1SDA056308R1 ABB E3S3200 PR122/P-LSI 3200A 3-Pole Fixed Air Circuit Breaker

1SDA056308R1 ABB E3S3200 PR122/P-LSI 3200A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA056308R1 is a SACE Emax E3S3200 three-pole fixed air circuit breaker rated at 3200 A with rear horizontal terminals and a PR122/P-LSI electronic overcurrent release for high-current low-voltage circuit protection.

SKU: 1SDA056308R1MPN: 1SDA056308R1
Price
List Price £23,621.93 ex VAT
Your Price (ex VAT) Save 25%
£17,716.45 25% OFF
You save £5,905.48 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £17,716.45
Trade pricing is personalised to your account

Manufacturer Lead Time

£17,716.45

Why Choose the ABB E3S3200 PR122/P-LSI 3200A 3-Pole Air Circuit Breaker?

The ABB E3S3200 PR122/P-LSI, order code 1SDA056308R1, is a high-performance SACE Emax air circuit breaker (ACB) designed for switching and protection in high-current low-voltage electrical distribution systems. As part of the ABB SACE Emax E3 series, this three-pole fixed circuit breaker combines a 3200 A rated uninterrupted current with the PR122/P-LSI electronic overcurrent release.

The PR122/P-LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. This LSI configuration supports selective coordination and dependable protection against sustained overloads and short-circuit faults, making the breaker suitable for demanding industrial, commercial and infrastructure power distribution applications.

With a 3200 A rated current, three-pole configuration and fixed construction with rear horizontal terminals, the E3S3200 is suited to main switchboards and high-current distribution systems. Its E3S performance level provides rated ultimate and service short-circuit breaking capacities of 75 kA at 415 V AC, together with short-time withstand ratings of 75 kA for 1 s and 65 kA for 3 s.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker for low-voltage power distribution.
  • 3200 A rated uninterrupted current for demanding high-current installations.
  • Three-pole configuration for three-phase electrical distribution systems.
  • Advanced PR122/P-LSI electronic overcurrent release.
  • Long-time, short-time and instantaneous overcurrent protection.
  • 75 kA ultimate and service short-circuit breaking capacity at 415 V AC.
  • High short-time withstand capability supports selective protection and system coordination.
  • Fixed construction with rear horizontal terminals for permanent switchboard integration.

Key Features

  • ABB SACE Emax E3S3200 air circuit breaker.
  • 3200 A rated uninterrupted current.
  • Three-pole (3P) configuration.
  • PR122/P-LSI electronic overcurrent release rated R3200.
  • Long-time overload protection (L).
  • Short-time short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Fixed (F) installation.
  • Rear horizontal (HR) terminals.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 75 kA rated ultimate short-circuit breaking capacity at 415 V AC.
  • 75 kA rated service short-circuit breaking capacity at 415 V AC.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Reliable Circuit Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E3S3200 provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The electronic trip unit monitors current conditions and initiates circuit-breaker operation when configured protection thresholds are exceeded, helping protect cables, switchgear and connected electrical equipment from damaging overloads and short circuits.

The PR122/P-LSI release provides three levels of overcurrent protection for effective coordination within electrical distribution systems. Long-time protection responds to sustained overloads, short-time protection enables a controlled response to short-circuit conditions for improved selectivity, and instantaneous protection provides rapid interruption of severe short-circuit currents.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing and process facilities.
  • High-current incomer and feeder protection.
  • Transformer and generator distribution systems.

Technical Specifications

Series SACE Emax E3
ABB order code 1SDA056308R1
Product group 310513-New Emax
Product type Air circuit breaker
Frame / performance level E3S
Rated current 3200 A
Rated uninterrupted current 3200 A
Rated operational current 3200 A
Number of poles 3
Version Fixed
Terminal arrangement Rear horizontal
Trip unit PR122/P-LSI
Release rating R3200
Release type Electronic overcurrent release
Protection functions LSI
Long-time protection L
Short-time protection S
Instantaneous protection I
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated ultimate short-circuit breaking capacity at 220–230 V AC 75 kA
Rated ultimate short-circuit breaking capacity at 380–440 V AC 75 kA
Rated ultimate short-circuit breaking capacity at 500 V AC 75 kA
Rated ultimate short-circuit breaking capacity at 660–690 V AC 75 kA
Rated service short-circuit breaking capacity at 220–230 V AC 75 kA
Rated service short-circuit breaking capacity at 380–440 V AC 75 kA
Rated service short-circuit breaking capacity at 500 V AC 75 kA
Rated service short-circuit breaking capacity at 660–690 V AC 75 kA
Rated short-time withstand current (1 s) 75 kA
Rated short-time withstand current (3 s) 65 kA
Power loss 330 W
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Electrical durability at ≤440 V 6000 cycles
Electrical durability at 500–690 V 5000 cycles
Electrical operating frequency 20 cycles per hour
Mechanical durability 20,000 cycles
Mechanical operating frequency 60 cycles per hour
Dimensions (W × H × D) 404 × 418 × 302 mm
Net weight 60 kg
EAN 8015644576486
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA056308R1 used for?

The ABB 1SDA056308R1 is a SACE Emax E3S3200 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution circuits.

What is the rated current of the ABB E3S3200 PR122/P-LSI?

The E3S3200 has a rated uninterrupted current of 3200 A, making it suitable for high-current low-voltage power distribution applications.

What protection functions does the PR122/P-LSI trip unit provide?

The PR122/P-LSI electronic overcurrent release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.

What is the breaking capacity of the ABB E3S3200?

The E3S3200 has rated ultimate and service short-circuit breaking capacities of 75 kA at 415 V AC, together with short-time withstand ratings of 75 kA for 1 s and 65 kA for 3 s.

Is the ABB 1SDA056308R1 fixed or withdrawable?

The 1SDA056308R1 is a fixed three-pole air circuit breaker fitted with rear horizontal terminals for permanent integration into low-voltage switchboards and power distribution equipment.

Trusted for Critical Power Distribution

ABB SACE Emax air circuit breakers are designed for dependable protection and control of low-voltage electrical distribution systems, combining high-current switching capability with advanced electronic overcurrent protection for demanding industrial, commercial and infrastructure applications.