Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056324R1 is a SACE Emax E3S3200 three-pole withdrawable air circuit breaker moving part rated at 3200 A with a PR122/P-LSI electronic overcurrent release for high-current low-voltage circuit protection.
£21,635.30
The ABB E3S3200 PR122/P-LSI, order code 1SDA056324R1, is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for switching and protection in high-current low-voltage electrical distribution systems. As part of the ABB SACE Emax E3 series, this three-pole withdrawable breaker combines a 3200 A rated uninterrupted current with the PR122/P-LSI electronic overcurrent release.
The PR122/P-LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. This LSI configuration supports selective coordination and dependable protection against sustained overloads and short-circuit faults, making the breaker suitable for demanding industrial, commercial and infrastructure power distribution applications.
With a 3200 A rated current, three-pole configuration and withdrawable moving-part construction, the E3S3200 is suited to main switchboards and high-current distribution systems where maintainability is important. The E3S performance level provides rated ultimate and service short-circuit breaking capacities of 75 kA at 415 V AC, together with short-time withstand ratings of 75 kA for 1 s and 65 kA for 3 s.
Air circuit breakers such as the ABB SACE Emax E3S3200 provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The electronic trip unit monitors electrical current and initiates circuit-breaker operation when configured protection thresholds are exceeded, helping protect cables, switchgear and connected electrical equipment against damaging overloads and short circuits.
The PR122/P-LSI release provides three levels of overcurrent protection for effective coordination within electrical distribution systems. Long-time protection responds to sustained overloads, short-time protection enables a controlled response to short-circuit conditions for improved selectivity, and instantaneous protection provides rapid interruption of severe short-circuit currents. The withdrawable construction also enables the breaker moving part to be removed from its associated fixed part for maintenance or replacement.
| Series | SACE Emax E3 |
|---|---|
| ABB order code | 1SDA056324R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E3S |
| Rated current | 3200 A |
| Rated uninterrupted current | 3200 A |
| Rated operational current | 3200 A |
| Number of poles | 3 |
| Execution | Withdrawable |
| Component | Moving part (MP) |
| Trip unit | PR122/P-LSI |
| Release rating | R3200 |
| Release type | Electronic overcurrent release |
| Protection functions | LSI |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Rated ultimate short-circuit breaking capacity at 415 V AC | 75 kA |
| Rated service short-circuit breaking capacity at 415 V AC | 75 kA |
| Rated short-time withstand current (1 s) | 75 kA |
| Rated short-time withstand current (3 s) | 65 kA |
| Power loss | 570 W |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Electrical durability at ≤440 V | 6000 cycles |
| Electrical durability at 500–690 V | 5000 cycles |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 432 × 461 × 396.5 mm |
| Net weight | 64 kg |
| EAN | 8015644576646 |
| Customs tariff number | 85362090 |
The ABB 1SDA056324R1 is a SACE Emax E3S3200 air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits.
The E3S3200 has a rated uninterrupted current of 3200 A, making it suitable for demanding high-current low-voltage power distribution applications.
The PR122/P-LSI electronic overcurrent release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
The E3S performance level provides rated ultimate and service short-circuit breaking capacities of 75 kA at 415 V AC, together with short-time withstand ratings of 75 kA for 1 s and 65 kA for 3 s.
The 1SDA056324R1 is a withdrawable three-pole circuit breaker moving part, allowing it to be withdrawn from its associated fixed part for inspection, servicing or replacement.
ABB SACE Emax air circuit breakers are designed for dependable protection and control of low-voltage electrical distribution systems, combining high-current switching capability with advanced electronic overcurrent protection for demanding industrial, commercial and infrastructure applications.