1SDA056321R1 ABB E3S 3200 PR121/P-LSI 3200 A 3-Pole Withdrawable Air Circuit Breaker

1SDA056321R1 ABB E3S 3200 PR121/P-LSI 3200 A 3-Pole Withdrawable Air Circuit Breaker

ABB 1SDA056321R1 E3S 3200 is a 3200 A three-pole withdrawable SACE Emax air circuit breaker moving part with a PR121/P-LSI R3200 electronic overcurrent release for high-current low-voltage power distribution protection.

SKU: 1SDA056321R1Alt SKU: E3S3200MPN: 1SDA056321R1
Price
List Price £28,704.11 ex VAT
Your Price (ex VAT) Save 25%
£21,528.08 25% OFF
You save £7,176.03 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £21,528.08
Trade pricing is personalised to your account

Manufacturer Lead Time

£21,528.08

Why Choose the ABB E3S 3200 PR121/P-LSI Air Circuit Breaker?

The ABB E3S 3200 PR121/P-LSI, order code 1SDA056321R1, is a high-performance SACE Emax air circuit breaker moving part designed for switching and protection of high-current low-voltage power distribution systems. This three-pole withdrawable version has a rated uninterrupted current of 3200 A and combines the E3S breaker platform with a PR121/P-LSI R3200 electronic overcurrent release.

The PR121/P-LSI R3200 electronic trip unit provides long-time, short-time and instantaneous protection. These LSI functions protect against sustained overloads and short-circuit faults while allowing coordinated protection within industrial and commercial low-voltage distribution networks.

The E3S performance level provides a rated ultimate short-circuit breaking capacity of 75 kA at 415 V AC and a rated short-time withstand current of 75 kA for 1 s. Its withdrawable moving-part configuration is designed for use with the corresponding E3 fixed part, supporting isolation and servicing in critical switchgear installations.

Key Advantages

  • High-current 3200 A SACE Emax air circuit breaker moving part.
  • PR121/P-LSI R3200 electronic overcurrent release for dependable protection.
  • LSI functions provide long-time, short-time and instantaneous protection.
  • Three-pole withdrawable configuration supports serviceable switchgear installations.
  • 75 kA short-circuit breaking capacity across the specified AC voltage range up to 690 V AC.
  • Four auxiliary contacts and open/closed position indication support switchboard signalling and control.

Key Features

  • ABB SACE Emax E3S series.
  • 3200 A rated uninterrupted current.
  • 690 V AC rated voltage.
  • PR121/P-LSI R3200 electronic trip unit.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Three-pole construction.
  • Withdrawable moving part (W MP) execution.
  • 75 kA rated ultimate short-circuit breaking capacity at 415 V AC.
  • 75 kA rated short-time withstand current for 1 s.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Withdrawable LSI Protection for High-Current Distribution

The PR121/P-LSI release provides three complementary protection functions for high-current electrical networks. Long-time protection responds to sustained overloads, short-time protection allows coordinated tripping for short-circuit conditions, and instantaneous protection provides rapid interruption when severe fault currents exceed the configured threshold.

The withdrawable moving-part design allows the breaker to operate with the corresponding fixed part in a serviceable switchgear arrangement. This configuration is well suited to critical distribution systems where isolation, inspection and maintenance are important, while the E3S performance level provides substantial fault-interruption capability for demanding installations.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Transformer-fed low-voltage distribution circuits.
  • Withdrawable high-current switchgear assemblies.

Technical Specifications

Series SACE Emax E3
Order code 1SDA056321R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Rated uninterrupted current (Iu) 3200 A
Rated voltage (Ur) 690 V
Number of poles 3
Execution Withdrawable moving part (W MP)
Trip unit PR121/P-LSI R3200 electronic overcurrent release
Protection functions Long-time, short-time and instantaneous
Release type Electronic
Short-circuit performance level S
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 75 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 75 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 75 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Product net width 432 mm
Product net height 461 mm
Standard IEC
EAN 8015644576615
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA056321R1 used for?

It is a 3200 A three-pole SACE Emax air circuit breaker moving part designed for switching and overcurrent protection in high-current low-voltage power distribution systems.

What trip unit is fitted to the ABB 1SDA056321R1?

The breaker is fitted with an ABB PR121/P-LSI R3200 electronic overcurrent release.

What protection functions does the PR121/P-LSI provide?

The PR121/P-LSI provides long-time, short-time and instantaneous protection against overload and short-circuit conditions.

Is the ABB 1SDA056321R1 fixed or withdrawable?

The 1SDA056321R1 is a three-pole withdrawable moving part designed for use with the corresponding ABB E3 fixed part.

What is the short-circuit breaking capacity of the E3S 3200?

The E3S 3200 has a rated ultimate short-circuit breaking capacity of 75 kA at 415 V AC, with 75 kA also specified at 690 V AC.

Trusted Low-Voltage Protection from ABB

ABB SACE Emax air circuit breakers provide high-current switching and electronic overcurrent protection for demanding low-voltage distribution systems, with withdrawable configurations supporting maintainable and serviceable switchgear installations.