short-time withstand current (1 s) 75 kA
Rated short-time withstand current (3 s) 65 kA
Power loss 570 W
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Electrical durability at ≤440 V 6000 cycles
Electrical durability at 500–690 V 5000 cycles
Electrical operating frequency 20 cycles per hour
Mechanical durability 20,000 cycles
Mechanical operating frequency 60 cycles per hour
Dimensions (W × H × D) 432 × 461 × 396.5 mm
Net weight 64 kg
EAN 8015644576646
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA056324R1 used for?

The ABB 1SDA056324R1 is a SACE Emax E3S3200 air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits.

What is the rated current of the ABB E3S3200 PR122/P-LSI?

The E3S3200 has a rated uninterrupted current of 3200 A, making it suitable for demanding high-current low-voltage power distribution applications.

What protection functions does the PR122/P-LSI trip unit provide?

The PR122/P-LSI electronic overcurrent release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.

What is the breaking capacity of the ABB E3S3200?

The E3S performance level provides rated ultimate and service short-circuit breaking capacities of 75 kA at 415 V AC, together with short-time withstand ratings of 75 kA for 1 s and 65 kA for 3 s.

Is the ABB 1SDA056324R1 fixed or withdrawable?

The 1SDA056324R1 is a withdrawable three-pole circuit breaker moving part, allowing it to be withdrawn from its associated fixed part for inspection, servicing or replacement.

Trusted for Critical Power Distribution

ABB SACE Emax air circuit breakers are designed for dependable protection and control of low-voltage electrical distribution systems, combining high-current switching capability with advanced electronic overcurrent protection for demanding industrial, commercial and infrastructure applications.