ABB E3S3200PR121/P-LSI is a 3200 A four-pole fixed SACE Emax air circuit breaker with rear horizontal terminals and a PR121/P-LSI R3200 electronic trip unit providing long-time, short-time and instantaneous overcurrent protection.
£22,803.38
The ABB E3S3200PR121/P-LSI is a high-performance 3200 A four-pole air circuit breaker designed for reliable switching and overcurrent protection in demanding low-voltage power distribution systems. Part of the established ABB SACE Emax New Emax series, this E3S breaker combines robust high-current switching capability with the PR121/P-LSI electronic overcurrent release.
The PR121/P-LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. These LSI functions help safeguard cables, busbars, switchboards and connected electrical equipment against sustained overloads and short-circuit faults while supporting selective protection and coordination in industrial, commercial and infrastructure distribution networks.
With a rated current of 3200 A, a four-pole fixed configuration and rear horizontal terminals, ABB order code 1SDA056313R1 is designed for integration into high-current low-voltage switchboards. The breaker incorporates a PR121/P-LSI R3200 overcurrent release, four auxiliary contacts and circuit-breaker open/closed position indication for monitoring and control integration.
Air circuit breakers such as the ABB E3S3200 provide switching and overcurrent protection for high-current low-voltage distribution circuits. The electronic trip release monitors circuit conditions and initiates breaker operation when configured protection thresholds are exceeded, helping protect cables, busbars, switchboards and connected electrical equipment against damaging overload and short-circuit currents.
The PR121/P-LSI release combines long-time overload, short-time short-circuit and instantaneous short-circuit protection within a single electronic trip system. Together with the 3200 A four-pole E3S configuration, high short-circuit capability and fixed rear-horizontal-terminal construction, this breaker is well suited to critical main distribution and high-current feeder applications.
| Series | SACE Emax / New Emax |
|---|---|
| Type designation | E3S32 |
| ABB order code | 1SDA056313R1 |
| Extended product type | E3S3200PR121/P-LSIIn=3200A4pFHR |
| Product type | Air circuit breaker |
| Frame | E3S |
| Short-circuit performance level | S |
| Rated current | 3200 A |
| Number of poles | 4 |
| Current type | AC |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Rated ultimate short-circuit breaking capacity | 75 kA |
| Rated service short-circuit breaking capacity | 75 kA |
| Rated short-time withstand current | 75 kA for 1 s; 65 kA for 3 s |
| Execution | Fixed |
| Terminal arrangement | Rear horizontal terminals (HR) |
| Trip unit | PR121/P-LSI |
| Release type | Electronic |
| Overcurrent release rating | R3200 |
| Protection functions | L, S and I |
| Long-time overload protection | Yes |
| Short-time short-circuit protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Mechanical durability | 20,000 cycles |
| Net weight | 76 kg |
| EAN | 8015644576530 |
| HS code | 85362090 |
| Standard | IEC |
It is a 3200 A four-pole air circuit breaker designed for switching and protecting high-current low-voltage AC power distribution circuits in industrial, commercial and infrastructure switchboards.
The PR121/P-LSI electronic trip unit provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
The E3S configuration provides high short-circuit performance, with a rated ultimate short-circuit breaking capacity of 75 kA and a rated short-time withstand current of 75 kA for 1 s.
ABB order code 1SDA056313R1 is a fixed four-pole SACE Emax air circuit breaker equipped with rear horizontal terminals.
The breaker uses rear horizontal terminals and is fitted with four auxiliary contacts together with circuit-breaker open/closed position indication.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial low-voltage distribution systems, combining robust high-current switching technology with configurable electronic protection for dependable operation in demanding electrical installations.